Plan Review Details - Permit 17080170
Plan Review Stops For Permit 17080170
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 09:52 Rev Time 0.00
Received By cthroop Date 2017-12-21 Time 16:29 Sent To  
Notes
2017-12-22 09:53:19PROVISO FOR PRODUCT APPROVALS FOR FRENCH DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By cthroop Date 2017-08-29 Time 13:29 Rev Time 0.00
Received By cthroop Date 2017-08-28 Time 07:21 Sent To M
Notes
2017-08-29 13:40:46BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEPERATE PERMIT REQUIRED FOR DETACHED GARAGE. BOTH
 STRUCTURES MAY BE ON A SINGLE SET OF PLANS.
 2. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR NEW ROOFING SYSTEM COMPONENTS.
 3. PROVIDE ENERGY SUBMITTAL.
 4. PROVIDE PRODUCT APPROVALS, REVIEWED AND APPROVED IN
 WRITING BY DESIGNER AND MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE R-10 WALL INSULATION AND THE
 POLYISO FLOOR INSULATION.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 - OR -
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR AND
 INSULATION SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-11 Cont ID  
Sent By jpearson Date 2017-12-11 Time 10:56 Rev Time 0.00
Received By jpearson Date 2017-12-11 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By jpearson Date 2017-08-22 Time 13:18 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 13:18 Sent To  
Notes
2017-08-22 13:18:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SMOKE ALARM IS MISSING IN MASTER BEDROOM AND THE
 AREA ADJACENT TO THE MASTER BEDROOM, PROVIDE
 CORRECITON. FBC RE314.3
 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE3903.3
 3. FOR THE AHU, A LUMINAIRE CONTROLLED BY A SWITCH
 LOCATED AT THE REQUIRED PASSAGEWAY OPENING AND A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT OR NEAR THE
 APPLIANCE LOCATION. FBC RE M1305.1.3.1
 4. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE
 CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER
 CODE. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2); FBC RE3703.2
 5. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7
 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 7. PROVIDE CORRECTION FOR AFCI NOTE. NOTE CURRENTLY
 STATES THAT ALL "RECEPTACLES ..... SHALL HAVE AFCI
 PROTECTION." CODE STATES: "ALL 120-VOLT, SINGLE PHASE,
 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION". NEC 210.12; FBC
 RE3902.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-11-29 Cont ID  
Sent By destabro Date 2017-11-29 Time 10:53 Rev Time 0.00
Received By destabro Date 2017-11-29 Time 10:53 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By destabro Date 2017-08-22 Time 10:28 Rev Time 0.00
Received By destabro Date 2017-08-22 Time 10:28 Sent To B
Notes
2017-08-22 10:30:398/22/2017 - CONTRIBUTING PROPERTY TO THE CENTRAL PARK
 HISTORIC DISTRICT. HOUSE WILL BE RESTORED TO ORIGINAL
 CONDITION VIA REPAIR AND SOME REPLACEMENT IN-KIND.
 EXISTING WINDOWS ARE NOT ORIGINAL - REPLACEMENTS OF 3
 OR 4/-1 LIGHT CRAFTSMAN STYLE, WHITE ALUMINUM FRAME
 MEET DESIGN GUIDELINES FOR HISTORIC DISTRICT. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 09:53 Rev Time 0.00
Received By cthroop Date 2017-11-20 Time 13:37 Sent To I
Notes
2017-11-21 13:38:11R30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-30 Cont ID  
Sent By hmoser Date 2017-08-30 Time 10:07 Rev Time 0.00
Received By hmoser Date 2017-08-03 Time 10:42 Sent To  
Notes
2017-08-04 10:42:45R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By hmoser Date 2017-12-13 Time 15:31 Rev Time 0.00
Received By hmoser Date 2017-12-13 Time 15:10 Sent To  
Notes
2017-12-13 15:30:52PLAN PASS PROVISO
 APPLICATION CALL FOR A AIR CONDITIONING CHANGE OUT.
 THERE IS NO INFORMATION FOR THE CHANGE OUT ON THE PLAN.
 ADDITIONAL PERMIT REQUIRED FOR THE CHANGE OUT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By hmoser Date 2017-08-30 Time 10:07 Rev Time 0.00
Received By hmoser Date 2017-08-30 Time 09:52 Sent To  
Notes
2017-08-30 10:07:01NO MECHANICAL PLAN SUBMITTED.
  
 HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-04 Cont ID  
Sent By thunt Date 2017-12-04 Time 06:58 Rev Time 0.00
Received By thunt Date 2017-12-04 Time 06:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By thunt Date 2017-08-23 Time 06:56 Rev Time 0.00
Received By thunt Date 2017-08-23 Time 06:34 Sent To  
Notes
2017-08-23 06:48:56SEPARATE PERMIT, REVIEW, AND PLANS REQUIRED FOR GAS
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1, 614.5 (CLOTHES DRYERS) OR
 2014 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2014 FBC-FUEL GAS SECS.
 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4, 10.5 OF NFPA 96-08.
  
 13. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT,
 SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS
 SYSTEM.
 14). SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 15) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK.
  
 16) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3.
  
 17) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 18) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4. I
  
 19) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 20) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 09:50 Rev Time 0.00
Received By cthroop Date 2017-12-21 Time 16:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By cthroop Date 2017-08-29 Time 13:41 Rev Time 0.00
Received By cthroop Date 2017-08-29 Time 13:41 Sent To  
Notes
2017-08-29 13:42:47BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By destabro Date 2017-08-22 Time 10:27 Rev Time 0.00
Received By destabro Date 2017-08-22 Time 10:27 Sent To AIPP
Notes
2017-08-22 10:28:408/22/2017 - NEW A/C UNIT AND CONCRETE PAD MEET SIDE
 SETBACK REQUIREMENTS. EXISTING REAR PAVERS AND GARAGE
 WILL BE REPAIRED TO MAINTAIN NONCONFORMITIES. DLE