Plan Review Details - Permit 17080149
Plan Review Stops For Permit 17080149
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By tklarge Date 2017-09-05 Time 10:14 Rev Time 0.00
Received By tklarge Date 2017-09-05 Time 10:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By tklarge Date 2017-08-09 Time 13:23 Rev Time 0.00
Received By tklarge Date 2017-08-09 Time 12:05 Sent To  
Notes
2017-08-09 13:07:571) SHOW THE BTU LOAD FOR EACH OF THE TIKI TORCHES. THE
 BTU LOAD OF EACH TIKI TORCH SHALL BE ADDED TO THE TOTAL
 LOAD OF THE GAS SYSTEM. 2014 FBC-FUEL GAS SEC. 401.4.
 2) SHOW THE SIZE OF THE EXISTING PIPE TO THE TIKI
 TORCHES TO ENSURE THE EXISTING SYSTEM IS SIZED PROPERLY
 AND TO DETERMINE IF IT HAS THE ADEQUATE CAPACITY FOR
 THE BTU LOAD. 2014 FBC- FUEL GAS SEC.401.4, 401.8.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 NEW APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED.
 FGC SEC.301.3.
 4) SHOW THE SIZE AND TYPE OF PIPE DOWNSTREAM OF THE
 REGULATOR AT THE TANKLESS WATER HEATERS.
 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE FOR
 THE LOW PRESSURE SYSTEM.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-05 Cont ID  
Sent By tklarge Date 2017-09-05 Time 10:14 Rev Time 0.00
Received By tklarge Date 2017-09-05 Time 10:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-09 Cont ID  
Sent By tklarge Date 2017-08-09 Time 13:23 Rev Time 0.00
Received By tklarge Date 2017-08-02 Time 10:54 Sent To  
Notes
2017-08-03 10:54:19PLUMB <5K