Plan Review Details - Permit 17080096
Plan Review Stops For Permit 17080096
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By rmcdouga Date 2017-08-24 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2017-08-24 Time 07:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-14 Cont ID  
Sent By rmcdouga Date 2017-08-14 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2017-08-10 Time 11:17 Sent To  
Notes
2017-08-14 09:29:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE EXTERIOR DOOR PRODUCT APPROVAL THAT WAS
 SUBMITTED (FL10537-R2) IS NOT THE ONE THAT IS SPECIFIED
 ON THE PLANS (FL15227-R2). PLEASE CLARIFY. FBC
 107.3.4.1
  
 2) THE REQUIRED COMPONENT AND CLADDING PRESSURES FOR
 THE NEW EXTERIOR DOORS ARE NOT SPECIFIED ON THE PLANS.
 FBC-R301.2.1
  
 3) FBC-R310.1 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 REQUIRED FROM ROOMS USED FOR SLEEPING. THIS IS AN
 EXISTING SINGLE FAMILY DWELLING AND FBC EXISTING
 BUILDING SECTION 704.1 HAS AN EXECPTION THAT ALLOWS A
 MAXIMUM 5 PERCENT REDUCTION IN THE CLEAR OPENING
 DIMENSIONS OF REPLACEMENT WINDOWS AS LONG AS THE
 PORTION OF THE BUILDING IS NOT ALTERED SUCH THAT THE
 BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITION
 PER SECTION 701.2. SHOW ON THE PLANS HOW THE NEW
 WINDOWS WILL COMPLY WITH SECTION 701.2 OR HOW THE
 OPENINGS WILL BE ALTERED TO COMPLY WITH FBC-R310.1.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 16:39 Rev Time 0.00
Received By jpearson Date 2017-08-23 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By jpearson Date 2017-08-07 Time 14:05 Rev Time 0.00
Received By jpearson Date 2017-08-07 Time 14:05 Sent To  
Notes
2017-08-07 14:05:07CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; FBC 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION FOR RESIDENCE. NEC
 220; FBC RE3602.3
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-24 Cont ID  
Sent By rmcdouga Date 2017-08-24 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2017-08-22 Time 15:48 Sent To  
Notes
2017-08-23 15:48:36RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-14 Cont ID  
Sent By rmcdouga Date 2017-08-14 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2017-08-02 Time 10:57 Sent To  
Notes
2017-08-04 10:57:56R07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By rmcdouga Date 2017-08-24 Time 07:57 Rev Time 0.00
Received By rmcdouga Date 2017-08-24 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-10 Cont ID  
Sent By rmcdouga Date 2017-08-10 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2017-08-10 Time 13:23 Sent To  
Notes
2017-08-10 15:26:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. SHOW ALL OF
 THE DUCT WORK ON THE PLANS INCLUDING THETRUNK LINE.
 SHOW THE RETURN AIR TO THE AIRHANDLER ON THE PLANS. IN
 ORDER TO PROVIDE CLARITY THE MECHANICAL PLANS SHOW BE
 ON A SEPARATE FLOOR PLAN.
  
 2) FBC ENERGY CONSERVATION R403.2.1 REQUIRES SUPPLY
 DUCTS IN ATTICS TO HAVE R-8 INSULATION. PLEASE CORRECT
 THE PLANS.
  
 3) ENERGY COMPLIANCE FORM R405-2014 IS REQUIRED TO HAVE
 THE PREPARER'S NAME AND THE SIGNATURE OF THE
 OWNER/AGENT ON THE FORM. FBC ENERGY CONSERVATION R103
  
 4) THE FORM STATES THAT THIS IS WORST CASE. WORST CASE
 IS USED WHEN THE SAME MODEL HOME WILL BE BUILT ON
 DIFFERENT LOTS WITH DIFFERENT ORIENTATIONS. THIS IS NOT
 THE CASE WITH THIS PROJECT. THEREFORE, THIS IS NOT
 WORST CASE AND IS REQUIRED TO SHOW THE ACTUAL
 ORIENTATION OF THE HOME. FBC ENERGY CONSERVATION
 R405.4.2
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-08-10 Cont ID  
Sent By rmcdouga Date 2017-08-10 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2017-08-10 Time 11:27 Sent To  
Notes
2017-08-10 11:28:59NO PLUMBING WORK IS INDICATED ON THE PLANS. A SEPARATE
 PERMIT, APPLICATION AND REVIEW IS REQUIRED.