Plan Review Details - Permit 17080040
Plan Review Stops For Permit 17080040
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-10 Cont ID  
Sent By shill Date 2017-10-10 Time 16:41 Rev Time 0.00
Received By shill Date 2017-10-10 Time 16:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By shill Date 2017-09-27 Time 12:09 Rev Time 0.00
Received By shill Date 2017-09-27 Time 12:05 Sent To  
Notes
2017-09-27 12:14:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENT FROM FIRST REVEW:
  
 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 2ND REVIEW - SPEC SHEET FOR PROFLEX MSC 90 WAS
 SUBMITTED. A LETTER DATED 8/27/14 FROM PROFLEX TO ME
 STATED THAT THEY DO NOT HAVE THE STC/IIC TESTS WITHOUT
 A DROPPED CEILING.
  
 WE DO HAVE THE TEST REPORTS FOR PROFLEX SUPERSIM 90 ON
 FILE.
  
 NEW COMMENT:
  
 2. VALUE IS TOO LOW FOR THE WORK PROPOSED, FBC 109. ALL
 PLANS RELATED TO THE PROPOSED RENOVATION ARE TO BE
 SUBMITTED WITH THIS SUBMITTAL AND THE VALUE OF ALL
 IMPROVEMENTS ARE TO BE INCLUDED, INCLUDING
 SUBCONTRACTORS AND MATERIAL PROVIDED BY OTHERS.
  
 3. A LETTER STATES THAT "A CHASE IS BEING RAISED". THE
 PROPOSED WORK IS NOT SHOWN ON THE PLANS, NO DETAIL
 PROVIDED. FBC 107, PLANS ARE TO SHOW SCOPE AND NATURE
 OF PROPOSED WORK. THE INDIVIDUAL TAKING RESPONSIBILITY
 FOR THE DESIGN IS TO SIGN THE PLAN. DEPENDING ON THE
 QUALITY OF THE RESUBMITTAL, IT IS POSSIBLE THAT A
 DESIGN PROFESSIONAL WILL BE REQUIRED TO PROVIDE A PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-04 Cont ID  
Sent By shill Date 2017-08-04 Time 07:55 Rev Time 0.00
Received By shill Date 2017-08-04 Time 07:55 Sent To  
Notes
2017-08-04 07:58:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-10-02 Cont ID  
Sent By jpearson Date 2017-10-02 Time 10:39 Rev Time 0.00
Received By jpearson Date 2017-10-02 Time 10:39 Sent To  
Notes
2017-10-02 10:39:28NOT REQUIRED UNDER THIS PERMIT NUMBER, APPROVED UNDER
 SEPARATE SUBMISSION. PERMIT # 17090458.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By jpearson Date 2017-08-08 Time 14:14 Rev Time 0.00
Received By jpearson Date 2017-08-08 Time 14:14 Sent To P
Notes
2017-08-08 14:12:38CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. IF THERE IS NOT ANY ELECTRICAL
 WORK INCLUDED WITH THIS PERMIT, STATE THAT ON PLAN. FS
 471.003(2)(H); 471.025; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-07 Cont ID  
Sent By scaldero Date 2017-08-07 Time 14:00 Rev Time 0.00
Received By scaldero Date 2017-08-07 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-10 Cont ID  
Sent By shill Date 2017-10-10 Time 16:41 Rev Time 0.00
Received By shill Date 2017-10-04 Time 09:58 Sent To  
Notes
2017-10-05 09:58:39RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-02 Time   Rev Time 0.00
Received By lmarchan Date 2017-09-22 Time 10:26 Sent To  
Notes
2017-09-25 10:26:56B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-15 Cont ID  
Sent By tklarge Date 2017-08-15 Time 06:29 Rev Time 0.00
Received By tklarge Date 2017-08-01 Time 13:26 Sent To  
Notes
2017-08-02 13:26:32B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-10 Cont ID  
Sent By ccole Date 2017-10-10 Time 12:49 Rev Time 0.00
Received By ccole Date 2017-10-10 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By ccole Date 2017-10-02 Time 14:43 Rev Time 0.00
Received By ccole Date 2017-10-02 Time 14:43 Sent To  
Notes
2017-10-02 14:46:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080040
 10/2/2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL PLAN SHOWING ALL PROPOSED
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS.
  
 2) SIGNATURE ON PLANS REQUIRED: ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE
 FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-09-18 Cont ID  
Sent By tklarge Date 2017-08-15 Time 06:29 Rev Time 0.00
Received By tklarge Date 2017-08-15 Time 06:24 Sent To  
Notes
***NONE***