Plan Review Details - Permit 17071238
Plan Review Stops For Permit 17071238
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By jleahy Date 2017-08-18 Time 14:42 Rev Time 0.00
Received By jleahy Date 2017-08-18 Time 14:41 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By jleahy Date 2017-08-02 Time 10:16 Rev Time 0.00
Received By jleahy Date 2017-08-02 Time 10:16 Sent To  
Notes
2017-08-02 10:20:04FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED RISER DIAGRAM
  
 NOTES STATE THAT THE MAIN IS 200A AND THE PANEL IS
 125A?
  
 SMOKE ALARMS WILL BE REQUIRED SEE FBC RESIDENTIAL R314.
  
 REPLACEMENT OUTLETS SHALL BE TAMPER RESISTANT AND
 PROTECTED BY AN ARC FAULT CIRCUIT INTERRUPTOR. PER
 406.4 (D)(1), AND (D)(5) OF THE 2011 NEC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-18 Cont ID  
Sent By jleahy Date 2017-08-18 Time 14:42 Rev Time 0.00
Received By jleahy Date 2017-08-16 Time 13:54 Sent To  
Notes
2017-08-17 13:54:41RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-02 Cont ID  
Sent By jleahy Date 2017-08-02 Time 10:20 Rev Time 0.00
Received By jleahy Date 2017-07-31 Time 11:21 Sent To  
Notes
2017-08-01 11:22:00ROUTED TO ELECTRICAL INBOX