Plan Review Details - Permit 17071168
Plan Review Stops For Permit 17071168
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-20 Cont ID  
Sent By skennedy Date 2017-09-20 Time 14:37 Rev Time 0.00
Received By skennedy Date 2017-09-20 Time 14:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-05 Cont ID  
Sent By rmcdouga Date 2017-09-05 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2017-09-05 Time 10:04 Sent To  
Notes
2017-09-05 17:06:20REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK ON THE PLANS AND THE PLUMBING
 PERMIT APPLICATION LISTS REPLACEMENT OF THE SHOWER
 LINER. THE FLOOR PLANS THAT WERE SUBMITTED SHOW
 BATHTUBS IN BOTH OF THE FULL BATHROOMS. THERE ARE NO
 SHOWERS SHOWN ON THE PLANS. PLEASE CLARIFY. FBC 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-04 Cont ID  
Sent By rmcdouga Date 2017-08-04 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2017-08-04 Time 09:46 Sent To  
Notes
2017-08-04 10:27:03REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE TWO COPIES OF AN ITEMIZED AND DETAILED SCOPE
 OF WORK. FBC 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By jpearson Date 2017-09-05 Time 07:03 Rev Time 0.00
Received By jpearson Date 2017-09-05 Time 07:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-01 Cont ID  
Sent By jpearson Date 2017-08-01 Time 14:51 Rev Time 0.00
Received By jpearson Date 2017-08-01 Time 14:51 Sent To  
Notes
2017-08-01 14:51:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE 2 COPIES OF ALL PLANS, ONLY ONE COPY OF THE
 RISER WAS PROVIDED. PLANS SHOULD BE A MINIMUM 1/8 SCALE
 PER WPB AMENDMENTS TO FBC. FBC 107.2.1, WPB AMENDMENT
 TO FBC 107.2.1.4
 2. EACH PAGE OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. FBC
 107.2.1, FS 471
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3,
 FBC 107.2.1
 4. PROVIDE FULL FLOOR PLAN SHOWING ALL OUTLETS TO CODE.
 MARK AS NEW OR EXISTING AS APPLICABLE. FBC 107.2.1
 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-05 Cont ID  
Sent By rmcdouga Date 2017-09-05 Time 17:07 Rev Time 0.00
Received By rmcdouga Date 2017-08-31 Time 09:44 Sent To  
Notes
2017-09-01 09:45:03RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-04 Cont ID  
Sent By rmcdouga Date 2017-08-04 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2017-07-28 Time 13:18 Sent To  
Notes
2017-07-31 13:18:21R02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-08-04 Cont ID  
Sent By rmcdouga Date 2017-08-04 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2017-08-04 Time 09:48 Sent To  
Notes
2017-08-04 09:50:43NO MECHANICAL SUB-PERMIT WAS SUBMITTED AND NO
 MECHANICAL WORK IS SPECIFIED. A SEPARATE PERMIT,
 APPLICATION AND REVIEW IS REQUIRED FOR MECHANICAL.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-09-20 Cont ID  
Sent By skennedy Date 2017-09-20 Time 14:37 Rev Time 0.00
Received By skennedy Date 2017-09-20 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-09-05 Cont ID  
Sent By rmcdouga Date 2017-09-05 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2017-09-05 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-04 Cont ID  
Sent By rmcdouga Date 2017-08-04 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2017-08-04 Time 09:47 Sent To  
Notes
2017-09-05 17:07:33SEE BUILDING REVIEW COMMENTS.