Plan Review Details - Permit 17071121
Plan Review Stops For Permit 17071121 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2017-08-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-08-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-08-16 |
Time |
16:54 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-07-31 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-07-31 |
Time |
10:25 |
Sent To |
M |
|
Notes |
2017-07-31 11:29:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) FLEX DROPS ARE INDICATED ON THE PLAN SHEET. THERE IS | | NO INDICATION OF HOW MANY FLEX DROPS OR WHERE THE FLEX | | DROPS ARE LOCATED. NO FLEX DROP SPECS WERE PROVIDED. | | | | A REVIEW OF THE EOR HYDRALIC DOCUMENTS IS WARRANTED DUE | | TO THE HIGHER FRICTION LOSS INHERENT OF FLEX DROPS. | | | | PLEASE PROVIDE A REVIEW OF THE HYDRALIC CALCULATIONS | | THAT INCLUDES THE PROPOSED FLEX DROPS, HOW MANY, THE | | PROPOSED LOCATIONS AND FLEX DROP SPEC SHEETS. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-08-22 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-08-22 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-08-15 |
Time |
14:52 |
Sent To |
|
|
Notes |
2017-08-16 14:52:18 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-08-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-08-11 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-07-27 |
Time |
13:08 |
Sent To |
|
|
Notes |
2017-07-28 13:08:16 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2017-08-22 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-08-22 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-08-22 |
Time |
14:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-08-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-08-11 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-08-11 |
Time |
13:33 |
Sent To |
|
|
Notes |
2017-08-11 13:33:49 | SEE FIRE COMMENTS. HM. |
|
|
|