Plan Review Details - Permit 17071073
Plan Review Stops For Permit 17071073
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By   Date 2017-10-06 Time   Rev Time 0.00
Received By   Date 2017-10-04 Time   Sent To  
Notes
2017-10-06 10:23:50HOLD ON PERMIT ISSUANCE UNTIL THE CITY IS IN RECEIPT OF
 JAMES BARRETT BN2612 RESUME'.
  
 ROOFING PRODUCT APPROVALS BEING RETURNED, REQUIRES
 SIGNED AND SEALED ENHANCED FASTENING BY ENGINEER,
 SUBMITTED NOT SIGNED AND SEALED.
  
  
 BUILDING PLAN REVIEW
 W. P. B. REVISION: 17071073
 W. P. B. PERMIT: 16071078
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. OCT. 04/ 2017
 ACTION: BUILDING PROVISO/ APPROVED WITH EXCEPTION
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THEIR PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEES.
  
 1) SHEET A-102A
 1A) REVISION REQUIRED. CAPTION DORMS REQUIRE 1 HOUR
 FIRE RATED WALLS, SEE WALL TAG (2) UL U-465. SHOWERS
 SHOW A WALL TAG (5) NOT FIRE RATED, DOES NOT GO ALL THE
 WAY TO THE DECK ABOVE. 2014 FBC-B 420.2 / 708.3.
  
 1B) REVISION REQUIRED. COMMON WALL BETWEEN DORM (5) AND
 LAUNDRY WALL TAG (10), PLEASE REFER BACK TO WALL
 IDENTIFICATION TAG (2) AND UL LISTING U465 A 1 HOUR
 FIRE RATED WALL TYPE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By jwitmer Date 2017-08-07 Time 15:10 Rev Time  
Received By jwitmer Date 2017-08-07 Time 08:28 Sent To  
Notes
2017-08-07 15:09:57BUILDING PLAN REVIEW
 W. P. B. REVISION: 17071073
 W. P. B. PERMIT: 16071078
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. AUGUST 07/ 2017
 ACTION: DENIED
  
 1) THE CHANGE/ REVISION FROM CBS (CONCRETE, BLOCK &
 STEEL) CONSTRUCTION TO TILT WALL CONSTRUCTION WILL
 REQUIRE A RESIDENT INSPECTOR ON SITE THRU THE ROOF
 FRAMING AND DOOR DECK INSPECTIONS.
 THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR
 PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION/ TILT WALL
 CONSTRUCTION.
  
 1A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS E-MAILED TO:
 [email protected] AT 08/07/2017 / 03:09 PM.
 [email protected] 08/31/17 / 08:15 AM.
  
 1B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1D) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED.
  
 1E) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) SHEET LS-101MAKES REFERENCES TO TABLE 601 AND NO
 FIRE RATING OF FLOOR SYSTEMS. THIS IS TRUE BUT THERE IS
 NO REFERENCE TO THE REQUIREMENT OF FIRE RATED FLOOR
 ASSEMBIES FOR R2 SLEEPING ROOMS UNDER SECTION 420.3
 HORIZONTAL SEPARATION AND THE REQUIRED IN FBC-B 711.3
 AND TABLE 707.3.10.
 3) SHEET A-100 PLAN REVISION HAS A NOTE THAT THE 2ND
 FLOOR ASSEMBLY HAS BEEN CHANGED TO AN 8 INCH HOLLOW
 CORE SLAB PLEASE PROVIDE THE FIRE RATING OF THE 2ND
 FLOOR 8 INCH HOLLOW CORE SLAB ASSEMBLY IN ACCORDANCE
 WITH 420.3 HORIZONTAL SEPARATION AND THE REQUIRED IN
 FBC-B 711.3 AND TABLE 707.3.10. PLEASE NOTE SHEET S-000
 INDICATES THIS FLOOR SYSTEM IS ACTUALLY 6 INCH CONCRETE
 HOLLOW CORE PLANK WITH 2 INCHES OF TOPPING.
 DISCREPANCY IN PLANS.
  
 4A) SHEET A-101A, HAS A NEW NOTE ABOUT WHEEL CHAIR LIFT
 REQUIREMENTS. PLEASE SPECIFY IF THE INTENT IS TO USE A
 LULA, LIMITED USE/ LIMITED APPLICATION ELEVATOR
 CLASSIFIED BY ASTM A17.1 OR IF THE SPECIFICATION IS FOR
 A PLATFORM LIFT CLASSIFIED UNDER ASTM E A18.1. PLEASE
 NOTE IF THE INTENT IS TO USE A PLATFORM LIFT UNDER ASTM
 E A18.1 IN NEW CONSTRUCTION IT IS VERY LIMITED USES,
 THE 2014 FBC-ACCESSIBILITY CODE SECTION 296.7 HAS ONLY
 (5) EXCEPTIONS FOR NEW CONSTRUCTION. EXCEPTION 3 ALLOWS
 FOR NOT ALLOWED FOR PUBLIC USE BUT THE EXCEPTION ALSO
 STATES TO BE OCCUPIED BY NOT MORE THAN 5 OCCUPANTS.
  
 4B) THE CHANGE SHOWING A 4 INCH RECESS FOR LIFT MAYBE
 CHANGED WHEN THE MANUFACTURERS SHOP DRAWINGS ARE
 SUBMITTED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. LULA, LIMITED USE/ LIMITED APPLICATION
 ELEVATOR CLASSIFIED BY ASTM A17.1.
  
 5) SHEET A-102A HAS A NOTE THAT MOST CMU WALLS HAVE
 BEEN REPLACED. THIS SHEET SHOWS THE DORM ROOM CORRIDOR
 WALLS AND WALLS ADJACENT TO ANOTHER DORM WITH A WALL
 TAG TYPE 2 WALL. THE LEGEND IDENTIFIES THE WALLS AS A 1
 HOUR FIRE RATED WALL. SHEET -500 DOES NOT SHOW THE WALL
 TYPE 2 AS FIRE RATED. SEE SECTION 420.2 OF THE 2014
 FBC-B AND THE REQUIREMENT FOR FIRE PARTITIONS IN
 COMPLIANCE WITH 708.3.
  
 6) SHEET A-102 THE DOOR IDENTIFICATION TAGS ARE TURNED
 OFF ON THIS SHEET. THE 1ST FLOOR DOOR TAGS ARE TURNED
 ON. SHEET A-600 THE DOOR SCHEDULE FOR THE DOOR ROOM
 DOORS # 34, 35, 39-43 ALL ARE MISSING THE FIRE RATING
 OF THE DOORS, SEE ISSUED SET OF PLANS SHOW A DOOR
 CLOSER AND 45 MINUTE FIRE RATING, FBC-B TABLE 716.5.
 NOTE THIS IS NOT SHOWN AS A REVISION!!!
  
 7) SHEET A-600 1ST FLOOR DOORS MISSING FIRE RATINGS,
 05, 05A STAIR # 1, DOOR # 17 MISSING LOCATION, CAPTAINS
 OFFICE MISSING FIRE RATING AND REDUCED TO 2 FT.- 10
 INCHES, REQUIRES 3 FEET FBC-B 1008.1.1, STAIR # 2 AND
 2A MISSING CLOSER AND FIRE RATINGS TABLE 716.5. DOOR 19
 MISSING ALL INFORMATION, LEADS INTO A I HR. FIRE RATED
 SHAFT, CLOSER 1ST FLOOR AND 2ND FLOOR TABLE 716.5 .
 NOTE THIS IS NOT SHOWN AS A REVISION!!!
  
 8) SHEET A-103 SHOWS A NOTE FOR FIRE RATED UPPER
 DRYWALL CEILING THROUGH DORMS 1-5 BUT THERE IS NO NOTE
 FOR THE FIRE RATING OF THE (2) CAPTAINS DORM ROOM.
 WHERE DOES THE WALL FIRE RATINGS STOP IN THE CAPTAINS
 DORM WHY NO RATING OF THE CEILING IN THIS DORM?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. WALL RATINGS
 TO THE ROOF STRUCTURE NO REQUIRED CEILING RATING, IF
 THE DRYWALL CEILING IS RATED THEN A WALL DAMPER WOULD
 BE REQUIRED.
  
 9) A-104 HAS INCLUDED MORE SPECS FOR THE CARLISLE ROOF
 SYSTEM, PLEASE PRODUCE THE PRODUCT APPROVAL FOR THE
 LIGHTWEIGHT CONCRETE AND CARLISLE ROOF AT THE SAME
 TIME. BOTH SUBMITTALS WILL NEED TO AGREE ON THE VENTING
 FOR THE LIGHTWEIGHT CONCRETE. THE LIGHTWEIGHT CONCRETE
 AS WELL AS THE ROOFING MANUFACTURER WILL HAVE OPTIONS
 FOR VENTING OF THE LIGHTWEIGHT CONCRETE. PLEASE
 IDENTIFY WHICH OPTION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TERM "LEGAL" OR ?OR? ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 10) SHEET A-104A DETAIL # 9 AN OVERFLOW SCUPPER NEEDS
 TO HAVE A MINIMUM AND MAXIMUM THE BOTTOM OF THE SCUPPER
 CAN BE LOCATED ABOVE THE FINISH ROOF, SHOW COMPLIANCE
 WITH 2014 FBC-B 1503.4.2.1.
  
 11) TILT WALL PANEL WALL SYSTEM PLANS PN-1-PN19 ARE
 FROM A SPECIALTY ENGINEER. THE ENGINEER OF RECORD DOES
 NOT HAVE THEIR SHOP DRAWING STAMP OF APPROVAL ON THESE
 PLANS. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 12A) ONLY 2 SETS OF TILT WALL CALCULATIONS SUBMITTED 3
 ORIGINAL SIGNED AND SEALED REQUIRED AND TO BE REVIEWED
 BY THE ENGINEER OF RECORD FOR THE PROJECT BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 12B) THE 2 SETS OF TILT-UP PANEL CALCULATIONS
 COVERSHEET IS SIGNED AND SEALED, PLEASE NOTE THE
 COVERPAGE DOES NOT LIST HOW MANY PAGES ARE COVERED
 UNDER THIS REPORT. 61G15-23.002(2) FL. ADMIN. CODE. A
 COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET
  
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-02 Cont ID  
Sent By jpearson Date 2017-10-02 Time 16:05 Rev Time 0.00
Received By jpearson Date 2017-10-02 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By jleahy Date 2017-08-08 Time 09:19 Rev Time 0.00
Received By jpearson Date 2017-08-08 Time 09:19 Sent To  
Notes
2017-08-08 09:19:28CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SUBMITTAL LETTER STATES THAT ALL REVISONS HAVE BEEN
 CLOUDED AND TAGGED. ELECTRICAL SHEETS DO NOT SHOW ANY
 CHANGES. PROVIDE DESCRIPTION OF CHANGES TO SUBMITTED
 SHEETS AND CLOUD ANY CHANGES ON PLAN. FBC 107.2.1
 2. SHEETS E2.2, E3.1, E3.2 HAVE A NOTE THAT THE
 BUILDING IS AN "EXPOSED BLOCK BUILDING". IS THIS NOTE
 STILL RELEVANT? CLARIFY AND/OR CORRECT. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-09-28 Cont ID  
Sent By wjolin Date 2017-09-28 Time 12:19 Rev Time 0.00
Received By wjolin Date 2017-09-28 Time 12:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-02 Cont ID  
Sent By wjolin Date 2017-08-02 Time 10:26 Rev Time 0.00
Received By wjolin Date 2017-08-02 Time 09:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 10:32 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 10:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By tklarge Date 2017-08-22 Time 09:11 Rev Time 0.00
Received By tklarge Date 2017-08-22 Time 09:10 Sent To  
Notes
2017-08-22 09:11:401) THE REVISED PLUMBING PLANS/GAS PLAN APPEAR TO HAVE
 COPIED ENGINEERS SEALS AND SIGNATURES. PLEASE PROVIDE
 ORIGINAL SIGNED AND SEALED DRAWINGS IN ACCORDANCE WITH
 SECTION 61G15-23.001, 23.002 FAC.
 2) SUBMIT A NARRATIVE THAT ITEMIZES ALL CHANGES MADE TO
 THE GAS SYSTEM, AND PROVIDE CLOUDS AND SYMBOLS TO
 HIGHLIGHT THOSE CHANGES ON THE PLANS.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2017-09-25 Time 10:58 Sent To  
Notes
2017-09-26 10:59:06C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-22 Cont ID  
Sent By cpuell Date 2017-08-22 Time 16:44 Rev Time 0.00
Received By cpuell Date 2017-07-26 Time 09:30 Sent To  
Notes
2017-07-27 09:30:20C37

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-10 Cont ID  
Sent By ccole Date 2017-10-10 Time 11:38 Rev Time 0.00
Received By ccole Date 2017-10-02 Time 11:38 Sent To  
Notes
2017-10-10 09:52:46BASED ON THE REVISED NARRATIVE SUBMITTED VIA EMAIL ON
 10/10/17 THERE WERE NO CHANGES TO THE APPROVED
 MECHANICAL PLANS.
 CCOLE- 10/10/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By ccole Date 2017-08-11 Time 10:09 Rev Time 0.00
Received By ccole Date 2017-08-10 Time 13:37 Sent To  
Notes
2017-08-11 10:20:441ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17071073
 8/11/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED MEP PLANS APPEAR TO HAVE COPIED
 ENGINEERS SEALS AND SIGNATURES. PLEASE PROVIDE ORIGINAL
 SIGNED AND SEALED DRAWINGS IN ACCORDANCE WITH SECTION
 61G15-23.002 FAC.
  
 2) SUBMIT A NARRATIVE THAT ITEMIZES ALL CHANGES MADE TO
 EACH MECHANICAL PLAN SHEET, AND PROVIDE CLOUDS AND
 SYMBOLS TO HIGHLIGHT THOSE CHANGES ON THE PLANS.
  
 3) M2.2: IDENTIFY THE LOCATIONS OF THE FRESH AIR AND
 RANGE EXHAUST CHASES ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 10:32 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By tklarge Date 2017-08-22 Time 09:10 Rev Time 0.00
Received By tklarge Date 2017-08-17 Time 06:07 Sent To Z
Notes
2017-08-22 08:37:111) THE REVISED PLUMBING PLANS APPEAR TO HAVE COPIED
 ENGINEERS SEALS AND SIGNATURES. PLEASE PROVIDE ORIGINAL
 SIGNED AND SEALED DRAWINGS IN ACCORDANCE WITH SECTION
 61G15-23.001, 23.002 FAC.
 2) SUBMIT A NARRATIVE THAT ITEMIZES ALL CHANGES MADE TO
 EACH PLUMBING PLAN SHEET, AND PROVIDE CLOUDS AND
 SYMBOLS TO HIGHLIGHT THOSE CHANGES ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-104A - DETAIL #9 - SHOW THE SIZE DIMENSIONS
 OF THE SCUPPER. THE SCUPPER SHALL BE LOCATED PER FBC
 SEC. 1504.4.2.1.
 4) SHT. A-402A - DETAIL #9 - THE SHOWER CONTROLS FOR
 THE HANDICAP ACCESSIBLE SHOWER SHALL COMPLY WITH THE
 2014 FBC-ACCESSIBILITY SEC. 608.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By kmartin Date 2017-08-22 Time   Rev Time 0.00
Received By kmartin Date 2017-08-22 Time 15:53 Sent To I
Notes
***NONE***