Plan Review Details - Permit 17071021
Plan Review Stops For Permit 17071021
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-11-17 Cont ID  
Sent By tklarge Date 2017-11-17 Time 07:24 Rev Time 0.00
Received By tklarge Date 2017-11-17 Time 07:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By tklarge Date 2017-08-09 Time 11:12 Rev Time 0.00
Received By tklarge Date 2017-08-09 Time 10:43 Sent To  
Notes
2017-08-09 11:12:381) PLACE THE PSI OF THE SYSTEM ON BOTH SETS OF PLANS.
 2014 FBC-FUEL GAS SEC.402.3.
 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 3) COPPER SHALL NOT BE USED IF THE GAS CONTAINS MORE
 THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN SULFIDE PER
 100 STANDARD CUBIC FEET OF GAS.SUPPLY INFORMATION FROM
 FLORIDA PUBLIC UTILITIES STATING THE HYDROGEN SULFIDE
 CONTENT IS LESS THE 0.3 GRAINS PE 100 STANDARD CUBIC
 FEET OF GAS. 2014 FBC-FUEL GAS SEC. 403.4.3.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-17 Cont ID  
Sent By tklarge Date 2017-11-17 Time 07:24 Rev Time 0.00
Received By tklarge Date 2017-11-17 Time 07:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-09 Cont ID  
Sent By tklarge Date 2017-08-09 Time 11:13 Rev Time 0.00
Received By tklarge Date 2017-07-26 Time 09:47 Sent To  
Notes
2017-07-27 09:47:57ROUTED TO PLUMB <5K