Plan Review Details - Permit 17071018
Plan Review Stops For Permit 17071018
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-28 Cont ID  
Sent By pleduc Date 2017-07-28 Time   Rev Time 0.00
Received By pleduc Date 2017-07-28 Time 10:17 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-25 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-23 Time 10:26 Sent To  
Notes
2017-10-25 10:26:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-14 Time   Rev Time 0.00
Received By cpuell Date 2017-07-26 Time 16:33 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By ccole Date 2017-10-25 Time 17:07 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 17:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-14 Cont ID  
Sent By ccole Date 2017-08-14 Time 13:07 Rev Time 0.00
Received By ccole Date 2017-08-14 Time 13:07 Sent To  
Notes
2017-08-14 13:22:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17071018
 8/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) VERIFY THAT THE TEMPERATURE DIFFERENTIAL OF THE
 MAKEUP AIR FOR THE HOOD EXHAUST SYSTEMS AND THE AIR IN
 THE CONDITIONED SPACE DOES NOT EXCEED 10 DEGREES, OR
 PROVIDE TEMPERED MAKE UP AIR- SECTION 508.1.1.
  
 2) SUBMITTALS REQUIRED TO BE REVIEWED AND APPROVED BY
 THE EOR: 1) UL LISTED GREASE EXHAUST DUCT. 2)
 MIAMI-DADE NOA'S FOR THE FANS.
  
 3) SHEET #7 & 8: AS NOTED IN THE CALCULATIONS 2273 CFMS
 OF O/A FROM THE AC SYSTEMS WILL BE PROVIDED AS MAKEUP
 AIR FOR THE HOODS. PLEASE INDICATE WHICH AC SYSTEMS
 WIIL BE PROVIDING THE AIR TO EACH EXHAUST HOOD- SEE THE
 MAIN PERMIT PLANS FOR THE PROJECT.
  
 4) SHEET #9: PROVIDE WIND LOAD ENGINEERING AND DESIGN
 CRITERIA FOR CONSTRUCTION AND ATTACHMENT OF THE WALL
 BRACKETS, AND ATTACHMENT OF THE FANS TO THE BRACKETS-
 SECTION 301.15.
  
 5) SHEET #9: THE DRAWING INDICATES THAT THE POSITION OF
 THE EXHAUST FAN OPENING WILL ALLOW FOR WATER TO INTRUDE
 INTO IT. PLEASE PROVIDE A MEANS OF PROTECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  