Plan Review Details - Permit 17070995
Plan Review Stops For Permit 17070995
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-27 Cont ID  
Sent By cthroop Date 2017-09-27 Time 08:47 Rev Time 0.00
Received By cthroop Date 2017-09-27 Time 07:56 Sent To  
Notes
2017-09-27 08:56:34BASED ON THE OFFICIAL ZONING MAP REFERRED TO IN SECTION
 53-2 OF CHAPTER 53 OF THE CITY CODE OF WEST PALM BEACH,
 FLORIDA, 1962, ADOPTED JUNE 15, 1964, YOUR PROPERTY,
 LOCATED AT 527 18TH STREET, IS NOT LOCATED IN AN AREA
 OF QUESTIONABLE SOILS AND DOES NOT REQUIRE
 INVESTIGATION BY A GEOTECHNICAL ENGINEER WITH ITS
 SUBSEQUENT SOILS REPORT AND DENSITY TESTING.
 THIS ONLY RELIEVES YOU FROM THE STATUTORY REQUIREMENTS
 OF THE FLORIDA BUILDING CODE. THERE MAY BE OTHER
 ENTITIES, SUCH AS YOUR DESIGN PROFESSIONAL OR YOUR
 LENDING INSTITUTION THAT MAY REQUIRE THE ABOVE
 MENTIONED INVESTIGATION.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By cthroop Date 2017-08-17 Time 13:45 Rev Time 0.00
Received By cthroop Date 2017-08-17 Time 10:24 Sent To  
Notes
2017-08-17 14:04:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT.
  
 2. ROOFING PERMIT REQUIRED.
  
 3. WINDOW SCHEDULE SPECIFIES PGT 700 SERIES WINDOWS.
 NOA 15-0204.01 SUBMITTED FOR REVIEW IS FOR AIR MASTER
 WINDOWS. PLEASE CLARIFY.
  
 4. REF. PLAN PAGE S-3. NOTES STATE ROOF WIND PRESSURES
 ARE BASED ON FBC 2010. PROVIDE DESIGN WIND LOADS FOR
 ROOF BASED ON THE 2014 FBC 5TH ED.
  
 5. WIND DESIGN LOADS FOR PROPOSED PLASTPRO DOORS DO NOT
 MEET THE CALCULATED DESIGN PRESSURE RATING FOR WALL
 AREA 4, SEE PLAN PAGE S-3.
  
 6. ROOFING NOA 11-1122.04 IS EXPIRED. PROVIDE VALID NOA
 FOR ROOFING SYSTEM COMPONENTS.
  
 7. REF. PLAN PAGE S-1. TYPO IN PRE-CAST LINTEL NOTES
 "POURED SOLID WITH 300 PSI CONCRETE". PLEASE CORRECT.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING AND DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-10-12 Cont ID  
Sent By jpearson Date 2017-10-12 Time 14:51 Rev Time 0.00
Received By jpearson Date 2017-10-12 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By jpearson Date 2017-09-27 Time 07:35 Rev Time 0.00
Received By jpearson Date 2017-09-27 Time 07:35 Sent To  
Notes
2017-09-27 07:35:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT WERE ADDRESSED HAVE BEEN
 REMOVED, THE REMAINING ARE ITEMS NOT ADDRESSED
 SATISFACTORILY. ADDITIONALLY, THE PLAN IS REQUIRED TO
 BE SIGNED BY THE PERSON RESPONSIBLE FOR THE DESIGN. FS
 481.229
  
  
 3. PROVIDE AFCI PROTECTION TO CODE. NEC 210.12; FBC
 RE3902.12, FBC 107.2.1 (THE NOTE PROVIDED REFERENCES
 THE 2008 NEC, WHICH IS NOT THE CURRENT CODE.
 ADDITIONALLY, AFCI PROTECTION IS REQUIRED IN MORE THAN
 JUST SLEEPING AREAS. CODE STATES: ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC
 210.12; FBC RE3902.12) PROVIDE CORRECTION.
 4. PROVIDE TAMPER RESISTANT OUTLETS TO CODE. NEC
 406.12; FBC RE4002.14 (THE NOTE PROVIDED REFERENCES THE
 2008 NEC, WHICH IS NOT THE CURRENT CODE. ALSO, THE CODE
 SECTION CITED, 406.11, IS NOT RELATED TO TAMPER
 RESISTANT OUTLETS.) PROVIDE CORRECTION.
 5. WATER HEATER BREAKER IS TOO LARGE. PROVIDE
 CORRECTION. NEC 422.13 (RESPONSE TO COMMENTS STATES
 THAT THE PANEL SCHEDULE WAS CHANGED, HOWEVER, IT IS
 STILL SHOWING A 30 AMP BREAKER. AT 125% OF THE LOAD,
 THE PROPER SIZE BREAKER FOR THIS IS 25 AMP.) PROVIDE
 CORRECTION.
 6. AHU UNIT IS SHOWN BEING FED BY #6 WIRE. IS THIS
 ROMEX, OR WIRING INSTALLED IN A CONDUIT? #6 ROMEX WIRE,
 WHICH IS TYPICAL IN RESIDENTIAL WIRING, IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4 (THE CORRECTION PROVIDED WAS TO CHANGE THE
 BREAKER SIZE TO 50 AMP. HOWEVER, WITH THE NEW
 MECHANICAL SUBMISSION, I SEE THAT THE AHU WILL HAVE A 5
 KW HEAT STRIP. SO, THE PROPER SIZE BREAKER IS 30 AMP.
 ALSO, THE CU UNIT SHOWS A 40 AMP BREAKER IN PANEL, BUT
 THE SPECS STATE THAT THE MOCP IS 35 AMP. PROVIDE
 CORRECTION FOR BOTH UNITS.)
 8. CLOSET LIGHT IS NOT SPECIFIED. PROVIDE DETAIL OF
 FIXTURE, OR NOTE TO COMPLY WITH CODE. NEC 410.16; FBC
 RE4003.12 (RESPONSE TO COMMENT STATES TO SEE NOTE # 6,
 BUT THERE IS NOTHING IN NOTE # 6 THAT RELATES TO CLOSET
 LIGHTING.) PROVIDE CORRECTION.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-10 Cont ID  
Sent By jpearson Date 2017-08-10 Time 10:50 Rev Time 0.00
Received By jpearson Date 2017-08-10 Time 10:50 Sent To  
Notes
2017-08-10 10:50:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER SHOWS 1/0 WIRE USED FOR A 200 AMP SERVICE. 1/0
 WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 215.2, 310.15; FBC RE3602.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. INCLUDE ALL AVAILABLE GROUNDING ELECTODES. NEC
 250.50, 250.94; FBC RE3609.3
 3.PROVIDE AFCI PROTECTION TO CODE. NEC 210.12; FBC
 RE3902.12, FBC 107.2.1
 4. PROVIDE TAMPER RESISTANT OUTLETS TO CODE. NEC
 406.12; FBC RE4002.14
 5.. WATER HEATER BREAKER IS TOO LARGE. PROVIDE
 CORRECTION. NEC 422.13
 6. AHU UNIT IS SHOWN BEING FED BY #6 WIRE. IS THIS
 ROMEX, OR WIRING INSTALLED IN A CONDUIT? #6 ROMEX WIRE,
 WHICH IS TYPICAL IN RESIDENTIAL WIRING, IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 7. AHU UNIT APPEARS TO BE IN ATTIC. PROVIDE RECEPTACLE
 OUTLET AT OR NEAR THE APPLIANCE. FBC RESIDENTIAL
 M1305.1.3.1
 8. CLOSET LIGHT IS NOT SPECIFIED. PROVIDE DETAIL OF
 FIXTURE, OR NOTE TO COMPLY WITH CODE. NEC 410.16; FBC
 RE4003.12
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 10. SMOLE ALARMS SHOULD BE LOCATED AT LEAST 3 FEET FROM
 CEILING FAN BLADES OR MECHANICAL GRILL. PROVIDE
 CORRECTION. NFPA 72, 11.8.3.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-12 Cont ID  
Sent By jpearson Date 2017-10-12 Time 14:51 Rev Time 0.00
Received By jpearson Date 2017-10-10 Time 15:05 Sent To  
Notes
2017-10-11 15:05:59RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-05 Cont ID  
Sent By hmoser Date 2017-10-05 Time 14:39 Rev Time 0.00
Received By hmoser Date 2017-09-15 Time 14:09 Sent To  
Notes
2017-09-18 14:09:34R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-01 Cont ID  
Sent By hmoser Date 2017-09-01 Time 14:54 Rev Time 0.00
Received By hmoser Date 2017-07-25 Time 10:46 Sent To  
Notes
2017-07-26 10:47:03R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2017-08-17 Cont ID  
Sent By cthroop Date 2017-08-17 Time 12:59 Rev Time 0.00
Received By cthroop Date 2017-08-17 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By hmoser Date 2017-10-05 Time 14:39 Rev Time 0.00
Received By hmoser Date 2017-10-05 Time 13:09 Sent To  
Notes
2017-10-05 14:35:03PASS PROVISO
 REFER TO SECTION R403.2.4 AIR HANDLING UNITS.
 2014 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-01 Cont ID  
Sent By hmoser Date 2017-09-01 Time 14:54 Rev Time 0.00
Received By hmoser Date 2017-09-01 Time 12:49 Sent To  
Notes
2017-09-01 14:54:30PLAN DENIED
 1) REFER TO SECTION R403.2.4 AIR HANDLING
 UNITS. 2014 FLORIDA ENERGY CODE.
 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN.
 SECTION 107 FBC 2014
 3) PROVIDE DUCT SIZE FOR MASTER BEDROOM
 RETURN AIR. 107 FBC 2014
 4) PLAN IS HARD TO READ PLEASE MAKE PLAN MORE LEGIBLE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 11:02 Rev Time 0.00
Received By gjohnson Date 2017-09-27 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By thunt Date 2017-08-18 Time 16:11 Rev Time 0.00
Received By thunt Date 2017-08-18 Time 15:56 Sent To M
Notes
2017-08-18 16:21:01WATER HEATER RELIEF AND PAN DRAIN LINE MUST COMPLY WITH
 504.6 THRU 504.7.2
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6696
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-09-27 Cont ID  
Sent By cthroop Date 2017-09-27 Time 08:46 Rev Time 0.00
Received By cthroop Date 2017-09-27 Time 07:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-08-17 Cont ID  
Sent By cthroop Date 2017-08-17 Time 13:43 Rev Time 0.00
Received By cthroop Date 2017-08-17 Time 10:25 Sent To  
Notes
2017-08-17 13:45:22BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOA 11-1122.04 HAS EXPIRED. PROVIDE CURRENT NOA FOR
 PROPOSED ROOFING.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-10-03 Cont ID  
Sent By ajones Date 2017-10-03 Time 12:08 Rev Time 0.00
Received By ajones Date 2017-10-03 Time 12:08 Sent To  
Notes
2017-10-03 12:10:13FRONT SETBACK SHALL BE MEASURE FROM THE HOUSE NOT THE
 PORCH.
  
 ANGELLA VANN
 PLANNING & ZONING ADMINISTRATOR
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-09-26 Cont ID  
Sent By awooten Date 2017-09-26 Time 16:10 Rev Time 0.00
Received By awooten Date 2017-09-25 Time   Sent To  
Notes
2017-09-25 15:26:06************ZONING REVIEW**********************
  
 PLEASE SHOW THE FOLLOWING ON A SITE PLAN.
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A. FRONT: 25 FEET;
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH WHICHEVER
 IS LESS;
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 THIS PROPERTY WOULD BE REQUIRED TO HAVE A 12.5 FOOT
 SETBACK ON THE CORNER SIDE AND A MINIMUM FIVE FOOT
 SETBACK ON THE WEST SIDE.
  
 ----
  
 A SEPARATE LANDSCAPE AND IRRIGATION PLAN IS ALSO
 REQUIRED INDICATING THE FOLLOWING:
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PLAN SHOWING
 COMPLIANCE WITH LANDSCAPE CODE:
  
 SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 THE DRIVEWAY REQUIRES A SEPARATE PERMIT.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By awooten Date 2017-08-09 Time 13:13 Rev Time 0.00
Received By awooten Date 2017-08-02 Time 16:12 Sent To  
Notes
2017-08-09 13:13:22************ZONING REVIEW**********************
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A. FRONT: 25 FEET;
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH WHICHEVER
 IS LESS;
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 THIS PROPERTY WOULD BE REQUIRED TO HAVE A 12.5 FOOT
 SETBACK ON THE CORNER SIDE AND A MINIMUM FIVE FOOT
 SETBACK ON THE WEST SIDE.
  
 A SEPARATE LANDSCAPE AND IRRIGATION PLAN IS ALSO
 REQUIRED INDICATING THE FOLLOWING:
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PLAN SHOWING
 COMPLIANCE WITH LANDSCAPE CODE:
  
 SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 THE DRIVEWAY REQUIRES A SEPARATE PERMIT.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  