Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-11-30 Cont ID  
Sent By jgomez Date 2017-11-30 Time 15:24 Rev Time 0.00
Received By jgomez Date 2017-11-30 Time 15:24 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-20 Cont ID  
Sent By jgomez Date 2017-11-20 Time 10:07 Rev Time 0.00
Received By jgomez Date 2017-11-17 Time 18:18 Sent To  
Notes
2017-11-17 18:19:12BUILDING REVIEW APPROVED WITH PROVISO:
 1- WALLS EXTERIOR FINISH IS NOT CLEAR. SHEET CVR SHOWS
 HORIZONTAL SIDING, SHEET A2 SHOWS TEXTURED STUCCO
 FINISH AND WALL SECTIONS ON SHEET S4 SHOWS 7" LAP
 SIDING. REVISE AS REQUIRED TO MATCH. NOTE: PRODUCT
 APPROVAL MAY BE REQUIRED.
 2- SHEET CVR SHOWS BAHAMA SHUTTERS AND COLONIAL
 SHUTTERS. THIS DOESN'T MATCH ELEVATIONS SHOWN ON SHEET
 A2. REVISE AS REQUIRED TO MATCH.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-31 Cont ID  
Sent By jgomez Date 2017-10-31 Time 11:39 Rev Time 0.00
Received By jgomez Date 2017-10-30 Time 12:35 Sent To  
Notes
2017-10-30 12:44:09RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT REQUIRED INFORMATION MAY BE SUBMITTED AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS
 TIME OR IF RESUBMITTING REQUIRED INFORMATION BEFORE
 PERMIT ISSUANCE.
 NEED COUNTY IMPACT FEES STAMP ON PLANS AND COPY OF PAID
 RECEIPT BEFORE ISSUING THE PERMIT.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT (2300 N. JOG RD.).
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 ORIGINAL COMMENT:
 2- REVISE ALL COMPONENTS AND CLADDING DESIGN PRESSURES
 ON SHEET S1 AND A2 TO REFLECT DESIGN PRESSURES FOR
 EXPOSURE "C". SEC. R301.2.1.4 FBC-RESIDENTIAL.
 RESPONSE:
 EXPOSURE WAS REVISED ON SHEET S1 BUT THE DESIGN
 PRESSURES SHOWN ON SHEET A2 FOR THE OVERHEAD GARAGE
 DOOR ARE NOT CLEAR. ACCORDING TO THE DESIGN DATA FOR
 WIND LOADS ON SHEET A2, THE DESIGN PRESSURES SHOWN ARE
 FOR THE 170 MPH ULTIMATE WIND SPEED. IT LOOKS LIKE THE
 DESIGN PRESSURES FOR DOORS AND WINDOWS ARE GIVEN BASE
 ON THE ULTIMATE WIND LOAD. BUT, THE DESIGN PRESSURES
 FOR THE OVERHEAD GARAGE DOOR ARE TOO LOW IF THEY ARE
 BASED ON THE 170 MPH ULTIMATE WIND SPEED WITH A "C"
 EXPOSURE. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING
 FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE
 WITH ALL THE REQUIREMENTS OF OPENING PROTECTION OF SEC.
 R302.5.1 FBC-RESIDENTIAL.
 RESPONSE:
 NEED TO SPECIFY THE SELF CLOSING DEVICE AS REQUIRED BY
 SEC. R302.5.1 FBC-RESIDENTIAL.
  
 4- ENGINEER OF RECORD IS DESIGNING AN UNVENTTED ATTIC.
 PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE
 ICYNENE ROOF INSULATION SPECIFIED BY THE ENGINEER OF
 RECORD. NEED THE ICC EVALUATION REPORT TO VERIFY
 COMPLIANCE WITH THE REQUIREMENTS OF SEC. R316
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 5- MASTER BATHROOM AND BATHROOM FOR OTHER BEDROOMS ARE
 SHOWING ONLY MECHANICAL VENTILATION FOR THE WATER
 CLOSET COMPARTMENT. NEED TO PROVIDE MECHANICAL
 VENTILATION FOR THE REST OF THE BATHROOM ALSO AS
 REQUIRED BY SEC. R303.3 FBC-RESIDENTIAL.
 NOTE: COORDINATE INFORMATION ON MECHANICAL AND
 ELECTRICAL PLANS.
 RESPONSE: MECHANICAL PLAN WAS REVISED, BUT ELECTRICAL
 PLAN WAS NOT. REVISE ELECTRICAL PLAN TO SHOW LOCATION
 AND SWITCH FOR THE EXHAUST FANS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) GARAGE OVERHEAD DOOR. DRAWINGS SUBMITTED ARE TOO
 LIGHT. THEY ARE NOT LEGIBLE. PROVIDE LEGIBLE DRAWINGS
 AND PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO DRAWINGS SUBMITTED.
 NOTE: PRODUCT APPROVAL WILL BE REVIEWED ONCE THE DESIGN
 PRESSURES ON ITEM #2 ABOVE ARE CLARIFIED.
  
 B) JAMES HARDI PLANK AS SPECIFIED ON PLANS. PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS FOR PROPOSED
 INSTALLATION THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL FL13192-R4 SUBMITTED.
  
 7- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 BAHAMA SHUTTERS SHOWING PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES AND NOA 14-1120.09
 SUBMITTED. SEC. R301.1 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 COLONIAL SHUTTERS SHOWING PROPOSED INSTALLATION TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES AND NOA
 14-1120.09 SUBMITTED. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- NO CLEAR WHAT KIND OF ROOFING IS GOING TO BE
 INSTALLED. METAL ROOF OR CONCRETE TILE. THERE ARE TWO
 DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED. ONE IS
 FOR METAL ROOF AND THE OTHER ONE IS FOR CONCRETE TILE.
 PLANS CALL FOR METAL ROOFING. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: ROOF TILE REQUIRES REVISION ON THE DESIGN
 CRITERIA TO INCLUDE THE ADDITIONAL WEIGHT.
  
 ******ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ***** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By jgomez Date 2017-08-11 Time 10:42 Rev Time 0.00
Received By jgomez Date 2017-08-10 Time 18:08 Sent To  
Notes
2017-08-10 08:44:26RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT (2300 N. JOG RD.).
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- BUILDING IS LOCATED IN EXPOSURE "C" NOT "B" AS
 REQUIRED BY SEC. R301.2.1.4 FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE DESIGN INFORMATION ON SHEET S1
 OR PROVIDE COMPLETE RATIONAL ANALYSIS FOR EACH WIND
 DIRECTIONS.
  
 3- REVISE ALL COMPONENTS AND CLADDING DESIGN PRESSURES
 ON SHEET S1 AND A2 TO REFLECT DESIGN PRESSURES FOR
 EXPOSURE "C" AS REQUIRED BY ITEM #2 ABOVE. SEC.
 R301.2.1.4 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING
 FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE
 WITH ALL THE REQUIREMENTS OF OPENING PROTECTION OF SEC.
 R302.5.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ROOF VENTILATION AS REQUIRED BY
 SEC. R806 FBC-RESIDENTIAL.
 NOTE: IF DESIGNING AND UNVENTED ATTIC, THEN PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS AS REQUIRED BY SEC.
 R806.5 FBC-RESIDENTIAL. COORDINATE WITH PERSON WHO IS
 PREPARING THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 6- ROOF FRAMING PLAN ON SHEET S3 IS MISSING INFORMATION
 FOR THE BOSTON HIP FRAMING ABOVE THE GARAGE AREA.
 REVISE ROOF FRAMING PLAN AS REQUIRED TO MATCH EXTERIOR
 ELEVATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- MASTER BATHROOM IS SHOWING ONLY MECHANICAL
 VENTILATION FOR THE WATER CLOSET COMPARTMENT. NEED TO
 PROVIDE MECHANICAL VENTILATION FOR THE BATHROOM ALSO AS
 REQUIRED BY SEC. R303.3 FBC-RESIDENTIAL.
 NOTE: COORDINATE INFORMATION ON MECHANICAL AND
 ELECTRICAL PLANS. .
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE BAHAMA SHUTTERS SHOWN ON THE FRONT
 ELEVATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE COLONIAL SHUTTERS SHOWN ON THE
 FRONT ELEVATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE GUARDRAILS SHOWN ON THE FRONT
 ELEVATION. SHOW COMPLIANCE WITH THE LIVE LOADS OF TABLE
 R301.5 FBC-RESIDENTIAL. ALSO, SPECIFY THE GUARDRAIL
 HEIGHT AND PICKETS SPACING. SEC. R312 FBC-RESIDENTIAL.
  
 11- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE AT THE BOTTOM OF FROM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) CONCRETE BLOCK WALL INSULATION SHOWN ON ITEM #9(A)
 DOESN'T MATCH INSULATION VALUE SPECIFIED BY THE
 ENGINEER OF RECORD ON PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) CEILING INSULATION INFORMATION ON ITEM #10 NEEDS TO
 BE COORDINATED WITH REVISED PLANS. SEE ITEM #5 ABOVE.
 COORDINATE TYPE AND INSULATION R-VALUE. ALSO,
 COORDINATE IF ENGINEER OF RECORD IS DESIGNING A VENTED
 OR UNVENTED ATTIC. SEE ITEM # 5 ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE INFORMATION FOR THE HOT WATER SYSTEM ON ITEM
 #14. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) REVISE ROOF TYPE ON PAGE 3 OF 5. PLANS SHOW TWO
 BOSTON HIP ENDS. ADD INFORMATION AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) COORDINATE ATTIC AND CEILING INFORMATION SHOWN ON
 PAGE 3 OF 5 WITH CEILING INFORMATION SHOWN ON ITEM #10
 ON PAGE 1 OF 5. COORDINATE WITH PLANS TO AVOID
 CONFLICTS/DELAYS. COORDINATE ATTIC VENTING AND
 INSULATION R-VALUE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE
 THE GLAZING DEFAULT FACTORS.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FRENCH DOORS WITH SIDELITES AND TRANSOM ABOVE AS
 SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) FIXED WINDOWS AS SHOWN ON PLANS.
  
 D) METAL ROOF AS SHOWN ON PLANS. NOTE: CLEARLY IDENTIFY
 FASTENING METHOD TO VERIFY COMPLIANCE WITH THE
 ENGINEER'S CALCULATED DESIGN PRESSURES.
  
 E) GARAGE OVERHEAD DOOR AS SHOWN ON PLANS.
  
 F) GARAGE OUTSIDE SWING DOOR AS SHOWN ON PLANS.
  
 G) JAMES HARDI PLANK AS SPECIFIED ON PLANS.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
  
 ******ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. .
 ***** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE..
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 14:22 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 14:22 Sent To  
Notes
2017-11-20 11:35:14REVISED DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By jpearson Date 2017-10-26 Time 07:26 Rev Time 0.00
Received By jpearson Date 2017-10-26 Time 07:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By jpearson Date 2017-08-08 Time 10:56 Rev Time 0.00
Received By jpearson Date 2017-08-08 Time 10:56 Sent To  
Notes
2017-08-08 10:25:53CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS LOCATION OF SMOKE ALARMS CLOSE TO CEILING
 FANS AND MECHANICAL SUPPLY AIR DUCTS. PROVIDE
 CORRECTION SO THAT SMOKE ALARM LOCATION ARE AT LEAST 3
 FEET FROM EACH FAN OR MECHANICAL GRILL. NFPA 72,
 11.8.3.5
 2. PLAN HAS 3 DIFFERENT NOTES ON TAMPER RESISTANT
 RECEPTACLES. 2 OF THOSE NOTES REFERENCE THE WRONG CODE
 SECTION (406.11) AND 1 OF THEM REFERENCES THE 2008 NEC,
 WHICH IS NOT THE CURRENT CODE. PLEASE REMOVE AND/OR
 CORRECT REDUNDANT NOTES. NEC 406.12; FBC RE4002.14
 3. PANEL SCHEDULE SHOWS THE AHU (WHICH REQUIRES A
 MINIMUM CIRCUIT AMPACITY OF 49 AMPS) ON A 50 AMP
 BREAKER WITH #8 WIRE. #8 ROMEX, WHICH IS TYPICAL IN
 HOUSE WIRING, IS NOT RATED FOR 49 AMPS. WILL THIS
 WIRING BE ROMEX, OR INSTALLED IN CONDUIT? PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 4. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE3903.3
 5. PLEASE CLARIFY THE OUTSIDE LIGHT FIXTURE LOCATIONS.
 PLAN SHOWS WIRING GOING TO LIGHTS, BUT DOES NOT SHOW
 SOME OF THE FIXTURE LOCATIONS. FBC 107.2.1
 6. PROVIDE GFCI PROTECTED OUTLET IN POWDER BATH WITHIN
 3 FEET OF BASIN. NEC 210.52(D); FBC RE3901.6
 7. WILL THE AQUARIUM BE PLACED ATOP WALL SPACE THAT
 WOULD REQUIRE AN OUTLET? PROVIDE WALL SPACE OUTLET IF
 NECESSARY. NEC 210.52(A); FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 17:23 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 17:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-10-29 Cont ID  
Sent By gjohnson Date 2017-10-29 Time 12:35 Rev Time 0.00
Received By gjohnson Date 2017-10-29 Time 12:35 Sent To  
Notes
2017-10-29 12:39:591ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. THE TANKLESS HEATER SHALL BE MOUNTED A MIN. OF 4'
 FROM ANY OPERABLE DOOR OR WINDOW PLEASE PLACE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-30 Cont ID  
Sent By jgomez Date 2017-11-30 Time 15:33 Rev Time 0.00
Received By jgomez Date 2017-11-30 Time 15:33 Sent To I
Notes
2017-11-30 15:35:19IMPACT FEES SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 17:24 Rev Time 0.00
Received By gjohnson Date 2017-11-14 Time 09:03 Sent To  
Notes
2017-11-15 09:11:11R33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-01 Cont ID  
Sent By cpuell Date 2017-11-01 Time 10:54 Rev Time 0.00
Received By cpuell Date 2017-10-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-13 Cont ID  
Sent By skennedy Date 2017-10-13 Time 12:51 Rev Time 0.00
Received By skennedy Date 2017-07-24 Time 15:02 Sent To  
Notes
2017-10-13 12:53:03I-STOPPED OUT AS THE SUBMITTAL HAS BEEN LOST FOR SOME
 TIME AND I HAVE INDICATED IN THE RECORD THAT I
 CORRESPONDED WITHT THE APPLICANT TO ATTEMPT TO OBTAIN A
 NEW APPLICATION AND PLANS.
2017-07-25 15:02:49R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-11-30 Cont ID  
Sent By jgomez Date 2017-11-30 Time 15:09 Rev Time 0.00
Received By jgomez Date 2017-11-30 Time 12:32 Sent To  
Notes
2017-11-30 15:09:53$236.59 PAID. MU-2017-032626.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-11-20 Cont ID  
Sent By jgomez Date 2017-11-20 Time 10:52 Rev Time 0.00
Received By jgomez Date 2017-11-20 Time 10:52 Sent To  
Notes
2017-11-20 10:53:221- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES
 ASSESSMENT (2300 N. JOG RD.). BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-10-30 Cont ID  
Sent By jgomez Date 2017-10-30 Time 13:50 Rev Time 0.00
Received By jgomez Date 2017-10-30 Time 13:50 Sent To  
Notes
2017-10-30 13:50:231- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT (2300 N. JOG RD.).
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-10 Cont ID  
Sent By jgomez Date 2017-08-10 Time 18:23 Rev Time 0.00
Received By jgomez Date 2017-08-10 Time 07:54 Sent To  
Notes
2017-08-10 18:24:451- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT (2300 N. JOG RD.).
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-11-20 Cont ID  
Sent By jgomez Date 2017-11-20 Time 11:14 Rev Time 0.00
Received By jgomez Date 2017-11-20 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-10-31 Cont ID  
Sent By jgomez Date 2017-10-31 Time 12:00 Rev Time 0.00
Received By jgomez Date 2017-10-30 Time 14:00 Sent To  
Notes
2017-10-30 14:00:27RESIDENTIAL (R3) ADDITION/ALTERATION SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE IS ONLY ONE SET OF MECHANICAL PLANS SUBMITTED.
 NEED TO PROVIDE TWO SETS SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. SEC. 107.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By jgomez Date 2017-08-11 Time 18:49 Rev Time 0.00
Received By jgomez Date 2017-08-11 Time 18:48 Sent To  
Notes
2017-08-11 18:53:40RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ONLY THE PROJECT SUMMARY OF THE EQUIPMENT SIZING
 CALCULATIONS WERE SUBMITTED. NEED TO PROVIDE THE
 COMPLETE EQUIPMENT SIZING CALCULATIONS TO VERIFY
 COMPLIANCE WITH SEC. R403.6 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 17:24 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 17:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-29 Cont ID  
Sent By gjohnson Date 2017-10-29 Time 12:28 Rev Time 0.00
Received By gjohnson Date 2017-10-29 Time 08:04 Sent To  
Notes
2017-10-29 12:35:091ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE POWDER ROOM DOES NOT HAVE THE REQUIRED CLEARANCE
 FOR OPENING AND CLOSING THE DOOR IT SHALL HAVE A MIN OF
 21 IN. IN FRONT OF ANY FIXTURE AND NOT HINDER THE
 OPERATION OF ANY DOOR. PER FBC RES P2705.1(5)(6)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2017-11-20 Cont ID  
Sent By jgomez Date 2017-11-20 Time 11:15 Rev Time 0.00
Received By jgomez Date 2017-11-20 Time 07:54 Sent To  
Notes
2017-11-20 11:26:161- METAL ROOF FL7271-R3.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-10-31 Cont ID  
Sent By jgomez Date 2017-10-31 Time 11:59 Rev Time 0.00
Received By jgomez Date 2017-10-31 Time 11:59 Sent To  
Notes
2017-10-31 11:59:531- NO CLEAR WHAT KIND OF ROOFING IS GOING TO BE
 INSTALLED. METAL ROOF OR CONCRETE TILE. THERE ARE TWO
 DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED. ONE IS
 FOR METAL ROOF AND THE OTHER ONE IS FOR CONCRETE TILE.
 PLANS CALL FOR METAL ROOFING. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: ROOF TILE REQUIRES REVISION ON THE DESIGN
 CRITERIA TO INCLUDE THE ADDITIONAL WEIGHT.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By jgomez Date 2017-08-11 Time 18:47 Rev Time 0.00
Received By jgomez Date 2017-08-11 Time 18:46 Sent To  
Notes
2017-08-11 18:48:421- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) METAL ROOF AS SHOWN ON PLANS. NOTE: CLEARLY IDENTIFY
 FASTENING METHOD TO VERIFY COMPLIANCE WITH THE
 ENGINEER'S CALCULATED DESIGN PRESSURES.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-11-17 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-17 Time 13:06 Sent To  
Notes
2017-11-17 13:05:241.) PROVIDE LANDSCAPE PERMIT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2017-11-01 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-01 Time 09:54 Sent To  
Notes
2017-11-01 09:55:531.) PLEASE PROVIDE A SITE PLAN AND LABEL SETBACKS FROM
 PROPERTY LINES
 2.) PLEASE PROVIDE REQUIRED LANDSCAPE PERMIT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
2017-08-28 08:30:36EXCEEDS 50% VALUE OF STRUCTURE, NEED LANDSCAPE PERMIT
 FOR COMPLIANCE.RC