Plan Review Stops For Permit 17070856 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2017-10-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-10-10 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-10-10 |
Time |
16:21 |
Sent To |
|
|
Notes |
2017-10-10 16:22:04 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) BALCONY | | DECK UNDERLAYMENT. ARCHITECT TO SPECIFY BALCONY FLOOR | | FINISH. NOTE: PRODUCT APPROVAL TO BE DESIGNED TO BE | | USED W/ SPECIFIED FINISH. MARK ASSEMBLY TO BE USED AND | | PROVIDE SIGNED/SEALED RAS 117 CALCULATIONS IF REQ'D. | | B) SINGLE HUNG WINDOWS FOR LARGE MISSILE IMPACT. | | C) WINDOW MULLIONS AND SPECIFY MULLION SIZE. | | D) FIXED WINDOWS AS SPECIFIED ON PLANS. | | E) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS. | | 2- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS. | | 3- ENGINEER'S RAS 117 CALCULATIONS SUBMITTED NEED | | ORIGINAL SEAL & SIGNATURE (NOT COPY). CHAPTER 471 F.S. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2017-09-29 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-09-29 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-09-29 |
Time |
16:39 |
Sent To |
|
|
Notes |
2017-09-29 16:39:21 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE | | OVERHEAD GARAGE DOOR ON SHEET A3.2 TO CORRESPOND TO | | EXPOSURE "D". | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | A) BALCONY DECK UNDERLAYMENT. ARCHITECT TO SPECIFY | | BALCONY FLOOR FINISH. NOTE: NEED PRODUCT APPROVAL THAT | | IS DESIGNED TO BE USED WITH THE SPECIFIC DECK FINISH | | MATERIAL TO BE INSTALLED IN THIS HOUSE. IN ADDITION | | CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | REQUIRED. | | *****NOA 14-0529.02 IS GOOD ONLY FOR OPTIONS SHOWN ON | | TABLE 4 OF SAME NOA. AND FLORIDA PRODUCT APPROVAL | | FL17442-R1 IS NOT GOOD EITHER. | | B) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES | | CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH | | ITEM #1 ABOVE. | | C) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT | | RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS | | FOR SMALL MISSILE IMPACT RESISTANT. | | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY | | MULLION SIZE. | | E) FIXED WINDOWS AS SPECIFIED ON PLANS. | | F) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS. | | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE | | PRODUCT APPROVALS. | | 4- ENGINEER WHO PREPARED THE RAS 117 CALCULATIONS FOR | | THE MAIN HOUSE TO PROVIDE CALCULATIONS WITH ORIGINAL | | SEAL AND SIGNATURE (NOT COPY) AS REQUIRED BY CHAPTER | | 471 F.S. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
|
Date |
2017-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-08-01 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-08-01 |
Time |
11:15 |
Sent To |
|
|
Notes |
2017-08-01 11:15:35 | 08/01/17 YANIL ESPINAL E-MAILED BACK. THEY ARE GETTING | | THE PRODUCT APPROVALS TO RE-SUBMIT. PLANS IN BACK LARGE | | PLANS SHELF UNDER "J". JG. | | | | | | | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS AS REQ'D GENERAL | | LIMITATION #7. | | | | 2- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE | | OVERHEAD GARAGE DOOR TO CORRESPOND TO EXPOSURE "D". SEE | | SHEET A3.1 | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT | | APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC | | DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN | | ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE | | INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS IF REQUIRED. | | | | B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON | | 02/01/16. | | | | C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL | | FOR LISTED ADHESIVES. | | | | D) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES | | CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH | | ITEM #2 ABOVE. | | | | E) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT | | RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS | | FOR SMALL MISSILE IMPACT RESISTANT. | | | | F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY | | MULLION SIZE. | | | | G) FIXED WINDOWS AS SPECIFIED ON PLANS. | | | | H) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS. | | | | 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE | | PRODUCT APPROVALS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
|
Date |
2017-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-07-31 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-07-31 |
Time |
15:16 |
Sent To |
|
|
Notes |
2017-07-31 15:16:59 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS AS REQ'D GENERAL | | LIMITATION #7. | | | | 2- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE | | OVERHEAD GARAGE DOOR TO CORRESPOND TO EXPOSURE "D". SEE | | SHEET A3.1 | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT | | APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC | | DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN | | ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE | | INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS IF REQUIRED. | | | | B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON | | 02/01/16. | | | | C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL | | FOR LISTED ADHESIVES. | | | | D) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES | | CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH | | ITEM #2 ABOVE. | | | | E) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT | | RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS | | FOR SMALL MISSILE IMPACT RESISTANT. | | | | F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY | | MULLION SIZE. | | | | G) FIXED WINDOWS AS SPECIFIED ON PLANS. | | | | H) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS. | | | | 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE | | PRODUCT APPROVALS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-07-31 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-07-31 |
Time |
14:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
destabro |
Date |
2017-07-31 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
destabro |
Date |
2017-07-31 |
Time |
15:00 |
Sent To |
B |
|
Notes |
2017-07-31 15:01:02 | 7/31/2017 - MET WITH APPLICANT - AWAITING PRODUCT | | APPROVAL FOR PAIRED CARRIAGE-STYLE GARAGE DOOR. DLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-07-31 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-07-21 |
Time |
15:51 |
Sent To |
|
|
Notes |
2017-07-27 15:31:09 | R23 TRAVELLING WITH 17010618 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-07-31 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-07-31 |
Time |
15:17 |
Sent To |
|
|
Notes |
2017-07-31 15:18:02 | $236.59 PAID. MU-2017-011708. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
HMOSER |
Date |
2017-07-31 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-07-31 |
Time |
14:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-07-31 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-07-31 |
Time |
14:40 |
Sent To |
|
|
Notes |
2017-07-31 14:41:41 | PLANS STAMPED ON 5/18/17 GPJ |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2017-07-31 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2017-07-31 |
Time |
15:18 |
Sent To |
|
|
Notes |
2017-07-31 15:19:33 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS AS REQ'D GENERAL | | LIMITATION #7. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT | | APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC | | DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN | | ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE | | INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS IF REQUIRED. | | | | B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON | | 02/01/16. | | | | C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL | | FOR LISTED ADHESIVES. | | | | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE | | PRODUCT APPROVALS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2017-07-31 |
|
|
Cont ID |
|
Sent By |
destabro |
Date |
2017-07-31 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
destabro |
Date |
2017-07-31 |
Time |
15:01 |
Sent To |
B |
|
Notes |
|
|