2017-08-18 06:59:40 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070813 |
| ADD: 300 CLEMATIS ST. SUITE: 2/ 2ND FLOOR |
| CONT: BUILTMORE CONTRACTING |
| TEL: 305-502-2464 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRIDAY AUGUST 18, 2017 |
| ACTION: DENIED |
| |
| 1) SHEET 004_DDA A-2ND-A1.1.1. THE DOOR TO THE EXIT |
| STAIRS CENTRAL TO THE BUILDING IS LABELED 234 BUT ON |
| THE DOOR SCHEDULE THIS EXIT DOOR DOES NOT PROVIDE ANY |
| INFORMATION AS TO THE SIZE AND FIRE RATING REQUIRED. |
| SHEET 003_DDA-2ND-AD1.1 THE DEMO PLAN HAS A NOTE 3 FOR |
| THIS DOOR. NOTE 3 IS THE CONTRACTOR SHALL REMOVE AND |
| STOCKPILE AT THE OWNERS SELECTION FOR BUILDING OWNERS |
| FUTURE USE ALL DOORS AND HARDWARE. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 104.9.1 USED MATERIALS AND EQUIPMENT. |
| THE USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH |
| MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS |
| PERMITTED. USED |
| EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS |
| APPROVED BY THE BUILDING OFFICIAL. |
| PLEASE PROVIDE THE FOR DOOR 234 IN THE DOOR SCHEDULE |
| COMPLIANCE WITH 2014 FBC-B 1008.1.1 SIZE OF DOOR AND |
| SECTION & TABLE 716.5 OPENING PROTECTIVES. |
| |
| 2) SHEET 012 DDA-2ND-A3.0.2 SEE DETAIL B TRANSFER TYPE |
| SHOWER PLEASE NOTE THE DETAIL SHOWS A GRAB BAR ONLY |
| AGAINST THE BACK WALL. PLEASE REFER TO THE |
| FBC-ACCESSIBILITY CODE TO FIGURE 608.3.1 FOR THE |
| REQUIRED PLACEMENT OF GRAB BAR IN A TRANSFER TYPE |
| SHOWER. |
| |
| 3) SHEET 012 DDA-2ND-A3.0.2 DOES NOT PROVIDE HOW |
| COMPLIANCE WITH SECTION 609.8 STRUCTURAL STRENGTH. |
| 609.8 STRUCTURAL STRENGTH. |
| ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS |
| USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS |
| IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, |
| MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| |
| 4) SHEET 012 DDA-2ND-A3.0.2 DETAIL B SHOWS THE SEAT |
| ABOUT 7 INCHES SHORT OF THE FRONT ENTRY WALL. CALIBRATE |
| AND MEASURE THE DISTANCE. PLEASE SHOW COMPLIANCE WITH |
| FBC-ACCESSIBILITY CODE 610.3 SHOWER COMPARTMENT SEATS |
| IN TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM |
| THE BACK WALL TO A POINT WITHIN 3 INCHES OF THE |
| COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES MAXIMUM ABOVE THE |
| BATHROOM FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 |
| OR 610.3.2. ALSO SEE FIGURE 610.3(B) L-SHAPED SEAT. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |