Plan Review Details - Permit 17070813
Plan Review Stops For Permit 17070813
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-14 Cont ID  
Sent By jwitmer Date 2017-09-14 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2017-09-14 Time 13:16 Sent To  
Notes
2017-09-14 13:47:552014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070813
 ADD: 300 CLEMATIS ST. SUITE: 2/ 2ND FLOOR
 CONT: BUILTMORE CONTRACTING
 TEL: 305-502-2464
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 14, 2017
 ACTION: BUILDING PROVISO
 2014 FBC-ACCESSIBILITY CODE- SHOWER SEAT AND REQUIRED
 BACKING. 610.4 STRUCTURAL STRENGTH. ALLOWABLE STRESSES
 SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A
 VERTICAL OR HORIZONTAL FORCE OF 250 LBS. IS APPLIED AT
 ANY POINT ON THE SEAT, FASTENER, MOUNTING DEVICE OR
 SUPPORTING STRUCTURE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-18 Cont ID  
Sent By jwitmer Date 2017-08-18 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2017-08-18 Time 06:00 Sent To  
Notes
2017-08-18 06:59:402014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070813
 ADD: 300 CLEMATIS ST. SUITE: 2/ 2ND FLOOR
 CONT: BUILTMORE CONTRACTING
 TEL: 305-502-2464
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUGUST 18, 2017
 ACTION: DENIED
  
 1) SHEET 004_DDA A-2ND-A1.1.1. THE DOOR TO THE EXIT
 STAIRS CENTRAL TO THE BUILDING IS LABELED 234 BUT ON
 THE DOOR SCHEDULE THIS EXIT DOOR DOES NOT PROVIDE ANY
 INFORMATION AS TO THE SIZE AND FIRE RATING REQUIRED.
 SHEET 003_DDA-2ND-AD1.1 THE DEMO PLAN HAS A NOTE 3 FOR
 THIS DOOR. NOTE 3 IS THE CONTRACTOR SHALL REMOVE AND
 STOCKPILE AT THE OWNERS SELECTION FOR BUILDING OWNERS
 FUTURE USE ALL DOORS AND HARDWARE.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 104.9.1 USED MATERIALS AND EQUIPMENT.
 THE USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH
 MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED
 EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS
 APPROVED BY THE BUILDING OFFICIAL.
 PLEASE PROVIDE THE FOR DOOR 234 IN THE DOOR SCHEDULE
 COMPLIANCE WITH 2014 FBC-B 1008.1.1 SIZE OF DOOR AND
 SECTION & TABLE 716.5 OPENING PROTECTIVES.
  
 2) SHEET 012 DDA-2ND-A3.0.2 SEE DETAIL B TRANSFER TYPE
 SHOWER PLEASE NOTE THE DETAIL SHOWS A GRAB BAR ONLY
 AGAINST THE BACK WALL. PLEASE REFER TO THE
 FBC-ACCESSIBILITY CODE TO FIGURE 608.3.1 FOR THE
 REQUIRED PLACEMENT OF GRAB BAR IN A TRANSFER TYPE
 SHOWER.
  
 3) SHEET 012 DDA-2ND-A3.0.2 DOES NOT PROVIDE HOW
 COMPLIANCE WITH SECTION 609.8 STRUCTURAL STRENGTH.
 609.8 STRUCTURAL STRENGTH.
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 4) SHEET 012 DDA-2ND-A3.0.2 DETAIL B SHOWS THE SEAT
 ABOUT 7 INCHES SHORT OF THE FRONT ENTRY WALL. CALIBRATE
 AND MEASURE THE DISTANCE. PLEASE SHOW COMPLIANCE WITH
 FBC-ACCESSIBILITY CODE 610.3 SHOWER COMPARTMENT SEATS
 IN TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM
 THE BACK WALL TO A POINT WITHIN 3 INCHES OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES MAXIMUM ABOVE THE
 BATHROOM FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1
 OR 610.3.2. ALSO SEE FIGURE 610.3(B) L-SHAPED SEAT.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-10-04 Cont ID  
Sent By jpearson Date 2017-10-04 Time 12:45 Rev Time 0.00
Received By jpearson Date 2017-10-04 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-09-18 Cont ID  
Sent By jpearson Date 2017-09-18 Time 11:40 Rev Time 0.00
Received By jpearson Date 2017-09-18 Time 11:40 Sent To  
Notes
2017-09-18 11:40:49CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PREVIOUS COMMENT NOT ADDRESSED SATISFACTORILY:
  
 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2 THIS SHOULD COMPLY WITH THE
 FOLLOWING:
  
 ASHRAE 90.1, 8.4.2:
  
 AUTOMATIC RECEPTACLE CONTROL. THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED:
 A. AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP
 RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS,
 ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING
 FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL
 WORKSTATIONS.
 B. AT LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR
 MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION
 DOCUMENTS.
  
 THIS CONTROL SHALL FUNCTION ON:
 A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED
 CONTROL DEVICE THAT TURNS RECEPTACLES OFF A SPECIFIC
 PROGRAMMED TIMES ? AN INDEPENDENT PROGRAM SCHEDULE
 SHALL BE PROVIDED FOR CONTROLLED AREAS OF NO MORE THAN
 5000 SQ. FT. AND NOT MORE THAN ONE FLOOR (THE OCCUPANT
 SHALL BE ABLE TO MANUALLY OVERRIDE THE CONTROL DEVICE
 FOR UP TO TWO HOURS), OR
 B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN 20 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR
 C. AN AUTOMATED SIGNAL FROM ANOTHER CONTROL OR ALARM
 SYSTEM THAT SHALL TURN RECEPTACLES OFF WITHIN 20
 MINUTES AFTER DETERMINING THAT THE AREA IS UNOCCUPIED.
  
 ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED
 TO VISUALLY DIFFERENTIATE THEM FROM UNCONTROLLED
 RECEPTACLES AND ARE TO BE UNIFORMLY DISTRIBUTED
 THROUGHOUT THE SPACE.
  
 PLUG IN DEVICES SHALL NOT BE USED TO COMPLY WITH
 SECTION 8.4.2
  
 EXCEPTIONS: RECEPTACLES FOR THE FOLLOWING SHALL NOT
 REQUIRE AN AUTOMATIC CONTROL DEVICE:
  
 1. RECEPTACLES SPECIFICALLY DESIGNATED FOR EQUIPMENT
 REQUIRING CONTINUOUS OPERATION (24 HOURS/DAY, 365
 DAYS/YEAR).
 2. SPACES WHERE AN AUTOMATIC CONTROL WOULD ENDANGER THE
 SAFETY OR SECURITY OF THE ROOM OR BUILDING OCCUPANTS.
  
 PROVIDE CORRECTION. FBC CE 405.7.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 13:19 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 13:19 Sent To  
Notes
2017-08-15 13:19:50CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 2. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN
 HOODS ETC. A NOTE WILL SUFFICE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-31 Cont ID  
Sent By scaldero Date 2017-08-31 Time 09:56 Rev Time 0.00
Received By scaldero Date 2017-08-31 Time 09:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-10 Cont ID  
Sent By scaldero Date 2017-08-10 Time 16:01 Rev Time 0.00
Received By scaldero Date 2017-08-10 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-04 Cont ID  
Sent By jpearson Date 2017-10-04 Time 12:48 Rev Time 0.00
Received By jpearson Date 2017-09-25 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-25 Cont ID  
Sent By cpuell Date 2017-09-25 Time 07:26 Rev Time 0.00
Received By cpuell Date 2017-08-30 Time 19:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-22 Cont ID  
Sent By ccole Date 2017-08-22 Time   Rev Time 0.00
Received By ccole Date 2017-08-08 Time 16:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-18 Cont ID  
Sent By ccole Date 2017-09-18 Time 11:41 Rev Time 0.00
Received By ccole Date 2017-09-18 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By ccole Date 2017-08-22 Time 11:36 Rev Time 0.00
Received By ccole Date 2017-08-22 Time 11:20 Sent To  
Notes
2017-08-22 11:48:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070813
 8/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE CORRIDORS 217 AND 233 CANNOT BE USED
 TO CONVEY RETURN AIR BACK TO AC 231- SEE SECTION 601.2.
  
 2) M2.1: THE LOUVERED MECHANICAL CLOSET DOORS SHALL BE
 NON-COMBUSTIBLE PER SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION, AND SECTION 602.2.1 FBC-14 MECHANICAL.
  
 3) M6.1: PLEASE PROVIDE EQUIPMENT SCHEDULES FOR THE
 EXISTING AC SYSTEMS.
  
 4) SHOW THE LOCATION OF THE NEW CONDENSER AND PROVIDE
 ENGINEERING AND THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION- SECTION 301.15.
  
 5) M2.1: VERIFY REQUIRED CLEARANCES FOR THE NEW O/A
 INTAKES- SECTION 401.4 AND INDICATE HOW THE OPENINGS
 WILL BE PROTECTED- SECTION 401.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By gjohnson Date 2017-09-22 Time 19:13 Rev Time 0.00
Received By gjohnson Date 2017-09-22 Time 19:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 08:14 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 08:14 Sent To  
Notes
2017-08-22 08:40:221ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WALLS AROUND THE MOP SINK SHALL COMPLY WITH FBC
 B 1210.2.2
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3. THE SIDE GRAB BAR FOR THE TOILET SHALL COMPLY WITH
 FBC ACC 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 4. PLEASE SHOW DIMENSIONS FOR SHOWER SEAT PER FBC ACC
 610.3 SHOWER COMPARTMENT SEATS.IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY.
 THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM
 FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR
 610.3.2.
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 21/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE L PORTION OF THE SEAT SHALL
 BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND THE
 FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND 15
 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF THE L
 SHALL BE 22 INCHES (560 MM) MINIMUM AND 23 INCHES
 MAXIMUM (585 MM) FROM THE MAIN SEAT WALL.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER
 TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 6. IN THE SHOWER ONLY ONE GRAB BAR IS SHOWN ON BACK
 WALL PLEASE SHOW COMPLIANCE WITH FBC ACC 608.3.1
 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 7. A BACKFLOW IS REQUIRED ON THE ICE MACHINE AND THE
 COFFEE MACHINE. PER FBC PL 608.3, 608.16.10
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-10-04 Cont ID  
Sent By jpearson Date 2017-10-04 Time 12:47 Rev Time 0.00
Received By jpearson Date 2017-10-04 Time 12:47 Sent To  
Notes
2017-09-22 19:15:12PLUMB DIG SIG OK /GPJ 9/22/17
2017-09-14 13:49:5609/14/2017
 ARCHITECTURAL SHEETS, SIGNATURE OK. JW
2017-08-22 12:10:03MECH DIG/SIGS OK- CCOLE