Plan Review Stops For Permit 17070785 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2017-08-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-08-01 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-08-01 |
Time |
14:52 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-08-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-07-21 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-07-21 |
Time |
13:47 |
Sent To |
|
|
Notes |
2017-07-21 14:18:13 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | ONLY ONE (1) SET OF SMALL DRAWINGS BROUGHT IN FOR | | REVIEW | | | | PLEASE LIST TYPE OF FUEL IN TANK. | | | | NEED TO DEFINE THE HAZARDOUS LOCATION AT AND AROUND | | TANK PER 500.4(A). | | | | VEEDEROOT CONDUIT LOOKS TO BE IN THE HAZARDOUS | | LOCATION. | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-07-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-07-21 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-07-19 |
Time |
11:41 |
Sent To |
|
|
Notes |
2017-07-20 11:42:01 | ELEC -$5000 |
|
|
|