Plan Review Details - Permit 17070728
Plan Review Stops For Permit 17070728
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-25 Cont ID  
Sent By   Date 2017-08-25 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2017-08-25 Time 07:12 Sent To  
Notes
2017-08-25 07:20:25BUILDING PROVISO:
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 (3.) ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH THICK
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES O.C. FOR 5/8-INCH THICK
 WATER-RESISTANT GYPSUM BACKING BOARD.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-08-16 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jwitmer Date 2017-07-28 Time 12:35 Rev Time  
Received By jwitmer Date 2017-07-28 Time 11:58 Sent To  
Notes
2017-07-28 12:34:082014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070728
 ADD: 1701 S. FLAGLER DR. SUITE: 204
 CONT: MARYJULI CONSTRUCTION
 TEL: 561-386-6032
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 28/ 2017
 ACTION: DENIED
  
 1) SHEET 1 DOES INDICATE A CEILING PLAN WHERE THE DROP
 CEILING (SOFFIT) IS BEING REMOVED. THERE IS A NOTE TO
 REFINISH THE CEILING WITH ? INCH METAL FURRING AND ?
 INCH GYPSUM BOARD. THE PLANS DO NOT PROVIDE A CODE
 COMPLIANT CEILING OVER THE NEW SHOWER AREA AND
 ENCLOSURE. PLEASE SHOW HOW COMPLIANCE WILL BE MET;
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 (3). ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH THICK WATER-RESISTANT GYPSUM
 BACKING BOARD AND MORE THAN 16 INCHES O.C. FOR 5/8-INCH
 THICK WATER-RESISTANT GYPSUM BACKING BOARD.
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-31 Cont ID  
Sent By jpearson Date 2017-08-31 Time 11:08 Rev Time 0.00
Received By jpearson Date 2017-08-31 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 13:45 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 13:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By jpearson Date 2017-07-27 Time 10:42 Rev Time 0.00
Received By jpearson Date 2017-07-27 Time 10:42 Sent To  
Notes
2017-07-27 10:55:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN REFERENCES THE 2008 NEC, WHICH IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 2. PLEASE INDICATE WHAT IS NEW AND WHAT IS EXISTING ON
 PLAN. IF BATH GFCI IS NEW, SHOW ON A 20 AMP CIRCUIT PER
 CODE. NEC 210.11(C)(3); FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-08-30 Cont ID  
Sent By pleduc Date 2017-08-30 Time   Rev Time 0.00
Received By pleduc Date 2017-08-29 Time 17:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By pleduc Date 2017-08-14 Time   Rev Time 0.00
Received By pleduc Date 2017-08-11 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-21 Cont ID  
Sent By pleduc Date 2017-07-21 Time   Rev Time 0.00
Received By pleduc Date 2017-07-21 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-31 Cont ID  
Sent By jpearson Date 2017-08-31 Time 11:08 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 14:01 Sent To  
Notes
2017-08-23 14:01:41B08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2017-08-09 Time 13:21 Sent To  
Notes
2017-08-10 13:21:16B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-28 Time 12:35 Rev Time 0.00
Received By lmarchan Date 2017-07-18 Time 16:40 Sent To  
Notes
2017-07-19 16:40:44B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-28 Cont ID  
Sent By jwitmer Date 2017-07-28 Time 12:33 Rev Time  
Received By jwitmer Date 2017-07-28 Time 11:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-08-29 Cont ID  
Sent By thunt Date 2017-08-29 Time 13:41 Rev Time 0.00
Received By thunt Date 2017-08-29 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 14:47 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By gjohnson Date 2017-07-26 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-07-26 Time 11:00 Sent To  
Notes
2017-07-26 12:48:311ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE COMPLETE FLOOR PLAN SHOWING ENTIRE
 UNIT. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  