Plan Review Details - Permit 17070726
Plan Review Stops For Permit 17070726
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-31 Cont ID  
Sent By skennedy Date 2017-08-31 Time 16:13 Rev Time 0.00
Received By skennedy Date 2017-08-31 Time 16:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-08 Cont ID  
Sent By jwitmer Date 2017-08-08 Time 06:09 Rev Time 0.00
Received By jwitmer Date 2017-08-08 Time 06:02 Sent To  
Notes
2017-08-08 06:09:122014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070726
 ADD: 400 N. FLAGLER DR.
 CONT:BESSENROTH BUILDERS
 TEL: 561-324-4871
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUGUST 08/2017
 ACTION: DENIED
  
 1) TO BE COMPLETED BY BESSENROTH BUILDERS.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By jwitmer Date 2017-07-27 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 16:06 Sent To  
Notes
2017-07-27 16:07:412014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070726
 ADD: 400 N. FLAGLER DR.
 CONT:BESSENROTH BUILDERS
 TEL: 561-324-4871
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 27/2017
 ACTION: DENIED
  
 1) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE
 THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-08-31 Cont ID  
Sent By jpearson Date 2017-08-31 Time 07:18 Rev Time 0.00
Received By jpearson Date 2017-08-31 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-21 Cont ID  
Sent By skennedy Date 2017-08-21 Time 12:25 Rev Time 0.00
Received By skennedy Date 2017-08-21 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-07 Cont ID  
Sent By jpearson Date 2017-08-07 Time 10:11 Rev Time 0.00
Received By jpearson Date 2017-08-07 Time 10:11 Sent To  
Notes
2017-08-07 10:10:55CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS COMMENT # 1 NOT ADDRESSED SATISFACTORILY.
 WRITING THE NAME OF THE ELECTRICAL CONTRACTOR ON THE
 PLAN DOES NOT SATISFY THE REQUIREMENTS OF FS 471.025, A
 SIGNATURE IS REQUIRED. PROVIDE AS PREVIOUSLY REQUESTED.
 FS 471.003(2)(H), 471.025. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jpearson Date 2017-07-28 Time 11:12 Rev Time 0.00
Received By jpearson Date 2017-07-28 Time 11:12 Sent To  
Notes
2017-07-28 11:14:30CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. SHOW LOCATION ON PLAN OF ANY ELECTRICAL FIXTURES TO
 BE REPLACED. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-08-29 Cont ID  
Sent By pleduc Date 2017-08-29 Time   Rev Time 0.00
Received By pleduc Date 2017-08-28 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-08-14 Cont ID  
Sent By pleduc Date 2017-08-14 Time   Rev Time 0.00
Received By pleduc Date 2017-08-11 Time 15:04 Sent To  
Notes
2017-08-11 16:54:402ND REVIEW
  
 1) CORRECT PLANS PER OTHER DEPARTMENT'S COMMENTS AND
 FIRE WILL PASS AND STAMP.
  
  
  
 2) IF ANY WALL TILE IS INVOLVED, FIRE ALARM DEVICES MAY
 BE AFECTED. FA WORK SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-24 Cont ID  
Sent By pleduc Date 2017-07-24 Time   Rev Time 0.00
Received By pleduc Date 2017-07-24 Time 12:33 Sent To  
Notes
2017-07-24 15:17:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) IF ANY WALL TILE IS INVOLVED, FIRE ALARM DEVICES MAY
 BE AFECTED. FA WORK SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-31 Cont ID  
Sent By skennedy Date 2017-08-31 Time 16:13 Rev Time 0.00
Received By skennedy Date 2017-08-25 Time 10:41 Sent To  
Notes
2017-08-28 10:42:06B04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 11:16 Rev Time 0.00
Received By gjohnson Date 2017-08-03 Time 13:20 Sent To  
Notes
2017-08-04 13:21:08B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-28 Cont ID  
Sent By jpearson Date 2017-07-28 Time 11:14 Rev Time 0.00
Received By jpearson Date 2017-07-20 Time 11:35 Sent To  
Notes
2017-07-21 11:36:08B14

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-08-31 Cont ID  
Sent By skennedy Date 2017-08-31 Time 16:13 Rev Time 0.00
Received By skennedy Date 2017-08-31 Time 16:13 Sent To  
Notes
2017-08-31 16:14:40MET W/ CUSTOMER. REVISED DESCRIPTION TO ADDRESS
 COMMENTS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-08-30 Cont ID  
Sent By tklarge Date 2017-08-30 Time 13:46 Rev Time 0.00
Received By tklarge Date 2017-08-30 Time 12:20 Sent To  
Notes
2017-08-30 12:41:021) SUBMIT AN APPLICATION FROM A CURRENTLY LICENSED
 PLUMBING CONTRACTOR FOR THE REMOVAL AND REPLACEMENT OF
 THE PLUMBING FIXTURES. FL. STATUTE 489.105.
 2) THERE ARE 3 PLANS IN THIS SUBMITTAL. ONE IS VOID,
 AND THE OTHER TWO HAVE DIFFERENT NOTES ON EACH OF
 THEM.SUBMIT TWO SETS OF PLANS THAT CORRELATE AND
 CLEARLY SHOW THE SCOPE OF WORK.WPB AMEND. TO FBC SEC.
 107.2.1.
 3) THERE IS A NOTE ON THE PLAN THAT READS "REMOVE AND
 REPLACE LIKE FOR LIKE." LIKE FOR LIKE WHAT? CLEARLY
 INDICATE ON THE PLANS WHAT EXACTLY IS BEING REMOVED AND
 REPLACED. WPB AMEND TO FBC SEC. 107.2.1.
 4) WILL THE SHOWER VALVES BE REPLACED? INDICATE ON THE
 PLANS. IF SO, THE VALVES SHALL COMPLY WITH 2014
 FBC-PLUMBING SEC. 424.3.
 5) THE LEVEL OF HANDICAPPED ACCESSIBILITY FOR THE
 SHOWERS AND THE ACCESSIBLE TOILET STALLS SHALL NOT BE
 REDUCED. ANY REMODEL WORK SHALL MAINTAIN OR MAY EXCEED
 THE CURRENT LEVEL OF ACCESSIBILITY PROVIDED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 11:15 Rev Time 0.00
Received By gjohnson Date 2017-08-21 Time 11:15 Sent To  
Notes
2017-08-21 11:16:291ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
 1.PUMBING WILL BE APPROVED WHEN ALL OTHER TRADES HAVE
 BEEN APPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-27 Cont ID  
Sent By gjohnson Date 2017-07-27 Time 08:39 Rev Time 0.00
Received By gjohnson Date 2017-07-26 Time 17:22 Sent To  
Notes
***NONE***