Plan Review Details - Permit 17070709
Plan Review Stops For Permit 17070709
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-18 Time 11:48 Sent To  
Notes
2017-07-19 11:49:15MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By ccole Date 2017-07-27 Time 09:34 Rev Time 0.00
Received By ccole Date 2017-07-27 Time 09:34 Sent To  
Notes
2017-07-27 09:59:341ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070709
 7/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PALM BEACH COUNTY APPRAISERS REPORT INDICATES
 THE RESIDENCE HAS NEVER HAD AN AC SYSTEM, AND THERE IS
 NO RECORD OF AN ISSUED PERMIT FOR A SYSTEM IN THE CITY
 PERMIT FILES- PLEASE CORRECT THE PLAN TO INDICATE A NEW
 SYSTEM IS BEING INSTALLED.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION
 1078.2.1 WPB AMENDMENTS TO THE FBC.
  
 3) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION R403.6.1 FBC-14 ENERGY CONSERVATION.
  
 4) REFER TO SECTION R101.4.5 AND SUBMIT AN ENERGY
 EFFICIENCY COMPLIANCE REPORT FOR THE NEW CONDITIONED
 SPACE. SEE TABLE R101.5.1 FOR COMPLAINCE FORMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  