Plan Review Details - Permit 17070699
Plan Review Stops For Permit 17070699
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-02 Cont ID  
Sent By wjolin Date 2017-08-02 Time 09:40 Rev Time 0.00
Received By wjolin Date 2017-08-02 Time 09:34 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By wjolin Date 2017-07-21 Time 12:39 Rev Time 0.00
Received By wjolin Date 2017-07-21 Time 12:34 Sent To M
Notes
2017-07-21 12:39:151555 PALM BEACH LAKES BOULEVARD - #150-155
 PERMIT #17070699
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN INDICATES CITY WATER SUPPLY ONLY. THIS BUILDING
 HAS A FIRE PUMP. PER NFPA 13 (2007 EDITION) SECTION
 24.2.1.2, PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE
 TESTED AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING
 PRESSURE AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS
 FOR 2-HOURS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-28 Time 14:31 Sent To  
Notes
2017-07-31 14:31:59RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-18 Time 16:35 Sent To  
Notes
2017-07-19 16:35:53ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-08 Cont ID  
Sent By ccole Date 2017-08-08 Time 09:24 Rev Time 0.00
Received By ccole Date 2017-08-08 Time 09:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By ccole Date 2017-07-28 Time 10:01 Rev Time 0.00
Received By ccole Date 2017-07-28 Time 10:01 Sent To  
Notes
2017-07-28 10:03:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070699
 7/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS REQUIRE THE SIGNATURE OF THE PERSON WHO
 PREPARED THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO
 THE FBC: ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  