Plan Review Details - Permit 17070695
Plan Review Stops For Permit 17070695
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-04 Cont ID  
Sent By cthroop Date 2017-08-04 Time 15:11 Rev Time 0.00
Received By cthroop Date 2017-08-04 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By cthroop Date 2017-07-24 Time 08:13 Rev Time 0.00
Received By cthroop Date 2017-07-24 Time 07:46 Sent To E
Notes
2017-07-24 08:17:30BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUBMITTAL INCLUDES A SPEC DATA SHEET FOR PROTECTO
 WRAP WHISPER MAT CS. THIS IS NOT INDICATED ON
 APPLICATION. IF FLOORING IS PART OF THIS SUBMITTAL,
 PLEASE PROVIDE THE FOLLOWING:
  
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 *
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED FLOORING
 (TILE/MARBLE/LAMINATE/WOOD/OTHER).
 4. STATED VALUE OF WORK.
 5. EXISTING SITE CONDITIONS:
 A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN
 CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL)
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON
 EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S,
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09 - FOR LAMINATE
 AND WOOD FLOORING.
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-24 Cont ID  
Sent By jleahy Date 2017-07-24 Time 16:16 Rev Time 0.00
Received By jleahy Date 2017-07-24 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-24 Cont ID  
Sent By jleahy Date 2017-07-24 Time 16:16 Rev Time 0.00
Received By jleahy Date 2017-07-18 Time 11:32 Sent To  
Notes
2017-07-20 11:32:35BLDG MISC 2


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved