2017-07-19 17:17:47 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070554 |
| ADD: 2500 METROCENTRE BLVD. W. SUITE # 5 |
| CONT: CHANDLER CONSTRUCTION |
| TEL: 561-791-6934 |
| E-MAIL: JOHN@ BUILDCCC.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JULY 20/ 2017 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET A-0.0 INDICATES IN THE NOTES ON THE |
| LEFT SIDE OF THE PLANS THE SQUARE FOOTAGE OF 1,787 SQ. |
| FT. FOR THIS TENANT SPACE AND AN OCCUPANT LOAD OF 17. |
| PLEASE SEE THE 2012 IBC-B CODE COMMENTARY WE NEVER |
| ROUND DOWN ON OCCUPANTS NOR FRACTIONS OF OCCUPANTS. |
| OCCUPANTS ONLY COME IN WHOLE NUMBERS, YOU ALWAYS ROUND |
| UP. 2012 IBC-B 1004.1.2/ 2014 FBC-B TABLE 1004.1.2 AND |
| THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA INFORMAL |
| CODE INTERPRETATION REPORT 5479. PLEASE NOTE ON THE |
| SAME SHEET JUST RIGHT ON THE FLOOR PLAN THE SAME NOTE |
| REAPPEARS PLEASE UPDATE PLANS TO THE CORRECT OCCUPANT |
| LOAD. |
| |
| 2A) THE COVERSHEET A-0.0 INDICATES AN OCCUPANCY |
| SEPARATION WALL BETWEEN A I-4 DAYCARE OCCUPANCY AND |
| BUSINESS OCCUPANCY WITH A 2 HOUR FIRE RATING PER TABLE |
| 508.4. THE PLANS DO NOT INDICATE A WALL TYPE OF |
| CONSTRUCTION FOR WALL REPAIRS FOR WATER PIPES AND |
| ELECTRICAL CONDUITS THAT WILL BE BEING INSTALLED IN |
| THIS WALL, SEE SECTION 707.3.9 SEPARATED OF |
| OCCUPANCIES. WHERE THE PROVISIONS OF SECTION 508.4 ARE |
| APPLICABLE, THE FIRE BARRIER SEPARATING MIXED |
| OCCUPANCIES SHALL HAVE A FIRE-RESISTANCE RATING OF NOT |
| LESS THAN THAT INDICATED IN TABLE 508.4 BASED ON THE |
| OCCUPANCIES BEING SEPARATED. NEITHER DOES THE PLAN |
| INDICATE HOW FAR THE LAPS HAVE TO BE FORM ONE LAYER TO |
| ANOTHER. |
| |
| 715.2 INSTALLATION. A FIRE-RESISTANT JOINT SYSTEM SHALL |
| BE SECURELY INSTALLED IN ACCORDANCE WITH THE LISTING |
| CRITERIA IN OR ON THE JOINT FOR ITS ENTIRE LENGTH SO AS |
| NOT TO DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY |
| TO ACCOMMODATE EXPECTED BUILDING MOVEMENTS AND TO |
| RESIST THE PASSAGE OF FIRE AND HOT GASES. |
| |
| 715.3 FIRE TEST CRITERIA. FIRE-RESISTANT JOINT SYSTEMS |
| SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF |
| EITHER ASTM E 1966 OR UL 2079. NONSYMMETRICAL WALL |
| JOINT SYSTEMS SHALL BE TESTED WITH BOTH FACES EXPOSED |
| TO THE FURNACE, AND THE ASSIGNED FIRE-RESISTANCE RATING |
| SHALL BE THE SHORTEST DURATION OBTAINED FROM THE TWO |
| TESTS. WHEN EVIDENCE IS FURNISHED TO SHOW THAT THE WALL |
| WAS TESTED WITH THE LEAST FIRE-RESISTANT SIDE EXPOSED |
| TO THE FURNACE, SUBJECT TO ACCEPTANCE OF THE BUILDING |
| OFFICIAL, THE WALL NEED NOT BE SUBJECTED TO TESTS FROM |
| THE OPPOSITE SIDE. |
| |
| 2B) THE COVERSHEET A-0.0 INDICATES AN OCCUPANCY |
| SEPARATION WALL BETWEEN A I-4 DAYCARE OCCUPANCY AND |
| BUSINESS OCCUPANCY WITH A 2 HOUR FIRE RATING PER TABLE |
| 508.4. THE PLANS (ARCHITECTURAL NOR M-E-P) DO NOT |
| INDICATE HOW TO FIRE RATE THE PENETRATIONS IN THE 2HR. |
| OCCUPANCY SEPARATION WALLS. PLEASE PROVIDE COMPLIANCE |
| WITH FBC-B SECTION 714 714.3.1 THROUGH PENETRATIONS. |
| THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS |
| SHALL COMPLY WITH SECTION 714.3.1.1 OR 714.3.1.2. |
| 3) SHEET A-1.0 THE FLOOR PLAN IDENTIFIES (3) DOORS R1, |
| R2 & R3, THE DOOR SCHEDULE ON SHEET A-4.0 THESE ARE |
| DOORS TO BE RE-USED. PLEASE NOTE THERE ARE NO NOTES IN |
| THE DOOR SCHEDULE FOR THESE DOORS. CODE COMPLIANCE FOR |
| THESE DOORS CANNOT BE DETERMINED. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 104.9.1 USED MATERIALS AND EQUIPMENT. |
| THE USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH |
| MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS |
| PERMITTED. USED |
| EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS |
| APPROVED BY THE BUILDING OFFICIAL. |
| |
| THE USED DOORS MUST MEET THE REQUIREMENTS OF 1008.1.1 |
| SIZE OF DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING |
| SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND |
| SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES . CLEAR |
| OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| WITH THE DOOR OPEN 90 DEGREES, MINIMUM OF A 36 INCH |
| DOOR. |
| |
| 4) SHEET A-3.0 DETAIL # 3 THE BREAK ROOM ELEVATION OF |
| CABINETS SHOWS A MICROWAVE ON A SHELF, THE SHELF AT THE |
| HEIGHT OF 54 INCHES, PLEASE SHOW COMPLIANCE WITH; |
| 4A)2014 FBC-ACCESS. CODE. REACH RANGES 308.2.2 |
| OBSTRUCTED HIGH REACH OR308.3.2 OBSTRUCTED HIGH REACH, |
| BOTH THE HIGHEST REACH RANGE IS 48 INCHES FROM FINISH |
| FLOOR. |
| |
| 4B) PLEASE ALSO SHOW HOW CODE COMPLIANCE WITH BE |
| ACHIEVED FOR ACCESS. CODE 309.2-309.4. |
| |
| 5) SHEET A-3.0 DETAILS FOR TOILETS 108 & 109 BOTH SHOW |
| A MIRROR THE HEIGHT TO THE BOTTOM OF THE MIRROR |
| INDICATES A HEIGHT OF 40 INCHES BUT DOES NOT INDICATE |
| WHERE THE 40 INCHES IS MEASURED TO. PLEASE REVIEW |
| SECTION 603.3 OF THE ACCESSIBILITY CODE THE BOTTOM OF |
| THE MIRROR IS TO BE MEASURED TO THE BOTTOM EDGE OF THE |
| REFLECTIVE SURFACE. |
| |
| 6) THE ARCHITECTS SEAL IS APPROXIMATELY 1 INCH IN |
| DIAMETER. THE ARCHITECTS SEAL SHALL COMPLY WITH: |
| ARCHITECT. 61G1-16.002(1) THE SEAL SHALL BE |
| APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR LINES |
| BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE WORDS |
| ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS |
| ?REGISTERED ARCHITECT. ? |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |