Plan Review Details - Permit 17070554
Plan Review Stops For Permit 17070554
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By jwitmer Date 2017-08-18 Time 05:59 Rev Time 0.00
Received By jwitmer Date 2017-08-18 Time 05:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 07:30 Rev Time  
Received By jwitmer Date 2017-07-19 Time 16:56 Sent To  
Notes
2017-07-19 17:17:472014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070554
 ADD: 2500 METROCENTRE BLVD. W. SUITE # 5
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: JOHN@ BUILDCCC.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 20/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET A-0.0 INDICATES IN THE NOTES ON THE
 LEFT SIDE OF THE PLANS THE SQUARE FOOTAGE OF 1,787 SQ.
 FT. FOR THIS TENANT SPACE AND AN OCCUPANT LOAD OF 17.
 PLEASE SEE THE 2012 IBC-B CODE COMMENTARY WE NEVER
 ROUND DOWN ON OCCUPANTS NOR FRACTIONS OF OCCUPANTS.
 OCCUPANTS ONLY COME IN WHOLE NUMBERS, YOU ALWAYS ROUND
 UP. 2012 IBC-B 1004.1.2/ 2014 FBC-B TABLE 1004.1.2 AND
 THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA INFORMAL
 CODE INTERPRETATION REPORT 5479. PLEASE NOTE ON THE
 SAME SHEET JUST RIGHT ON THE FLOOR PLAN THE SAME NOTE
 REAPPEARS PLEASE UPDATE PLANS TO THE CORRECT OCCUPANT
 LOAD.
  
 2A) THE COVERSHEET A-0.0 INDICATES AN OCCUPANCY
 SEPARATION WALL BETWEEN A I-4 DAYCARE OCCUPANCY AND
 BUSINESS OCCUPANCY WITH A 2 HOUR FIRE RATING PER TABLE
 508.4. THE PLANS DO NOT INDICATE A WALL TYPE OF
 CONSTRUCTION FOR WALL REPAIRS FOR WATER PIPES AND
 ELECTRICAL CONDUITS THAT WILL BE BEING INSTALLED IN
 THIS WALL, SEE SECTION 707.3.9 SEPARATED OF
 OCCUPANCIES. WHERE THE PROVISIONS OF SECTION 508.4 ARE
 APPLICABLE, THE FIRE BARRIER SEPARATING MIXED
 OCCUPANCIES SHALL HAVE A FIRE-RESISTANCE RATING OF NOT
 LESS THAN THAT INDICATED IN TABLE 508.4 BASED ON THE
 OCCUPANCIES BEING SEPARATED. NEITHER DOES THE PLAN
 INDICATE HOW FAR THE LAPS HAVE TO BE FORM ONE LAYER TO
 ANOTHER.
  
 715.2 INSTALLATION. A FIRE-RESISTANT JOINT SYSTEM SHALL
 BE SECURELY INSTALLED IN ACCORDANCE WITH THE LISTING
 CRITERIA IN OR ON THE JOINT FOR ITS ENTIRE LENGTH SO AS
 NOT TO DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY
 TO ACCOMMODATE EXPECTED BUILDING MOVEMENTS AND TO
 RESIST THE PASSAGE OF FIRE AND HOT GASES.
  
 715.3 FIRE TEST CRITERIA. FIRE-RESISTANT JOINT SYSTEMS
 SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF
 EITHER ASTM E 1966 OR UL 2079. NONSYMMETRICAL WALL
 JOINT SYSTEMS SHALL BE TESTED WITH BOTH FACES EXPOSED
 TO THE FURNACE, AND THE ASSIGNED FIRE-RESISTANCE RATING
 SHALL BE THE SHORTEST DURATION OBTAINED FROM THE TWO
 TESTS. WHEN EVIDENCE IS FURNISHED TO SHOW THAT THE WALL
 WAS TESTED WITH THE LEAST FIRE-RESISTANT SIDE EXPOSED
 TO THE FURNACE, SUBJECT TO ACCEPTANCE OF THE BUILDING
 OFFICIAL, THE WALL NEED NOT BE SUBJECTED TO TESTS FROM
 THE OPPOSITE SIDE.
  
 2B) THE COVERSHEET A-0.0 INDICATES AN OCCUPANCY
 SEPARATION WALL BETWEEN A I-4 DAYCARE OCCUPANCY AND
 BUSINESS OCCUPANCY WITH A 2 HOUR FIRE RATING PER TABLE
 508.4. THE PLANS (ARCHITECTURAL NOR M-E-P) DO NOT
 INDICATE HOW TO FIRE RATE THE PENETRATIONS IN THE 2HR.
 OCCUPANCY SEPARATION WALLS. PLEASE PROVIDE COMPLIANCE
 WITH FBC-B SECTION 714 714.3.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS
 SHALL COMPLY WITH SECTION 714.3.1.1 OR 714.3.1.2.
 3) SHEET A-1.0 THE FLOOR PLAN IDENTIFIES (3) DOORS R1,
 R2 & R3, THE DOOR SCHEDULE ON SHEET A-4.0 THESE ARE
 DOORS TO BE RE-USED. PLEASE NOTE THERE ARE NO NOTES IN
 THE DOOR SCHEDULE FOR THESE DOORS. CODE COMPLIANCE FOR
 THESE DOORS CANNOT BE DETERMINED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 104.9.1 USED MATERIALS AND EQUIPMENT.
 THE USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH
 MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED
 EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS
 APPROVED BY THE BUILDING OFFICIAL.
  
 THE USED DOORS MUST MEET THE REQUIREMENTS OF 1008.1.1
 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING
 SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND
 SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES . CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES, MINIMUM OF A 36 INCH
 DOOR.
  
 4) SHEET A-3.0 DETAIL # 3 THE BREAK ROOM ELEVATION OF
 CABINETS SHOWS A MICROWAVE ON A SHELF, THE SHELF AT THE
 HEIGHT OF 54 INCHES, PLEASE SHOW COMPLIANCE WITH;
 4A)2014 FBC-ACCESS. CODE. REACH RANGES 308.2.2
 OBSTRUCTED HIGH REACH OR308.3.2 OBSTRUCTED HIGH REACH,
 BOTH THE HIGHEST REACH RANGE IS 48 INCHES FROM FINISH
 FLOOR.
  
 4B) PLEASE ALSO SHOW HOW CODE COMPLIANCE WITH BE
 ACHIEVED FOR ACCESS. CODE 309.2-309.4.
  
 5) SHEET A-3.0 DETAILS FOR TOILETS 108 & 109 BOTH SHOW
 A MIRROR THE HEIGHT TO THE BOTTOM OF THE MIRROR
 INDICATES A HEIGHT OF 40 INCHES BUT DOES NOT INDICATE
 WHERE THE 40 INCHES IS MEASURED TO. PLEASE REVIEW
 SECTION 603.3 OF THE ACCESSIBILITY CODE THE BOTTOM OF
 THE MIRROR IS TO BE MEASURED TO THE BOTTOM EDGE OF THE
 REFLECTIVE SURFACE.
  
 6) THE ARCHITECTS SEAL IS APPROXIMATELY 1 INCH IN
 DIAMETER. THE ARCHITECTS SEAL SHALL COMPLY WITH:
 ARCHITECT. 61G1-16.002(1) THE SEAL SHALL BE
 APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR LINES
 BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE WORDS
 ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS
 ?REGISTERED ARCHITECT. ?
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By jpearson Date 2017-08-21 Time 09:16 Rev Time 0.00
Received By jpearson Date 2017-08-21 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By jpearson Date 2017-07-25 Time 12:32 Rev Time 0.00
Received By jpearson Date 2017-07-25 Time 12:32 Sent To  
Notes
2017-07-25 12:36:53CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD SUMMARY FOR WWA PROVIDED SHOWS C PHASE OF 600
 AMP DISCONNECT OVERLOADED. PROVIDE CORRECTION. NEC
 230.79
 2. CIRCUIT 17,19 IN PANEL A1 SHOWS THE DRYER WITH #12
 WIRE ON A 30 AMP BREAKER. PROVIDE CORRECTION. NEC
 240.4, 310.15(B)(16)
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC C405.7.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By pleduc Date 2017-08-17 Time   Rev Time 0.00
Received By pleduc Date 2017-08-16 Time 16:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By pleduc Date 2017-07-24 Time   Rev Time 0.00
Received By pleduc Date 2017-07-24 Time 12:28 Sent To  
Notes
2017-07-24 14:08:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO DOOR SCHEDULE.
  
 PLEASE PROVIDE A DOOR SCHEDULE TO INCLUDE, EXISTING,
 RE-USED AND NEW DOORS, INCLUDING HARDWARE.
  
  
  
  
 2) THERE ARE TWO SEPARATE FIRE WALL TYPES INDICATED
 THAT MAY INCLUDE SOME TYPE CONSTRUCTION WORK TO THEM OR
 WITHIN THEM. HOWEVER, THERE IS NO LISTED FIRE WALL CALL
 OUT FOR PENETRATIONS OR RE-CONSTRUCTIONS DUE TO THE
 REMODEL.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE LISTED FIRE
 WALL(S).
  
  
  
  
 3) THERE IS NO INDICATION OF AN EXISTING FIRE ALARM OR
 FIRE SPRINKLER SYSTEM.
  
 PLEASE REVIEW EXISING CONDITIONS AND PROVIDE OF
 APPLICABLE NOTE AND/OR THE SUBMITTAL OF FUTURE SHOP
 DRAWINGS FOR THE WORK.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-10 Time 14:44 Sent To  
Notes
2017-08-11 14:45:06B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-27 Cont ID  
Sent By cpuell Date 2017-07-27 Time 11:20 Rev Time 0.00
Received By cpuell Date 2017-07-14 Time 11:01 Sent To  
Notes
2017-07-18 11:01:14B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-18 Time   Rev Time 0.00
Received By jwitmer Date 2017-08-18 Time 05:41 Sent To  
Notes
2017-08-18 05:55:08PALM BEACH COUNTY IMPACT FEE ASSESSMENT
 AUGUST 04/2017
 OCCUPANCY: BUSINESS
 FEES: NO FEES DUE
 PERMIT TECH ID: DB

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By jwitmer Date 2017-07-27 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 16:35 Sent To  
Notes
2017-07-27 16:36:26IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By ccole Date 2017-08-24 Time 14:15 Rev Time 0.00
Received By ccole Date 2017-08-24 Time 14:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By ccole Date 2017-07-27 Time 16:27 Rev Time 0.00
Received By ccole Date 2017-07-27 Time 16:26 Sent To  
Notes
2017-07-27 16:33:051ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070554
 7/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE DIMENSIONS OF THE MAIN SUPPLY AND RETURN
 TRUNK LINES- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By gjohnson Date 2017-08-23 Time 09:50 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By gjohnson Date 2017-07-25 Time 15:57 Rev Time 0.00
Received By gjohnson Date 2017-07-25 Time 15:42 Sent To  
Notes
2017-07-25 17:19:541ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 THE TOP OF THE GRIPING SURFACE. PER FBC ACC 609.4
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3. LAVATORY'S SHALL COMPLY WITH FBC PL TEMPERED WATER
 DELIVERED THROUGH A TEMPERATURE LIMITING DEVISE THAT
 COMPILES WITH ASSE 1070
  
 4. PROVIDE BACKFLOW FOR ICE MAKER PER FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  