Plan Review Details - Permit 17070538
Plan Review Stops For Permit 17070538
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-29 Cont ID  
Sent By rmcdouga Date 2017-09-29 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2017-09-29 Time 18:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-28 Cont ID  
Sent By rmcdouga Date 2017-08-28 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2017-08-28 Time 16:49 Sent To  
Notes
2017-08-28 19:03:00PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTRACOASTAL WATERWAY WHICH IS SURFACE ROUGHNESS D. IN
 THE WIND DESIGN TABLE ON SHEET A101, THE SURFACE
 ROUGHNESS IS LISTED AS B WHEN IT IS ACTUALLY D FOR THIS
 PROJECT AS STATED IN THE PREVIOUS SENTENCE. SEE FBC-R
 301.2.1.4 AND R 301.2.1.4.3.
  
 2) ON SHEET A104 THE ELEVATIONS AT THE BOTTOM OF THE
 SHEET ARE BOTH INCORRECTLY IDENTIFIED. THEY SHOULD BE
 THE PROPOSED WEST AND THE PROPOSED NORTH ELEVATIONS.
 PLEASE CORRECT. FBC 107.2.1
  
 3) THE PROPOSED ARMOR SCREEN HAS A MAXIMUM DESIGN
 PRESSURE OF -60 PSF AND ONE OF THE DOOR OPENINGS
 REQUIRES -61.0 PSF. THIS EXCEEDS THE ARMOR SCREEN
 DESIGN PRESSURE. FBC-R 301.2.1
  
 4) EXPLAIN HOW A PERSON WILL BE ABLE TO ENTER AND LEAVE
 THE DWELLING WITH THE ARMOR SCREEN INSTALLED OVER THE
 ONLY EGRESS DOOR TO THE SECOND STORY THAT IS LOCATED ON
 THE FIRST FLOOR. FBC-R310.4
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-03 Cont ID  
Sent By rmcdouga Date 2017-08-03 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2017-08-02 Time 18:39 Sent To  
Notes
2017-08-03 10:59:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING TO THE FBC EXISTING BUILDING SECTION 505,
 THIS IS A LEVEL 3 ALTERATION.
  
 2) BASED ON THE PLANS THAT WERE SUBMITTED, THIS
 STRUCTURE HAS A MEAN ROOF HEIGHT OF 23 FEET AND IS
 LOCATED IN EXPOSURE CATEGORY "D" WITH A 175 MPH VULT
 WIND SPEED. PLEASE PROVIDE THE WINDSPEED DESIGN DATA ON
 THE PLANS. FBC-R301.2.1
  
 3) THE REQUIRED DESIGN PRESSURES FOR THE WINDOWS AND
 DOORS THAT ARE SPECIFIED ON THE PLANS APPEAR TO BE
 BASED ON EXPOSURE CATEGORY "C". PLEASE REVIEW AND
 ADJUST AS NECESSARY. FBC-R301.1
  
 4) THE REQUIRED DESIGN PRESSURES FOR THE NEW SECTIONAL
 GARAGE DOORS WERE NOT SPECIFIED ON THE PLANS. PLEASE
 SPECIFY THEM ON THE PLANS. FBC 107.2.1
  
 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 6) ON SHEET A104 THE WEST AND NORTH ELEVATIONS ARE BOTH
 INCORRECTLY IDENTIFIED AS EAST ELEVATIONS. PLEASE
 CORRECT. FBC 107.2.1
  
 7) PLEASE IDENTIFY THE REQUIRED EGRESS WINDOW FOR THE
 SECOND FLOOR BEDROOM ON THE PLANS. FBC-R310.1 EMERGENCY
 ESCAPE AND RESCUE REQUIRED. FBC-R310.1.1 MINIMUM
 OPENING AREA. ALL EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE
 FEET
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-10-03 Cont ID  
Sent By jpearson Date 2017-10-03 Time 07:50 Rev Time 0.00
Received By jpearson Date 2017-10-03 Time 07:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-09-13 Cont ID  
Sent By jpearson Date 2017-09-13 Time 16:17 Rev Time 0.00
Received By jpearson Date 2017-09-13 Time 16:17 Sent To  
Notes
2017-09-13 16:15:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY.
 ALL OUTLETS IN GARAGE MUST BE GFCI PROTECTED, INCLUDING
 GARAGE DOOR OPENER. PROVIDE CORRECTION. NEC 210.8; FBC
 RE3902.2
 2. PREVIOUS COMMENT #8 NOT ADDRESSED SATISFACTORILY.
 PROVIDE ACCURATE LOAD CALCULATION. IT IS NOT
 PERMISSIBLE TO APPLY DEMAND FACTORS TO PANEL G AND
 INCLUDE THAT TOTAL IN THE SERVICE CALCULATION WHICH
 ALSO APPLIES DEMAND FACTORS. ADD ALL LOADS TOGETHER
 BEFORE APPLYING DEMAND FACTORS. NEC 220; FBC RE3602.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-31 Cont ID  
Sent By jpearson Date 2017-07-31 Time 12:29 Rev Time 0.00
Received By jpearson Date 2017-07-31 Time 12:28 Sent To  
Notes
2017-07-31 12:28:54CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. GARAGE DOES NOT SHOW ANY OUTLETS. CODE STATES: "AT
 LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO THOSE FOR
 SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN EACH
 BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH DETACHED
 GARAGE OR ACCESSORY BUILDING WITH ELECTRIC POWER".
 PROVIDE OUTLET. NEC 210.52(G); FBC RE3901.9
 2. RECEPTACLES IN GARAGE AND STORAGE AREAS REQUIRE GFCI
 PROTECTION. NEC 210.8; FBC RE3902.2
 3. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
 4. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. PROVIDE SMOKE
 ALARM ON EACH STORY OF THE DWELLING. FBC R315.1, R314.3
 5. SERVICE CALCULATION SHOWS SMALL APPLIANCE CIRCUITS
 ON A 15 AMP CIRCUIT. PROVIDE CORRECTION. NEC
 210.11(C)(1), 210.52(B)(3); FBC RE3703.2
 6. THERE IS NO A/C EQUIPMENT SHOWN ON ELECTRICAL PLAN,
 BUT THERE IS A VALUE INCLUDED IN THE CALCULATION FOR AN
 A/C. PROVIDE DETAILS OF EQUIPMENT AND ASSOCIATED WIRING
 ON PLAN AND PANEL SCHEDULE. FBC 107.2.1, NEC 215.5
 7. RISER DIAGRAM DOES NOT IDENTIFY THE SIZE OF MAIN 1
 OF 2. PROVIDE DETAILS ON RISER, INCLUDING ANY OTHER
 MAINS AND THEIR RESPECTIVE SIZES. NEC 215.5; FBC
 107.2.1
 8. LOAD CALCULATION IS NOT ACCURATE AND HAS CONFLICTING
 INFORMATION ON IT. FOR INSTANCE, WHY DOES IT SAY THE
 LIGHTING LOAD IS "2500 SQ. FT X 3VA= 7500 WATTS", BUT
 THE CALCULATION INCLUDES 3300 WATTS FOR GENERAL
 LIGHTING LOAD. ALSO, MATH IS NOT CORRECT. BY MY
 CALCULATION, A MINIMUM AMPACITY LOAD ON THE SERVICE IS
 102 AMPS FOR THE GARAGE PORTION, AND IT ONLY SUPPLIED
 BY A 100 AMP SERVICE. HOWEVER, WHAT IS BEING FED FROM
 PANEL G AS OPPOSED TO PANEL GH IS NOT CLEAR(SEE COMMENT
 9). PROVIDE CORRECTION FOR CALCULATIONS AND SERVICE
 EQUIPMENT AS NECESSARY. PROVIDE LOAD CALCULATION FOR
 MAIN SERVICE TO SHOW IT IS SUFFICIENTLY SIZED. NEC 220,
 215.5, 408.30; FBC RE3602.3, FBC 107.2.1
 9. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. RISER SHOWS 2 DIFFERENT
 FEEDERS TO 2 PANELS. PROVIDE CORRECTION. NEC 225.30
 10. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE.
 PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM
 AND WIRING. NEC 250.32; FBC RE3607.3
 11. PROVIDE PANEL SCHEDULE FOR PANEL TO BE USED (PANEL
 G OR PANEL GH?). INCLUDE WIRE AND BREAKER SIZES FOR
 EACH CIRCUIT, AND AFCI OR GFCI PROTECTION AS REQUIRED
 PER CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 12. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 10. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE.
 PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM
 AND WIRING. NEC 250.32; FBC RE3607.3
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-10-05 Cont ID  
Sent By rmcdouga Date 2017-10-05 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2017-10-05 Time 16:56 Sent To  
Notes
2017-10-05 16:56:39RESUB GIVEN TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-03 Cont ID  
Sent By jpearson Date 2017-10-03 Time 07:50 Rev Time 0.00
Received By jpearson Date 2017-09-22 Time 15:37 Sent To  
Notes
2017-09-25 15:38:05R01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-25 Cont ID  
Sent By lmarchan Date 2017-09-25 Time 15:31 Rev Time 0.00
Received By lmarchan Date 2017-08-21 Time 15:11 Sent To  
Notes
2017-08-22 15:11:16R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-03 Cont ID  
Sent By rmcdouga Date 2017-08-03 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2017-07-14 Time 13:42 Sent To  
Notes
2017-07-17 13:42:52R03

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-10-05 Cont ID  
Sent By rmcdouga Date 2017-10-05 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2017-10-05 Time 17:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-10-02 Cont ID  
Sent By rmcdouga Date 2017-10-02 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2017-09-29 Time 18:20 Sent To E
Notes
2017-09-29 19:03:49PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORMS CONTAIN ERRORS AND DO NOT
 ACCURATELY REFLECT THE DATA THAT IS SHOWN ON THE PLANS.
 FBC 107.2.1
 - THERE IS ONLY ONE BEDROOM AND IT IS LOCATED ON THE
 SECOND FLOOR. THE FORM HAS THREE (3) BEDROOMS. ONE ONE
 THE FIRST FLOOR AND TWO ON THE SECOND FLOOR. THE FIRST
 FLOOR IS A GARAGE AND STORAGE AND THE SECOND FLOOR HAS
 ONLY ONE (1) BEDROOM.
 - THE PLANS DO NOT SHOW A WHOLE HOUSE FAN. HOWEVER, THE
 CREDIT FOR ONE IS LISTED ON THE FORMS. THE PLANS STATE
 THAT THIS STRUCTURE HAS AN UNVENTED ATTIC, SUBMIT
 DOCUMENTS THAT SHOW HOW THE REQUIREMENTS OF FBC ENERGY
 CONSERVATION R405.7.5 WILL BE MET.
 - THE WINDOW OPENINGS AND ORIENTATIONS LISTED ON THE
 FORMS DO MATCH THE ONES THAT ARE SHOWN ON THE PLANS.
 TWELVE (12) WINDOW OPENINGS ARE LISTED ON THE FORMS AND
 SIXTEEN (16) ARE SHOWN ON THE PLANS. PLEASE CORRECT FBC
 107.2.1 AND FBC ENERGY CONSERVATION R 101.5.1.1.1
 - THE OWNER / AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM 402. FBC ENERGY CONSERVATION R103.1.1.2
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-30 Cont ID  
Sent By rmcdouga Date 2017-08-30 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2017-08-29 Time 18:04 Sent To  
Notes
2017-08-29 18:46:24PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORMS CONTAIN ERRORS AND DO NOT
 ACCURATELY REFLECT THE DATA THAT IS SHOWN ON THE PLANS.
 FBC 107.2.1
 - THERE IS ONLY ONE BEDROOM AND IT IS LOCATED ON THE
 SECONG FLOOR.
 - THE PLANS DO NOT SHOW THAT THERE IS AN UNVENTED
 ATTIC.
 - THE R-VALUE OF THE ATTIC INSULATION IS LISTED AS 0
 FOR THE BLOWN INSULATION.
 - THE MINIMUM R-VALUE FOR DUCTS IS R-6 PER FBC ENERGY
 CONSERVATION R405.2
 -THE COMBINED KBTU OF THE HEATING SYSTEMS IS 36.0 PER
 THE MECHANICAL PLANS.
 - THE PLANS DO NOT SHOW CEILING FANS OR A WHOLE HOUSE
 FAN. HOWEVER, THESE CREDITS ARE LISTED ON THE FORMS.
 - THE FLOOR/CEILING ASSEMBLY AND THE INTERIOR WALLS
 THAT SEPARATE THE GARAGE AND STORAGE FROM THE DWELLING
 UNIT SHOULD BE THERMALLY INSULATED.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-03 Cont ID  
Sent By rmcdouga Date 2017-08-03 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2017-08-03 Time 11:29 Sent To  
Notes
2017-08-03 11:24:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THAT THE SECOND FLOOR DWELLING IS IN COMPLIANCE
 WITH FBC-R303.9 REQUIRED HEATING. WHEN THE WINTER
 DESIGN TEMPERATURE IN TABLE R301.2(1) IS BELOW 60
 DEGREES F , EVERY DWELLING UNIT SHALL BE PROVIDED WITH
 HEATING FACILITIES CAPABLE OF MAINTAINING A MINIMUM
 ROOM TEMPERATURE OF 68 DEGREES F AT A POINT 3 FEET (914
 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR
 WALLS IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE.
 THE INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 3) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 4) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
 PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS
 THAT CORRESPONDS WITH THE EQUIPMENT SIZING
 CALCULATIONS. FBC 107.3.5.3
  
 5) SHOW COMPLIANCE WITH FBC-R - M 1602.4 WHICH REQUIRES
 BALANCED AIR RETURN AT THE BEDROOMS.
  
 6) PROVIDE A WIND LOAD TIE DOWN/ANCHORING DETAIL FOR
 THE A/C CONDENSING UNIT . FBC-R 301.1
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2017-07-14 Cont ID  
Sent By shill Date 2017-07-14 Time 10:11 Rev Time 0.00
Received By shill Date 2017-07-14 Time 10:11 Sent To  
Notes
2017-07-14 10:12:01THIS APPLICATION IS FOR THE ACCESSORY STRUCTURE IN THE
 WEST PORTION OF THE PROPERTY. BASED ON THE CURRENT MAP,
 THE ACCESSORY STRUCTURE IS NOT IN THE SFHA (SCALED 400'
 FROM FLAGLER DRIVE). BASED ON THE BEST CURRENT DATA
 (NEW FIRMS), THIS IS OUT OF THE SFHA. A FIRMETTE WAS
 CREATED AND PUT WITH THE FILE. THE FLOOD ZONE
 ASSIGNMENT FOR THE DEMO PERMIT (17070537) AND
 RENOVATION PERMIT (17070538) WAS CHANGED FROM AE TO B.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-20 Cont ID  
Sent By thunt Date 2017-09-20 Time 15:43 Rev Time 0.00
Received By thunt Date 2017-09-20 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-27 Cont ID  
Sent By gjohnson Date 2017-07-27 Time 13:34 Rev Time 0.00
Received By gjohnson Date 2017-07-27 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-09-29 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-27 Time 15:53 Sent To  
Notes
2017-09-29 13:34:16PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-09-15 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-15 Time 14:30 Sent To  
Notes
2017-09-15 14:30:07PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-07-25 Time   Rev Time 0.00
Received By pgreilic Date 2017-07-24 Time 11:18 Sent To  
Notes
2017-07-25 11:59:29PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]