Plan Review Details - Permit 17070528
Plan Review Stops For Permit 17070528 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2017-07-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-07-18 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-07-18 |
Time |
10:53 |
Sent To |
|
|
Notes |
2017-07-18 10:54:12 | APPROVED WITH EXCEPTION - NEED ELECTRICAL PERMIT | | APPLICATION. FBC 105.1 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-08-08 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-08-02 |
Time |
10:21 |
Sent To |
|
|
Notes |
2017-08-03 10:21:49 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-07-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-07-18 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-07-13 |
Time |
14:02 |
Sent To |
|
|
Notes |
2017-07-17 14:02:38 | ROUTED TO MECHANICAL INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2017-08-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-08-18 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-08-18 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-08-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-08-08 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-08-08 |
Time |
14:42 |
Sent To |
|
|
Notes |
2017-08-08 14:53:17 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17070528 | | 8/8/17 | | | | 1) AS PREVIOUSLY REQUESTED IN THE FIRST REVIEW, PROVIDE | | VERIFICATION THAT THE THE NEW COOLING TOWERS ARE LISTED | | IN ACCORDANCE WITH UL 1995. | | | | 2) CLARIFY IF THE BOILER REPLACEMENT NOTED ON SHEET M1 | | IS TO BE INCLUDED IN THIS PERMIT, AND IF SO, PROVIDE | | DRAWINGS AND DETAILS, AND INCREASE THE VALUE OF THE | | PERMIT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-07-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-07-18 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-07-18 |
Time |
09:19 |
Sent To |
|
|
Notes |
2017-07-18 10:08:57 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17070528 | | 7/18/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE VERIFICATION THAT THE COOLING TOWERS ARE | | LISTED IN ACCORDANCE WITH UL 1995- SEE SECTION 908.1. | | | | 2) SHEET M1: PROVIDE THE TONNAGE OF THE TOWERS IN THE | | EQUIPMENT SCHEDULE. | | | | 3) PER MANUFACTURER'S SPECIFICATIONS: INDICATE THE | | REQUIRED CLEARANCES AROUND THE TOWERS FOR SERVICE, AND | | THE REQUIRED CLEARANCE FOR THE AIR INTAKE TO THE | | ADJACENT UPPER ROOF WALL. | | | | 4) PROVIDE A PERMANENT LADDER AND PLATFORM TO ACESS THE | | PLENUM AND THE MOTOR- SECTION 306.5 | | | | 5) THE $135,000 VALUE ON THE PERMIT APPLICATION APPEARS | | TOO LOW FOR THE SCOPE OF WORK. PLEASE SEE SECTION 109.3 | | WPB AMENDMENTS TO THE FBC AND PROVIDE A CONTRACT OR BID | | DOCUMENT TO VERIFY COSTS THAT INCLUDE: A) LABOR, | | MATERIALS AND EQUIPMENT FOR MECHANICAL, ELECTRICAL, AND | | PLUMBING WORK. B) DEMOLITION, SITE WORK AND CRANE, AND | | DESIGN FEES. | | | | 6) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH | | SECTIONS C408.2 & C408.2.1 FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
|