Plan Review Details - Permit 17070528
Plan Review Stops For Permit 17070528
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-18 Cont ID  
Sent By jpearson Date 2017-07-18 Time 10:53 Rev Time 0.00
Received By jpearson Date 2017-07-18 Time 10:53 Sent To  
Notes
2017-07-18 10:54:12APPROVED WITH EXCEPTION - NEED ELECTRICAL PERMIT
 APPLICATION. FBC 105.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-02 Time 10:21 Sent To  
Notes
2017-08-03 10:21:49RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-18 Cont ID  
Sent By jpearson Date 2017-07-18 Time 10:54 Rev Time 0.00
Received By jpearson Date 2017-07-13 Time 14:02 Sent To  
Notes
2017-07-17 14:02:38ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-18 Cont ID  
Sent By ccole Date 2017-08-18 Time 14:04 Rev Time 0.00
Received By ccole Date 2017-08-18 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-08 Cont ID  
Sent By ccole Date 2017-08-08 Time 14:42 Rev Time 0.00
Received By ccole Date 2017-08-08 Time 14:42 Sent To  
Notes
2017-08-08 14:53:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070528
 8/8/17
  
 1) AS PREVIOUSLY REQUESTED IN THE FIRST REVIEW, PROVIDE
 VERIFICATION THAT THE THE NEW COOLING TOWERS ARE LISTED
 IN ACCORDANCE WITH UL 1995.
  
 2) CLARIFY IF THE BOILER REPLACEMENT NOTED ON SHEET M1
 IS TO BE INCLUDED IN THIS PERMIT, AND IF SO, PROVIDE
 DRAWINGS AND DETAILS, AND INCREASE THE VALUE OF THE
 PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By ccole Date 2017-07-18 Time 09:53 Rev Time 0.00
Received By ccole Date 2017-07-18 Time 09:19 Sent To  
Notes
2017-07-18 10:08:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070528
 7/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE VERIFICATION THAT THE COOLING TOWERS ARE
 LISTED IN ACCORDANCE WITH UL 1995- SEE SECTION 908.1.
  
 2) SHEET M1: PROVIDE THE TONNAGE OF THE TOWERS IN THE
 EQUIPMENT SCHEDULE.
  
 3) PER MANUFACTURER'S SPECIFICATIONS: INDICATE THE
 REQUIRED CLEARANCES AROUND THE TOWERS FOR SERVICE, AND
 THE REQUIRED CLEARANCE FOR THE AIR INTAKE TO THE
 ADJACENT UPPER ROOF WALL.
  
 4) PROVIDE A PERMANENT LADDER AND PLATFORM TO ACESS THE
 PLENUM AND THE MOTOR- SECTION 306.5
  
 5) THE $135,000 VALUE ON THE PERMIT APPLICATION APPEARS
 TOO LOW FOR THE SCOPE OF WORK. PLEASE SEE SECTION 109.3
 WPB AMENDMENTS TO THE FBC AND PROVIDE A CONTRACT OR BID
 DOCUMENT TO VERIFY COSTS THAT INCLUDE: A) LABOR,
 MATERIALS AND EQUIPMENT FOR MECHANICAL, ELECTRICAL, AND
 PLUMBING WORK. B) DEMOLITION, SITE WORK AND CRANE, AND
 DESIGN FEES.
  
 6) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH
 SECTIONS C408.2 & C408.2.1 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  