Plan Review Details - Permit 17070496
Plan Review Stops For Permit 17070496
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-18 Cont ID  
Sent By rmcdouga Date 2017-09-18 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2017-09-18 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-05 Cont ID  
Sent By rmcdouga Date 2017-09-05 Time 18:06 Rev Time 0.00
Received By rmcdouga Date 2017-09-05 Time 18:06 Sent To  
Notes
2017-09-05 18:15:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERAL NOTE 2 ON THE GENERATOR PAD ENGINEERING
 REQUIRES THAT THE CALCULATIONS FOR POSITIVE AND
 NEGATIVE DESIGN PRESSURES FOR USE WITH THIS SYSTEM BE
 DETERMINED BY OTHERS ON A JOB SPECIFIC BASIS IN
 ACCORDANCE WITH THE GOVERING CODE. THIS SYSTEM IS
 LOCATED IN EXPOSURE C AND 170 MPH VULT WINDSPEED.
 SUBMIT THE REQUIRED DESIGN PRESSURES FOR THIS SYSTEM.
 FBC 301.2.1 NOTE THAT THE ALLOWABLE PRESSURE IS 39.20
 PSF FOR THE 22KW GENERATOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By rmcdouga Date 2017-07-25 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2017-07-25 Time 09:03 Sent To E
Notes
2017-07-25 09:11:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-09-18 Cont ID  
Sent By jleahy Date 2017-09-18 Time 13:57 Rev Time 0.00
Received By jleahy Date 2017-09-18 Time 13:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-28 Cont ID  
Sent By jleahy Date 2017-08-28 Time 16:15 Rev Time 0.00
Received By jleahy Date 2017-08-28 Time 16:15 Sent To G
Notes
2017-08-28 16:16:52FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER IS MISSING OLD ONE WAS VOIDED AND SHOWED TRANSFER
 SWITCH.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-26 Cont ID  
Sent By jleahy Date 2017-07-26 Time 15:50 Rev Time 0.00
Received By jleahy Date 2017-07-26 Time 15:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-08-29 Cont ID  
Sent By thunt Date 2017-08-29 Time 13:12 Rev Time 0.00
Received By thunt Date 2017-08-29 Time 13:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By tklarge Date 2017-07-21 Time 13:41 Rev Time 0.00
Received By tklarge Date 2017-07-21 Time 12:30 Sent To  
Notes
2017-07-21 13:41:481) SHOW THE DISTANCE FROM THE 2ND STAGE REGULATOR TO
 THE GENERATOR AND THE TYPE OF PIPING FROM THE REGULATOR
 TO THE GENERATOR. COMPLY WITH 2014 FBC-FUEL GAS OR NFPA
 58 FOR PIPE SIZE REQUIREMENTS. SUBMIT TWO COPIES OF THE
 SIZING TABLE USED FOR THIS SECTION OF PIPE.
 2) INDICATE THE PSI OF THE SYSTEM DOWNSTREAM OF THE 2ND
 STAGE REGULATOR AT THE GENERATOR.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 2ND
 STAGE REGULATOR. WPB AMEND. TO FBC SEC. 107.2.1, 2014
 FBC-FUEL GAS SEC.410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-05 Cont ID  
Sent By rmcdouga Date 2017-09-05 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2017-08-21 Time 10:19 Sent To  
Notes
2017-08-22 10:19:30RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-26 Cont ID  
Sent By jleahy Date 2017-07-26 Time 15:51 Rev Time 0.00
Received By jleahy Date 2017-07-13 Time 11:45 Sent To  
Notes
2017-07-17 11:45:30ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2017-09-18 Cont ID  
Sent By njwira Date 2017-09-18 Time 12:32 Rev Time 0.00
Received By njwira Date 2017-09-18 Time 12:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-08-24 Cont ID  
Sent By njwira Date 2017-08-24 Time 16:29 Rev Time 0.00
Received By njwira Date 2017-08-22 Time 16:07 Sent To E
Notes
2017-08-24 16:30:319/14/17- PASS WHEN BROUGHT UP
 8/24/17- FAILED
  
 SURVEY PROVIDED IN PREVIOUS APPLICATION IS VOID MUST
 PROVIDE A CURRENT SURVEY SHOWING THE LOCATION OF THE
 GENERATOR
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-19 Cont ID  
Sent By njwira Date 2017-07-19 Time 10:11 Rev Time 0.00
Received By njwira Date 2017-07-17 Time 16:02 Sent To  
Notes
***NONE***