Plan Review Details - Permit 17070265
Plan Review Stops For Permit 17070265
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-18 Cont ID  
Sent By jwitmer Date 2017-08-18 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2017-08-18 Time 11:55 Sent To  
Notes
2017-08-18 12:21:012014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070265
 ADD: 501 S. FLAGLER DR. SUITE : 302
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-308-1590
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. AUG. 18/ 2017
 ACTION: BUILDING PROVISO
  
 1) PROVISO: 2014 ACCESSIBILITY CODE SECTION 404.2.4
 MANEUVERING CLEARANCES, MINIMUM 18 INCHES
 LATCH SIDE OF DOOR. TABLE 404.2.4.1 AND FIGURE
 404.2.4.1(A).
  
 2) PROVISO: POCKET DOORS, DOORS ARE IDENTIFIED AS 313B
 & 314B.
 2014 ACCESSIBILITY CODE 404.2.7 DOOR HARDWARE. WHERE
 SLIDING DOORS ARE IN THE FULLY OPEN POSITION, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS.
 2014 ACCESSIBILITY CODE 309.4 OPERATION. OPERABLE PARTS
 SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE
 TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE
 FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5
 POUNDS MAXIMUM.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-04 Cont ID  
Sent By jwitmer Date 2017-08-04 Time 08:52 Rev Time 0.00
Received By jwitmer Date 2017-08-04 Time 07:45 Sent To  
Notes
2017-08-04 08:52:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070265
 ADD: 501 S. FLAGLER DR. SUITE : 302
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-308-1590
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. AUG. 04/ 2017
 ACTION: BUILDING PROVISO
  
 1) PROVISO: 2014 ACCESSIBILITY CODE SECTION 404.2.4
 MANEUVERING CLEARANCES, MINIMUM 18 INCHES
 LATCH SIDE OF DOOR. TABLE 404.2.4.1 AND FIGURE
 404.2.4.1(A).
  
 2) PROVISO: POCKET DOORS, DOORS ARE IDENTIFIED AS 313B
 & 314B.
 2014 ACCESSIBILITY CODE 404.2.7 DOOR HARDWARE. WHERE
 SLIDING DOORS ARE IN THE FULLY OPEN POSITION, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS.
 2014 ACCESSIBILITY CODE 309.4 OPERATION. OPERABLE PARTS
 SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE
 TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE
 FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5
 POUNDS MAXIMUM.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2017-07-20 Time 11:47 Sent To  
Notes
2017-07-20 14:36:292014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070265
 ADD: 501 S. FLAGLER DR. SUITE : 302
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-308-1590
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 20/ 2017
 ACTION: DENIED
  
 1) THE SHEET 004_A.1.1.1. INDICATES A NEW ALCOVE AND
 ENTRY DOOR, THE DOOR IS IDENTIFIED AS 315. THE DOOR
 SCHEDULE FOUND ON 007_A2.0.1 INDICATES THIS DOOR IS A
 3-0X 8-0 FOOT DOOR. THE INTERIOR SIDE OF THE ALCOVE IS
 DIMENSIONED AS 4 FOOT 6 INCHES WIDE. THE PLANS WHEN
 SCALED SHOW THE 18 INCHES ON THE LATCH SIDE OF THE DOOR
 AS REQUIRED BY THE ACCESSIBILITY CODE. WHEN THE DOOR IS
 MEASURES FOR WIDTH, IT ONLY MEASURES AS A 2 FOOT 71/2
 INCH DOOR. PLEASE NOTE FOR DOORS IN A MEANS OF EGRESS
 THE DOOR WIDTH WOULD NEED TO BE A 36 INCH WIDE DOOR.
  
 PLEASE REFER TO THE 2014 FBC-B SECTION 1008.1.1 SIZE OF
 DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 ONCE THE DOOR MEETS THE EGRESS REQUIREMENTS WITH A 4
 FOOT 6 INCH ALCOVE WIDTH YOU WILL NO LONGER HAVE THE
 REQUIRED 18 INCHES MANEUVERING CLEARANCES ON THE LATCH
 SIDE OF THE DOOR. SEE 2014 ACCESSIBILITY CODE SECTION
 404.2.4 MANEUVERING CLEARANCES, TABLE 404.2.4.1 AND
 FIGURE 404.2.4.1(A). PLEASE UPDATE THE PLANS.
  
 2) THE SHEET 004_A.1.1.1. ALSO SHOWS (2) POCKET DOORS,
 DOORS ARE IDENTIFIED AS 313B & 314B. THE DOOR SCHEDULE
 FOUND ON 007_A2.0.1 INDICATES THESE DOORS HARDWARE AS
 GROUP 3, NOTES INDICATE POCKET HARDWARE? PLEASE SHOW
 COMPLIANCE WITH :
  
 2014 ACCESSIBILITY CODE 404.2.7 DOOR AND GATE HARDWARE.
 WHERE SLIDING DOORS ARE IN THE FULLY OPEN POSITION,
 OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM
 BOTH SIDES. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER
 OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH
 309.4. OPERABLE PARTS.
  
 2014 ACCESSIBILITY CODE 309.4 OPERATION. OPERABLE PARTS
 SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE
 TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE
 FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5
 POUNDS (22.2 N) MAXIMUM.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-17 Cont ID  
Sent By jpearson Date 2017-08-17 Time 07:34 Rev Time 0.00
Received By jpearson Date 2017-08-17 Time 07:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-01 Cont ID  
Sent By jpearson Date 2017-08-01 Time 11:30 Rev Time 0.00
Received By jpearson Date 2017-08-01 Time 11:30 Sent To  
Notes
2017-08-01 11:30:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEW SHEETS SUBMITTED FOR ELECTRICAL, E0-1 AND E2-1,
 NOT SIGNED AND SEALED. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC 107.2.1; FS 471
 2. RECEPTACLE CONTROL NOT TO CODE. OFFICES 314 AND 315
 DO NOT SHOW ANY CONTROL. BREAK AREA DOES NOT MEET
 AMOUNT OF CONTROL REQUIRED. BOTH AREAS REQUIRE A
 MINIMUM OF 50% OF THE OUTLETS CONTROLLED PER ASHRAE
 90.1:8.4.2. ADDITIONALLY, PLAN CURRENTLY SHOWS 8
 CIRCUITS BEING CONTROLLED BY A 6 POLE CONTACTOR, WHICH
 WILL OBVIOUSLY NOT WORK. PROVIDE CORRECTIONS. FBC
 C405.7.1, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jpearson Date 2017-07-19 Time 12:09 Rev Time 0.00
Received By jpearson Date 2017-07-19 Time 12:09 Sent To  
Notes
2017-07-19 12:14:37CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE AUTOMATIC LIGHTING CONTROLS FOR ALL FIXTURES
 PER CODE. IT APPEARS THAT THE HALL IS MISSING CONTROL,
 AND THE CONTROL FOR THE MAIN WORK AREA IS NOT CLEAR.
 CLARIFY AND/OR CORRECT. FBC 107.2.1, C405.2.2
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-01 Cont ID  
Sent By wjolin Date 2017-08-01 Time 13:18 Rev Time 0.00
Received By wjolin Date 2017-08-01 Time 13:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-14 Cont ID  
Sent By wjolin Date 2017-07-14 Time 08:32 Rev Time 0.00
Received By wjolin Date 2017-07-14 Time 08:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-18 Cont ID  
Sent By jwitmer Date 2017-08-18 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-09 Time   Rev Time 0.00
Received By cpuell Date 2017-07-31 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-12 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 10:14 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 10:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 17:11 Rev Time 0.00
Received By ccole Date 2017-07-21 Time 17:11 Sent To  
Notes
2017-07-21 17:13:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070265
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M2.1: THE 16X12 MAIN TRUNK IS UNDERSIZED FOR 1600
 CFMS AT A TYPICAL LOW PRESSURE FRICTION LOSS OF 0.1
 W.G.
  
 2) M2.1: PROVIDE THE FLEX DUCT SIZES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 09:41 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 09:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2017-08-18 Cont ID  
Sent By jwitmer Date 2017-08-18 Time 12:27 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 10:16 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
2017-08-09 10:17:16SHEET M2.1 NOT DIGITALLY SIGNED AND SEALED- CCOLE-
 8/9/17
2017-08-04 09:03:44BUILDING SIGNATURES FOR ARCHITECTURAL SHEETS, MISSING
 ELECTRONIC SIGNATURES:
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 AD1.0
 A.1.1.1
 A.1.1.2.
 A1.1.3
 A2.0.1.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 17:18 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
2017-07-21 17:14:21MECHANICAL AND ELECTRICAL SIGNATURES VERIFIED- CCOLE-
 7/21/17
2017-07-20 14:37:41ARCHITECTURAL SHEETS SIGNATURES GOOD. JW 7/20/2017
2017-07-18 09:43:377/18/17 DIG SIG ON PLUMB SHTS. OK/GPJ