 |
Plan Review Details - Permit 17070253
Plan Review Stops For Permit 17070253 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2018-02-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-02-12 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-02-12 |
Time |
09:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2018-01-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-01-29 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-01-29 |
Time |
07:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-01-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-01-11 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-01-11 |
Time |
07:15 |
Sent To |
|
|
Notes |
2018-01-11 09:21:37 | BUILD. INFO. | | | | TYPE: III-B | | OCC.: I-B | | SPRINKLERED | | 11,888 SQ. FT. | | 75 OCCUPANTS / 26 BED UNIT | | 29 RESTROOM/BATHROOMS | | FLOOD ZONE A9 BFE 13.0 FT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2017-10-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-10-24 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-10-24 |
Time |
11:29 |
Sent To |
|
|
Notes |
2017-10-24 15:16:07 | 2014 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 17070253 | | ADD: 1803 S. AUSTRALIAN AVE. | | CONT: DRY ART CONSTRUCTION | | TEL: 561-436-3703 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: TUES. OCT. 24TH/ 2017 | | ACTION: DENIED | | | | 1)2ND REQUEST. | | 1A) PLEASE NOTE THE CITY OF WEST PALM BEACH OFFICIALLY | | ADOPTED THE NEW FLOOD MAPS, THE NAVD 88 STANDARD AND AN | | ADDITION 1 FOOT FREEBOARD ALL ON OCT. 5/ 2017. SINCE | | THE PROJECT CAME IN ON 07/07/2017 (PERMIT APPLICATION | | DATE) THIS PROJECT STAYS WITH THE NGVD 29 STANDARD. THE | | ELEVATION CERTIFICATE NEEDS TO REFLECT ALL VERTICAL | | HEIGHTS IN NGVD. | | | | 1B) THE SUBMITTED ELEVATION CERTIFICATE LINE C1 HAS THE | | BOX CHECKED THIS CERTIFICATE IS BUILDING UNDER | | CONSTRUCTION. PLEASE CORRECT TO CONSTRUCTION DRAWINGS. | | | | 1C) CORRECT ON ALL SHEETS (A-5,A-6, & A-7 AND THE SITE | | PLAN A-00) THE ELEVATION TO THE NGVD 29 STANDARD. | | | | | | 1ST ROUND OF COMMENTS. THE SURVEY SUBMITTED BY PM | | SURVEYING LIST THIS PROPERTY IN A B FLOOD ZONE. USING | | THE ADOPTED FIRM MAPS DATED MARCH 1, 1979 COMMUNITY | | PANEL NUMBER 120229 0020 B THIS SITE IS LOCATED IN AN | | A-9 FLOOD ZONE THE FREEBOARD AT THAT TIME WOULD HAVE | | BEEN AN ADDITIONAL 6 INCHES OR FINISH FLOOR ABOVE 13 | | FOOT 6 INCHES. THIS BUILDING IS CONSIDERED A POST FIRM | | BUILDING WITH THE PERMIT APPLICATION FOR THIS BUILDING | | DATED 10/19/79. THE BUILDING AT THAT TIME WAS ALSO | | ADDRESSED OFF OF (OLD) OKEECHOBEE RD., 1501 OLD | | OKEECHOBEE RD. THIS BUILDING IS TO BE CONSIDERED | | SUBSTANTIAL IMPROVEMENT AS WELL SINCE THE PROPERTY | | APPRAISERS OFFICE LIST THE IMPROVED VALUE OF THIS | | BUILDING AT $687,288.00 DOLLARS IN VALUE AND THE | | RENOVATION AND ADDITION ARE VALUED AT OVER 50% OF THE | | APPRAISED (PALM BEACH COUNTY PROPERTY APPRAISERS | | OFFICE) BUILDING VALUE. PLEASE PROVIDE A NEW SURVEY | | SHOWING THE PROPERTY IN AN A9 FLOOD ZONE AND PLEASE | | PROVIDE A FLOOD ZONE CERTIFICATE. PLEASE MAKE REFERENCE | | TO ELEVATIONS IN NGVD 29, THE CITY IS STILL USING THIS | | REFERENCE UNTIL AUGUST 28/ 2017 WHEN THE NEW MAPS WILL | | BE ADOPTED AND A 2 FOOT FREEBOARD REQUIREMENT. | | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION | | IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016. | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | REQUIRED: | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 | | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS, | | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. | | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 | | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON | | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND | | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION | | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL. | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. | | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS | | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS | | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR | | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL | | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR | | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING | | JURISDICTION. | | FEMA NEW FORM AVAILABLE JUNE 13/2016. | | OMB NO. 1660-0008 | | EXPIRATION DATE: NOV. 30/2018 | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | 2-6B) COMPLIED. | | | | 6C) PLEASE PROVIDE CALCULATIONS FOR COMPLYING WITH | | FBC-B 407.5.1 REFUGE AREA. | | | | 7A) COMPLIED. | | | | 7B) 2ND REQUEST. ACCESSIBILITY CODE 805.2 TURNING | | SPACE. SLEEPING ROOM. NO FURNITURE LAYOUT IN THE | | ACCESSIBLE SLEEPING ROOMS. | | | | 7C)2ND REQUEST. NO FURNITURE IN THE SLEEPING ROOMS. | | 805.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING | | WITH 305 SHALL BE PROVIDED ON EACH SIDE OF THE BED. A | | CLEAR FLOOR SPACE SHALL BE POSITIONED FOR A PARALLEL | | APPROACH TO THE SIDE OF THE BED. | | | | 7D) COMPLIED. 805.4. TOILET & BATHING ROOMS TOILET AND | | BATHING ROOMS THAT ARE PART OF THE PATIENT OR RESIDENT | | SLEEPING ROOM SHALL COMPLY WITH 603. WHERE PROVIDED, NO | | FEWER THAN ONE WATER CLOSET, ONE LAVATORY, AND ONE | | BATHTUB OR SHOWER SHALL COMPLY WITH THE APPLICABLE | | REQUIREMENTS OF 603 THROUGH610. | | | | 7E)2ND REQUEST. THE PLANS DO NOT PROVIDE COMPLIANCE FOR | | ACCESSIBLE SIGNAGE AS PER REQUIRED PER SECTION 216.1 OF | | THE ACCESSIBILITY CODE. SIGNS SHALL BE PROVIDED IN | | ACCORDANCE WITH ALL OF SECTION 216 AND SHALL COMPLY | | WITH 703. | | | | 8-12) COMPLIED. | | | | 13) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | ON SUBSEQUENT REVIEWS. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-07-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-07-25 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-07-24 |
Time |
11:57 |
Sent To |
|
|
Notes |
2017-07-25 17:20:29 | 2014 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 17070253 | | ADD: 1803 S. AUSTRALIAN AVE. | | CONT: DRY ART CONSTRUCTION | | TEL: 561-436-3703 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: MON. JULY 24TH/ 2017 | | ACTION: DENIED | | | | 1) THE SURVEY SUBMITTED BY PM SURVEYING LIST THIS | | PROPERTY IN A B FLOOD ZONE. USING THE ADOPTED FIRM MAPS | | DATED MARCH 1, 1979 COMMUNITY PANEL NUMBER 120229 0020 | | B THIS SITE IS LOCATED IN AN A-9 FLOOD ZONE THE | | FREEBOARD AT THAT TIME WOULD HAVE BEEN AN ADDITIONAL 6 | | INCHES OR FINISH FLOOR ABOVE 13 FOOT 6 INCHES. THIS | | BUILDING IS CONSIDERED A POST FIRM BUILDING WITH THE | | PERMIT APPLICATION FOR THIS BUILDING DATED 10/19/79. | | THE BUILDING AT THAT TIME WAS ALSO ADDRESSED OFF OF | | (OLD) OKEECHOBEE RD., 1501 OLD OKEECHOBEE RD. THIS | | BUILDING IS TO BE CONSIDERED SUBSTANTIAL IMPROVEMENT AS | | WELL SINCE THE PROPERTY APPRAISERS OFFICE LIST THE | | IMPROVED VALUE OF THIS BUILDING AT $687,288.00 DOLLARS | | IN VALUE AND THE RENOVATION AND ADDITION ARE VALUED AT | | OVER 50% OF THE APPRAISED (PALM BEACH COUNTY PROPERTY | | APPRAISERS OFFICE) BUILDING VALUE. PLEASE PROVIDE A NEW | | SURVEY SHOWING THE PROPERTY IN AN A9 FLOOD ZONE AND | | PLEASE PROVIDE A FLOOD ZONE CERTIFICATE. PLEASE MAKE | | REFERENCE TO ELEVATIONS IN NGVD 29, THE CITY IS STILL | | USING THIS REFERENCE UNTIL AUGUST 28/ 2017 WHEN THE NEW | | MAPS WILL BE ADOPTED AND A 2 FOOT FREEBOARD | | REQUIREMENT. | | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS | | REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION | | IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016. | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES | | REQUIRED: | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 | | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL | | BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS, | | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. | | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND | | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. | | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 | | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON | | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND | | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION | | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL. | | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. | | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS | | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS | | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR | | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL | | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR | | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING | | JURISDICTION. | | FEMA NEW FORM AVAILABLE JUNE 13/2016. | | OMB NO. 1660-0008 | | EXPIRATION DATE: NOV. 30/2018 | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | 2) DISCREPANCY IN OCCUPANT LOADS. THE COVERSHEET A-00 | | LIST THE OCCUPANT LOAD FOR THE I-2 OCCUPANCY 10,373 SQ. | | FT./ 240= 44 OCCUPANTS WHEREAS THE LIFE SAFETY SHEET | | LIST THE TOTAL AMOUNT OF OCCUPANTS AT 75 OCCUPANTS. THE | | LIFE SAFETY SHEET HAS THE CORRECT OCCUPANT LOAD AND | | CALCULATIONS. PLEASE UPDATE THE PLANS SEE 2014 FBC-B | | TABLE 1004.1.2 | | | | 3) WITH THE OCCUPANT LOAD OF 50 OR MORE IN I-2 | | OCCUPANCY THE RISK CATEGORY OF THE BUILDING IS | | INCREASED TO A RISK CATEGORY III AND WIND SPEED TO 180 | | MPH VULT. GROUP I-2 OCCUPANCIES WITH AN OCCUPANT LOAD | | OF 50 OR MORE RESIDENT CARE RECIPIENTS BUT NOT HAVING | | SURGERY OR EMERGENCY TREATMENT FACILITIES, IF THE | | FACILITY DOES HAVE SURGERY OR EMERGENCY TREATMENT | | FACILITIES THEN THE STRUCTURES RISK CATEGORY BECOMES AN | | IV. | | | | 4A) THE OTHER ISSUE THE FRONT COVER SHEET A00 LIST THIS | | STRUCTURE AS A B EXPOSURE. TO THE NORTHEAST THERE IS A | | C SURFACE ROUGHNESS AS WELL AS TO THE SOUTH AND | | SOUTHEAST. SEE THE 2014 FBC-B EXPOSURE CATEGORY | | 1609.4.2 SURFACE ROUGHNESS. THIS SURFACE ROUGHNESS | | SHALL APPLY TO ANY BUILDING LOCATED WITHIN SURFACE | | ROUGHNESS B TYPE TERRAIN WHERE THE BUILDING IS WITHIN | | 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF | | SURFACE ROUGHNESS C OR D TYPE TERRAIN THAT EXTENDS MORE | | THAN 600 FEET IN THE UPWIND DIRECTION AND WIDTH GREATER | | THAN 150 FEET. | | | | 4B) THE ADJUSTMENT FACTORS WILL COME INTO PLAY WITH THE | | ASSOCIATED PRESSURES FOR A C EXPOSURE, SEE TABLE | | 1609.7(2) ADJUSTMENT FACTORS FOR BUILDING HEIGHT AND | | EXPOSURE. | | | | 5) SHEET A-00: | | 5A) THE SITE PLAN PROVIDED SHOWS 31 PARKING SPACES ONLY | | ONE OF THE SPACES IS AN ACCESSIBLE PARKING SPACE WITH | | ACCESS AISLE. THE 2014 FBC-ACCESSIBILITY CODE TABLE | | 208.2 PARKING SPACES REQUIRES 2 ACCESSIBLE PARKING | | SPACES AND ACCESS AISLES FOR 26 TO 50 PARKING SPACES. | | | | 5B) THE SITE PLAN ALSO SHOWS THE PARKING SPACES 18 AND | | 19 TO BE UNDER THE PORTE COCHERE BUT NOT THE ACCESSIBLE | | PARKING STALL. THE PLAN DOES NOT PROVIDE EQUIVALENT | | FACILITATION SECTION 103 OF THE ACCESSIBILITY CODE. IF | | COVERED PARKING IS PROVIDED THEN AT LEAST ONE | | ACCESSIBLE SPACE IS REQUIRED TO BE ALSO UNDER THE PORT | | COCHERE OR AN EQUIVALENCY TO. | | | | 5C) WITH THE REQUIREMENT OF A NEW ACCESSIBLE PARKING | | SPACE PLEASE PROVIDE COMPLIANCE WITH THE 2014 | | FBC-ACCESSIBILITY CODE 502.4 GROUND SURFACES 502.4 | | FLOOR OR GROUND SURFACES. | | PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL | | COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME | | LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN | | LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES NOT STEEPER | | THAN 1:48 SHALL BE PERMITTED. | | | | 5D)(1) WITH THE ADDITION OF THE PORTE COCHERE PLEASE | | ALSO NOTE THIS BEING A DROP OFF ZONE WILL NEED TO SHOW | | COMPLIANCE WITH THE ACCESS. CODE 209.2.1 PASSENGER | | LOADING ZONES. PASSENGER LOADING ZONES, EXCEPT THOSE | | REQUIRED TO COMPLY WITH 209.2.2 AND 209.2.3, SHALL | | PROVIDE AT LEAST ONE PASSENGER LOADING ZONE COMPLYING | | WITH 503 IN EVERY CONTINUOUS 100 LINEAR FEET (30 M) OF | | LOADING ZONE SPACE, OR FRACTION THEREOF. | | | | 5D)(2) 2014 FBC-ACCESS. CODE 209.3 MEDICAL CARE AND | | LONG-TERM CARE FACILITIES. AT LEAST ONE PASSENGER | | LOADING ZONE COMPLYING WITH 503 SHALL BE PROVIDED AT AN | | ACCESSIBLE ENTRANCE TO LICENSED MEDICAL CARE AND | | LICENSED LONG-TERM CARE FACILITIES WHERE THE PERIOD OF | | STAY EXCEEDS TWENTY-FOUR HOURS. | | | | 5E) THE SITE PLAN SHOWS (2) NEW SIDEWALKS THAT ENTER | | THE BUILDING. PLEASE PROVIDE THE SLOPES FOR THE | | SIDEWALKS DO THEY RISE FROM THE PARKING LOT TO THE NEW | | LANDING NEXT TO THE DOORS? PLEASE PROVIDE THE CHANGE IN | | GRADE AND CROSS SLOPES? ARE THESE SIDEWALKS TO BE | | CONSIDERED RAMPS BECAUSE OF THE ELEVATION CHANGE? | | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE | | TO DETERMINE CODE COMPLIANCE. | | | | 6) SHEET A-02; | | 6A) PLEASE NOTE THE WALL LEGEND SHOWS A CROSSED HATCHED | | WALL AS A 1 HOUR FIRE RATED ASSEMBLY, WHEREAS SHEETS | | A-03 & A-04 BOTH SHOW THESE WALLS TYPES AS NEW GYPSUM | | PARTITIONS. PLEASE PROVIDE HOW COMPLIANCE WITH FBC-B | | 407.5 SMOKE BARRIERS. SMOKE BARRIERS SHALL BE PROVIDED | | TO SUBDIVIDE EVERY STORY USED BY PERSONS RECEIVING | | CARE, TREATMENT OR SLEEPING AND TO DIVIDE OTHER STORIES | | WITH AN OCCUPANT LOAD OF 50 OR MORE PERSONS, INTO NO | | FEWER THAN TWO SMOKE COMPARTMENTS. 407.3 CORRIDOR WALL | | CONSTRUCTION. | | CORRIDOR WALLS SHALL BE CONSTRUCTED AS SMOKE PARTITIONS | | IN ACCORDANCE WITH SECTION 710. | | | | 6B) PLEASE PROVIDE HOW COMPLIANCE WITH FBC-B 407.4.3.5 | | CARE SUITES CONTAINING SLEEPING ROOM AREAS. | | SLEEPING ROOMS SHALL BE PERMITTED TO BE GROUPED INTO | | CARE SUITES WITH ONE INTERVENING ROOM IF ONE OF THE | | FOLLOWING CONDITIONS IS MET: | | 1. THE INTERVENING ROOM WITHIN THE CARE SUITE IS NOT | | USED AS AN EXIT ACCESS FOR MORE THAN EIGHT CARE | | RECIPIENT BEDS. | | 2. THE ARRANGEMENT OF THE CARE SUITE ALLOWS FOR DIRECT | | AND CONSTANT VISUAL SUPERVISION BY CARE | | PROVIDERS. | | | | 6C) PLEASE PROVIDE CALCULATIONS FOR COMPLYING WITH | | FBC-B 407.5.1 REFUGE AREA. | | | | 7A) NEITHER SHEET A-00.1 NOR A-01 SHOW COMPLIANCE WITH | | THE 2014 ACCESSIBILITY CODE 223.2 DETOXIFICATION | | FACILITIES SHALL HAVE AT LEAST 10 % BUT NOT FEWER THAN | | ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE | | MOBILITY FEATURES COMPLYING WITH 805. | | | | 7B) ACCESSIBILITY CODE 805.2 TURNING SPACE. | | | | 7C) 805.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE | | COMPLYING WITH 305 SHALL BE PROVIDED ON EACH SIDE OF | | THE BED. A CLEAR FLOOR SPACE SHALL BE POSITIONED FOR A | | PARALLEL APPROACH TO THE SIDE OF THE BED. | | | | 7D) 805.4. TOILET & BATHING ROOMS TOILET AND BATHING | | ROOMS THAT ARE PART OF THE PATIENT OR RESIDENT SLEEPING | | ROOM SHALL COMPLY WITH 603. WHERE PROVIDED, NO FEWER | | THAN ONE WATER CLOSET, ONE LAVATORY, AND ONE BATHTUB OR | | SHOWER SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF | | 603 THROUGH610. | | | | 7E) THE PLANS DO NOT PROVIDE COMPLIANCE FOR ACCESSIBLE | | SIGNAGE AS PER REQUIRED PER SECTION 216.1 OF THE | | ACCESSIBILITY CODE. SIGNS SHALL BE PROVIDED IN | | ACCORDANCE WITH ALL OF SECTION 216 AND SHALL COMPLY | | WITH 703. | | | | 8) SHEETS A-06, A-07, A-09 & S-01 ARE ALL IN VULT FOR | | 170 MPH EXPOSURE B. ALSO SEE COMMENT # 3. PLEASE UPDATE | | THE PLANS TO THE 180 VULT, EXPOSURE C AND THE N CONVERT | | PRESSURES INTO VASD SINCE THE PRODUCT APPROVALS ARE ALL | | IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. | | | | 9) / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | APPROVALS: | | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. NOA | | 16-0629.16 COMPLY WITH COMMENT #10 | | (B) WINDOWS & MULLIONS FL 14604.8 PROVIDE THE FLORIDA | | REPORT COVERSHEET!!!!!!!!!! (A) | | 14608.3 PROVIDE THE FLORIDA REPORT COVERSHEET!!!!!!!!!! | | (B) ONLY ONE REPORT SUBMITTED | | 14632.5 PROVIDE THE FLORIDA REPORT COVERSHEET!!!!!!!!!! | | SEE COMMENT # 10 COMPLY | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | LOUVERS, EFIS SYSTEMS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | VENTILATORS | | (G) PRE-ENGINEERED A/C STANDS | | | | 10) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | 11) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, | | THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE | | AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, | | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND | | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. | | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE | | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE | | SPECIFIC SITE. | | | | 12) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 13) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | ON SUBSEQUENT REVIEWS. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-01-04 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-01-04 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-01-04 |
Time |
08:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2017-11-02 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-11-02 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-11-01 |
Time |
10:28 |
Sent To |
I |
|
Notes |
2017-11-02 08:14:36 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: ALL ITEMS EXCEPT # 4 | | CORRECTED. SEE ADDITIONAL COMMENTS IN PARANTHESES. | | | | 1. CORRECTED. | | 2. CORRECTED. | | 3. CORRECTED. | | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 (RISER DIAGRAM DOES NOT MATCH THE | | INSTALLATION SHOWN ON THE PLAN. IS THERE AN 800 AMP | | MAIN THAT FEEDS DISCONNECTS FOR EACH PANEL, OR IS THERE | | AN MDP PANEL THAT HAS BREAKERS THAT FEED EACH PANEL. A | | "CT CAN" DOES NOT HAVE ANY OVERCURRENT PROTECTION | | INSIDE. CLARIFY AND/OR CORRECT DISCREPANCIES BETWEEN | | PLAN AND RISER DIAGRAM. PROVIDE CALCULATION THAT STATES | | THE AVAILABLE FAULT CURRENT FOR EACH PANEL. A NOTE IS | | NOT SUFFICIENT COMPLIANCE. NEC 110.9, 110.10, 215.5; | | FBC 107.2.1) | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | 8.CORRECTED. | | 9. CORRECTED. | | 10. CORRECTED. | | 11. CORRECTED. | | 12. CORRECTED. | | 13. CORRECTED. | | 15. CORRECTED. | | 16. CORRECTED. | | 17. CORRECTED. | | 18. CORRECTED. | | 19. CORRECTED. | | 20. CORRECTED. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-07-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-07-18 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-07-18 |
Time |
14:17 |
Sent To |
|
|
Notes |
2017-07-18 15:04:32 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. SHEET E-01, NOTE 1 REFERENCES THE 2013 NATIONAL | | ELECTRICAL CODE (NEC), WHICH DOESN'T EXIST. REVISE | | REFERENCE TO THE CURRENT CODE, WHICH IS THE 2011 NEC. | | FBC PREFACE. | | 2. SHEET E-01, NOTE 4 STATES THAT ALL RECEPTACLES SHALL | | BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION | | DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | CORRECTION. NEC 406.12 | | 3. SHEET E-09, PANEL SCHEDULES FOR PANELS A, B, C, D, | | AND K STATE THAT THEY ARE 120/240 SINGLE PHASE PANELS. | | THEY ARE FED FROM A 120/208 SYSTEM, SO THEY SHOULD BE | | LABELED AS 120/208 SINGLE PHASE PANELS. THE CORRECT | | VOLTAGE SHOULD BE USED IN ALL LOAD CALCULATIONS AND | | SHORT CIRCUIT CALCULATIONS FOR THE PANELS. PROVIDE | | CORRECTION FOR ALL PANEL SCHEDULES AND PANELS IN RISER | | DIAGRAM. FBC 107.2.1; NEC 220.5, 215.5 | | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | 5. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE | | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | AVAILABLE PER NEC 110.24. | | 6. RISER DIAGRAM SHOWS A GROUNDING ELECTRODE | | CONDUCTOR(GEC) TO 2 GROUND RODS. REVISE RISER DIAGRAM | | TO SHOW ALL GROUNDING ELECTRODES AVAILABLE AND THE GEC | | SIZE TO EACH. NEC 250.50, 250.66 | | 7. CIRCUIT NUMBERS FOR LIGHTING ARE NOT IDENTIFIED ON | | ANY OF THE LIGHTING PLANS. PROVIDE CORRECTION. FBC | | 107.2.1, NEC 215.5 | | 8. PROVIDE DETAIL OF EXTERIOR LIGHTING CONTROLS FOR | | PORTE COCHERE PER ENERGY CODE: "LIGHTING NOT DESIGNATED | | FOR DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY | | EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME | | SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS." FBC ENERGY | | C405.2.4 | | 9. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED | | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE | | OCCUPANCY SENSORS REQUIRED. FBC C405.2.2, 405.2.2.2 | | 10. WILL THERE BE ANY PATIENT CARE AREAS? PLEASE | | INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED PER NEC | | 517.13. | | 11. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED | | LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC | | MECHANICAL CODE M306.3.1 | | 12. PROVIDE KITCHEN EQUIPMENT SCHEDULE SHOWING CURRENT | | REQUIREMENTS FOR EACH APPLIANCE AND LISTING. NEC 110.3; | | FBC 107.2.1 | | 13. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL | | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN | | HOODS ETC. A NOTE WILL SUFFICE. | | 14. SHOW ON PLAN THE LOCATION OF PANEL K. FBC 107.2.1 | | 15. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN KITCHEN. | | NEC 210.8(B)(2) | | 16. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 | | AND ASHREA 90.1: 8.4.2 | | 17. SHEET E-02, THE CIRCUIT FOR THE WATER FEATURE IS | | NOT INDICATED. PROVIDE CORRECTION. FBC 107.2.1; NEC | | 215.5 | | 18. PROVIDE COMPLIANCE WITH VOLTAGE DROP REQUIREMENTS | | OF THE ENERGY CODE. FBC C405.7.3 | | 19. AE TYPE FIXTURES SHOWN ON LIGHTING PLANS ARE | | CONTROLLED BY A SWITCH. WHEN THE SWITCH IS TURNED OFF, | | THE LIGHTS WILL THEN USE THE BATTERY BACKUP TO POWER | | THE LIGHT, THUS DEFEATING THE PURPOSE OF AN EMERGENCY | | LIGHTING SYSTEM. PROVIDE CORRECTION. NEC 700.12(F) | | 20. PROVIDE DETAIL OF INTERIOR LIGHTING POWER | | ALLOWANCES, EITHER BY BUILDING TYPE OR BY AREA METHOD | | AS EXPLAINED IN THE FBC ENERGY CODE, WITH EXPLANATION | | OF THE TOTAL AMOUNT OF LIGHTING POWER PROPOSED TO MEET | | CODE REQUIREMENTS. FBC 405.5.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2018-02-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-02-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-02-09 |
Time |
13:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2018-01-25 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-01-25 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-01-24 |
Time |
16:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2018-01-19 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-01-19 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-12-27 |
Time |
10:23 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2017-10-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-10-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-10-27 |
Time |
11:55 |
Sent To |
|
|
Notes |
2017-10-27 11:56:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) A PREVIOUS COMMENT WAS NOT CORRECTLY ADDRESSED. | | | | PREVIOUS COMMENT: | | | | 3) SHEET A 00.1 - THERE IS A REFERENCE TO A FIRE | | SPRINKLER SYSTEM. THE FIRE SPRINKLER SYSTEM SHALL | | COMPLY WITH NFPA 13. | | | | PLEASE BE ADVISED: IF THERE IS NO EXISTING FIRE | | SPRINKLER SYSTEM, AND THE OCCUPANCY CLASSIFICATION | | REQUIRES A FIRE SRINKLER SYSTEM, THIS MASTER PERMIT | | SHALL CONTAIN THE FLORIDA STATUTES 61G REQUIREMENTS. | | | | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION | | ENGINEERING | | DOCUMENTS. | | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS | | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED | | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT | | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE | | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND | | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), | | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND | | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE | | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. | | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS | | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE | | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND | | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES | | AND STANDARDS, WHERE AVAILABLE. | | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A | | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION | | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENTS. | | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE | | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT | | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT | | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE | | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND | | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT | | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENTS. | | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED | | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE | | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL | | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. | | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION | | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT | | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED | | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER | | OF RECORD FOR THE FIRE PROTECTION SYSTEM. | | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, | | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY | | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN | | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, | | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. | | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER | | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION | | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED | | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE | | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR | | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE | | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION | | SYSTEM ENGINEERING DOCUMENTS. | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED | | 4-2-2000, 6-26-01 | | | | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION | | SYSTEMS. | | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT | | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, | | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE | | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE | | WATER MAINS AND DEDICATED FIRE PROTECTION WATER | | SOURCES. | | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION | | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL | | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN | | APPLICABLE: | | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER | | SUPPLY AS DEFINED BY 633.021(18) F.S. | | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE | | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING | | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND | | CONCLUSIONS. | | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | AREA. | | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, | | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR | | EACH SEPARATE 42 HAZARD OCCUPANCY. | | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS | | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR | | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE | | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM | | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY | | DEMANDING DESIGN AREA. | | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE | | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO | | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, | | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH | | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND | | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF | | SERVICE. | | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE | | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF | | WATER. | | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF | | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER | | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION | | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE | | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY | | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY | | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND | | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE | | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE | | MEASURES. | | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND | | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS | | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. | | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD | | AND INTERIOR FIRE PROTECTION COMPONENTS. | | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE | | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL | | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING | | APPROVAL AND DOCUMENTATION. | | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE | | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE | | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL | | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE | | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED | | 4-2-2000, 6-26-01, 7-12-05 | | | | THIS INFORMATION CAN BE SUBMITTED IN NARRATIVE OR | | DRAWING FORM, BUT SHALL CONTAIN THE REQUIRED | | INFOMRATION. | | | | PLEASE PROVIDE THE REQUIRED INFORMATION WITH THIS | | RESUBMITTAL. | | | | | | NEW COMMENT: | | | | CONTACTED MIQUEL ON 10/19 ABOUT MISSING 61G DOCUMENTS, | | HE STATED HE WOULD SUPPLY THE DOCUMENTS. HAVE NOT | | RECEIVED ANY INFORMATION AS OF THIS DATE 10/27. | | RESUBMITTAL FAILED. | | | | | | | | 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-07-13 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-07-13 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-07-12 |
Time |
16:38 |
Sent To |
|
|
Notes |
2017-07-13 09:49:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEETA 00 & 00.1 - THERE ARE NO CODE REFERENCES TO | | THE FLORIDA FIRE PREVENTION CODE. | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | APPLICABLE CODES OR STANDARDS. | | | | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN | | APPLICABLE NOTE. | | | | | | | | | | 2) SHEET A 00 & 00.1 - THERE IS NO INDICATION OF THE | | OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE | | PREVENTION CODE. | | | | PER NFPA 101, CHAPTER 6 | | | | 6.1 CLASSIFICATION OF OCCUPANCY. | | 6.1.1 GENERAL. | | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A | | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR | | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 | | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE | | SUBJECT TO THE RULING OF THE AUTHORITY HAVING | | JURISDICTION WHERE THERE IS A QUESTION OF PROPER | | CLASSIFICATION IN ANY INDIVIDUAL CASE. | | | | PLEASE PROVIDE A DETAILED REVIEW OF THE PURPOSE AND | | OPERATION OF THE PROPOSED USE OF THE BUILDING. | | | | BASED ON PROPOSED USE, PLEASE PROVIDE THE OCCUPANCY | | CLASSIFICATION PER NFPA 101, CHAPTER 6. | | | | | | | | 2) SHEET A 00.1 - THERE IS AN INDICATION OF A KITCHEN | | AND HOOD WITH REFERENCE TO NFPA 96, | | | | PLEASE PROVIDE A NOTE INDICATING THAT "THE KITCHEN HOOD | | & HOOD SUPPRESSION SYSTEMS SHALL BE SUBMITTED UNDER | | SEPARATE SHOP DRAWINGS." | | | | | | | | 3) SHEET A 00.1 - THERE IS A REFERENCE TO A FIRE | | SPRINKLER SYSTEM. THE FIRE SPRINKLER SYSTEM SHALL | | COMPLY WITH NFPA 13. | | | | PLEASE BE ADVISED: IF THERE IS NO EXISTING FIRE | | SPRINKLER SYSTEM, AND THE OCCUPANCY CLASSIFICATION | | REQUIRES A FIRE SRINKLER SYSTEM, THIS MASTER PERMIT | | SHALL CONTAIN THE FLORIDA STATUTES 61G REQUIREMENTS. | | | | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION | | ENGINEERING | | DOCUMENTS. | | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS | | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED | | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT | | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE | | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND | | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), | | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND | | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE | | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. | | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS | | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE | | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND | | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES | | AND STANDARDS, WHERE AVAILABLE. | | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A | | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION | | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENTS. | | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE | | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT | | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT | | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE | | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND | | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT | | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENTS. | | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED | | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE | | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL | | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. | | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION | | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM | | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT | | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED | | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER | | OF RECORD FOR THE FIRE PROTECTION SYSTEM. | | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, | | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY | | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN | | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, | | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. | | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER | | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION | | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED | | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE | | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR | | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE | | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION | | SYSTEM ENGINEERING DOCUMENTS. | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED | | 4-2-2000, 6-26-01 | | | | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION | | SYSTEMS. | | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT | | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, | | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE | | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE | | WATER MAINS AND DEDICATED FIRE PROTECTION WATER | | SOURCES. | | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION | | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL | | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN | | APPLICABLE: | | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER | | SUPPLY AS DEFINED BY 633.021(18) F.S. | | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE | | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING | | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND | | CONCLUSIONS. | | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | AREA. | | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, | | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR | | EACH SEPARATE 42 HAZARD OCCUPANCY. | | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS | | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR | | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE | | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM | | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY | | DEMANDING DESIGN AREA. | | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE | | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO | | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, | | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH | | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND | | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF | | SERVICE. | | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE | | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF | | WATER. | | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF | | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER | | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION | | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE | | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY | | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY | | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND | | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE | | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE | | MEASURES. | | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND | | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS | | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. | | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD | | AND INTERIOR FIRE PROTECTION COMPONENTS. | | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE | | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL | | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING | | APPROVAL AND DOCUMENTATION. | | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE | | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE | | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL | | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE | | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED | | 4-2-2000, 6-26-01, 7-12-05 | | | | THIS INFORMATION CAN BE SUBMITTED IN NARRATIVE OR | | DRAWING FORM, BUT SHALL CONTAIN THE REQUIRED | | INFOMRATION. | | | | PLEASE PROVIDE THE REQUIRED INFORMATION WITH THE | | RESUBMITTAL. | | | | | | | | | | 4) SHEET A 00.1 - THERE IS AN INDICATION OF USING "SAFE | | LOCKS". | | | | PLEASE PROVIDE A NARRATIVE NOTE TO DESCRIBE WHAT THIS | | TERM MEANS AND HOW WILL THE LOCKS BE USED. | | | | IF A DELAYED EGRESS OR CARD SWIPE SYSTEM BE USED, | | PLEASE PROVIDE AND NOTE AND ENSURE IT COMPLIES WITH | | NFPA 101, CHAPTER 7, MEANS OF EGRESS, UNDER SEPARATE | | SHOP DRAWINGS. | | | | | | | | 5) SHEET 00.1 - THERE IS AN INDICATION OF A FIRE ALARM | | SYSTEM. THE FIRE ALARM SYSTEM SHALL COMPLY WITH NFPA 72 | | AND SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS BY | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | | | 6) SHEET A 05 - THERE IS LIMITED DETAIL ON THE EXISTING | | ROOF SYSTEM, BUT THE NEW ROOF SYSTEM OVER THE PORTE | | COCHERE IS LIGHTWEIGHT. | | | | PLEASE PROVIDE DETAILED INFORMATION REGARDING THE | | EXISTING ROOF SYSTEM. | | | | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR | | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. | | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT | | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES | | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE | | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A | | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND | | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. | | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO | | THE LEFT OF THE MAIN ENTRY DOOR. | | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | MARKED WITH THE LETTER "R". | | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | SHALL BE MARKED WITH THE LETTER "F". | | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2017-08-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-08-10 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-08-10 |
Time |
09:54 |
Sent To |
|
|
Notes |
2017-08-10 09:57:19 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | GAS COMMENTS: | | | | GAS PLAN REVIEW | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | GAS PERMIT APPLICATION REQUIREMENTS | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | IN THE CITY OF WEST PALM BEACH: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | SEC. 402.4.1. | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | SEC. 502 THRU 505. | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | PER NFPA 58, TABLE 3-2.2.2. | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | PER NFPA 58 SECTION 3-2.2.7(H). | | | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW | | CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO | | BE DOWN STREAM OF MANUAL VALVE. | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2018-02-14 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2018-02-14 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-02-05 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-01-31 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-01-22 |
Time |
16:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-01-22 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-01-22 |
Time |
12:49 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-12-21 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-11-02 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-11-02 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-10-17 |
Time |
16:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-08-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-08-10 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-07-07 |
Time |
14:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
6 |
Status |
P |
Date |
2018-03-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-03-01 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-03-01 |
Time |
13:16 |
Sent To |
|
|
Notes |
2018-03-01 13:16:35 | MU-2018-006143-0000 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
5 |
Status |
F |
Date |
2018-02-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-02-12 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-02-12 |
Time |
10:55 |
Sent To |
|
|
Notes |
2018-02-12 10:56:56 | AS OF THIS DATE THE PLANS HAVE NOT RECEIVED A PALM | | BEACH COUNTY IMPACT FEE REVIEW. BEFORE A PERMIT TO | | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. ONE SET OF PLANS WILL HAVE TO BE | | TAKEN (BY THE CONTRACTOR OR REPRESENTATIVE) TO THE PALM | | BEACH COUNTY IMPACT FEE OFFICE LOCATED AT 2300 N. JOG | | RD. ROOMS 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
4 |
Status |
F |
Date |
2018-01-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-01-29 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-01-29 |
Time |
07:20 |
Sent To |
|
|
Notes |
2018-01-29 07:56:03 | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
F |
Date |
2018-01-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-01-11 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-01-11 |
Time |
07:16 |
Sent To |
|
|
Notes |
2018-01-11 08:48:03 | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2017-10-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-10-24 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-10-24 |
Time |
11:32 |
Sent To |
|
|
Notes |
2017-10-24 15:15:08 | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2017-07-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-07-25 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-07-24 |
Time |
11:57 |
Sent To |
|
|
Notes |
2017-07-25 17:21:05 | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2018-02-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-02-01 |
Time |
12:23 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-02-01 |
Time |
12:14 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2018-01-31 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-01-31 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-01-31 |
Time |
13:20 |
Sent To |
I |
|
Notes |
2018-01-31 14:59:21 | 4TH REVIEW FBC-2014 MECHANICAL | | PERMIT #17070253 | | 1/31/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PERSON WHO PREPARED THE ENERGY CALCULATIONS | | CANNOT SIGN AS THE OWNER/AGENT TO CERTIFY THE BUILDING | | IS IN COMPLIANCE WITH THE FLORIDA ENERGY CODE, UNLESS | | THAT PERSON HAS BEEN LEGALLY DESIGNATED AS THE AGENT BY | | THE OWNER. IN LIEU OF PROVIDNG DOCUMENTATION TO VERIFY | | KAREN WALLEN OLIVER IS THE LEGAL DESIGNEE, THE OWNER OR | | ARCHITECT OF RECORD CAN PROVIDE THE CERTIFICATION | | | | SIGNATURE- SECTION C103.1.1.2 FBC -14 ENERGY | | CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2017-12-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-12-28 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-12-28 |
Time |
16:50 |
Sent To |
|
|
Notes |
2017-12-28 17:46:13 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #17070253 | | 12/28/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REFER TO SECTION 607.5.4 CONCERNING THE FLEX DUCTS | | PENETRATING THE CORRIDOR WALLS AS SHOWN ON SHEETS M.01, | | M.02, M.03, & M.04. THE CORRIDOR WALLS HAVE BEEN | | DESIGNATED AS SMOKE BARRIERS ON SHEETS A.02, A.03, AND | | A.04, AND THEREFORE ONLY STEEL DUCTS WITH THICKNESSES | | NO LESS THAN 0.019 INCH (0.48MM) ARE PERMITTED TO | | PENETRATE THE WALLS WITHOUT SMOKE DAMPERS- SEE | | EXCEPTION 3 AND PROVIDE EITHER SMOKE DAMPERS TO PROTECT | | THE PENETRATIONS, OR CHANGE THE DUCTS TO STEEL. | | | | 2) SHEET M.01: THE AIR BALANCE CALULATION FOR THE | | KITCHEN DOES NOT INCLUDE THE HOOD EXHAUST AND SUPPLY | | CFMS. | | | | 3) SHEET M.01: THE CARRIER INFINITY MODEL NO. | | 24ANB748A003 IS A 4-TON 17 SEER VARIABLE SPEED UNIT. IT | | IS INCORRECTLY LISTED AS IN THE HVAC SCHEDULES AS A | | 5-TON, A 3.75-TON, A 3.25 TON, A 4.75 TON, AND A 2.0 | | TON UNIT. PLEASE CORRECT THE SCHEDULES AND CORRECT THE | | ENERGYGAUGE COMPLIANCE FORM WHICH IS ALSO LISTING | | INCORRECT DATA FOR CAPACITIES AND EFFICIENCY RATINGS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-10-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-10-30 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-10-30 |
Time |
12:30 |
Sent To |
|
|
Notes |
2017-10-30 14:40:17 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17070253 | | 10/30/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS | | FOR THE NEW AC SYSTEMS- SECTION C403.2.1 CALCULATION OF | | HEATING AND COOLING LOADS. | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | APPLICATION FOR THE MECHANICAL PERMIT. | | | | 2) 2ND REQUEST FOR AIR BALANCE CALCULATIONS IN THE | | KITCHEN AND DINING ROOM. | | | | 3) PLEASE PROVIDE A FL. PRODUCT APPROVAL OR A | | MIAMI-DADE NOA FOR THE O/A INTAKE LOUVER- RULE 9N-3 | | FLORIDA ADMINISTRATIVE CODE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-07-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-07-17 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-07-17 |
Time |
12:02 |
Sent To |
|
|
Notes |
2017-07-17 14:27:28 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | ENERGY CONSERVATION CODES. | | PERMIT #17070253 | | 7/17/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) PROVIDE AN AIR BALANCE CALCULATION FOR THE KITCHEN | | AND DINING ROOM AREAS. | | | | 3) PLACE A NOTE ON THE PLAN INDICATING THAT SEPARATE | | PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST AND FIRE | | SUPPRESSION SYSTEMS. PLEASE NOTE THAT CONDITIONED | | MAKEUP AIR MAY BE REQUIRED FOR THE HOOD EXHAUST- | | SECTION 508.1.1. | | | | 4) FIRE DAMPERS ARE REQUIRED FOR ALL SUPPLY, RETURN, | | AND EXHAUST DUCTS AND TRANSFERS THAT ARE PENETRATING | | THE FIRE-RATED CORRIDOR WALLS, RESIDENT ROOM WALLS, | | OFFICE WALLS, ETC.- SEE SECTION 607.5.2 & 607.5.3. | | | | 5) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | SYSTEMS OF ALL OF THE 5.0 TON AIR HANDLERS PER SECTION | | 606.2.1. PLEASE NOTE THAT A TYPICAL 5-TON SYSTEM CAN | | PRODUCE OVER 2000 CFMS OF SUPPLY AIR. PROVIDE SYMBOLS | | ON THE PLANS TO IDENTIFY THE LOCATIONS OF THE DEVICES. | | | | 6) INDICATE HOW ACCESS FOR SERVICE AND REPLACEMENT OF | | THE AIR HANDLERS ABOVE THE CEILING WILL BE | | ACCOMPLISHED. SHOW THE LOCATIONS OF ACCESS PANELS AND | | PROVIDE DETAILS AND DIMENSIONS- SECTION 306.1. | | | | 7) VERIFY WITH NOTES, OR PROVIDE CLEARANCE DISTANCE | | MEASUREMENTS FOR ALL O/A INTAKE OPENINGS TO EXHAUST | | OUTLETS, PROPERTY LINES, AND DRIVE AREAS SUCH AS | | DRIVEWAYS OR PARKING LOTS- SECTION 401.4. | | | | 8) PROVIDE MOTORIZED OR GRAVITY DAMPERS FOR ALL O/A | | INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY | | CONSERVATION. | | | | 9) REFER TO SECTION 506.3.13.2 AND PROVIDE THE REQUIRED | | CLEARANCE DISTANCE MEASUREMENTS FOR THE HOOD EXHAUST | | OUTLET. | | | | 10) PROVIDE AN ENLARGED KTICHEN PLAN AND EQUIPMENT | | SCHEDULE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | ALL COOKING APPLIANCES AND THE EXHAUST HOOD. PLEASE | | NOTE THAT COMBUSTION AIR CALCULATIONS ARE REQUIRED FOR | | GAS-FIRED APPLIANCES. | | | | 11) PROVIDE AN AIR DEVICE SCHEDULE. | | | | 12) M-02: SHOW A MEANS OF RETURN AIR FROM GROUP 106, & | | OFFICES 105, 107, & 108- SECTION 601.5. | | | | 13) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER | | SMACNA STANDARDS. | | | | 14) M-04: PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | STRUCTURAL ENGINEERING FOR INSTALLATION OF THE ROOF TOP | | CONDENSERS AND ROOF STANDS- SECTION 301.15. SUBMIT A | | FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE STANDS | | IF APPLICABLE. | | | | 15) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW SYSTEMS.- SECTION C403.2.1 FBC-14 ENERGY | | CONSERVATION. | | | | PLEASE NOTE THAT FURTHER COMMENTS MAY OCCUR AFTER | | CORRECTED PLANS A RE-SUBMITTED. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2018-01-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-01-18 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-01-18 |
Time |
16:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2017-10-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-10-30 |
Time |
06:54 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-10-26 |
Time |
09:12 |
Sent To |
|
|
Notes |
2017-10-27 15:15:52 | 1) SHT. A-00 NOTES 26 BEDS BUT SHT. A-00.1 NOTES THE | | SLEEPING AREA OCCUPANT LOAD AS 63. CLARIFY. | | 2) SHT.A-08 - THE CONFIGURATION OF THE ACCESSIBLE | | SHOWER IN THE ADA SLEEPING ROOM DOES NOT COMPLY WITH | | THE 2014 FBC-ACCESSIBILITY SEC.608.2.2 (STANDARD | | ROLL-IN SHOWER) OR 608.2.3 ( ALTERNATE ROLL-IN SHOWER). | | 3) THE SHOWER SEAT IN THE ACCESSIBLE SHOWER IN THE ADA | | SLEEPING ROOM SHALL COMPLY WITH 2014 FBC - | | ACCESSIBILITY SECS 610.3.1 OR 610.3.2. | | 4) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWER IN THE | | ADA SLEEPING ROOM SHALL COMPLY WITH 2014 | | FBC-ACCESSIBILITY SECS. 608.5.2 OR 608.5.3. | | 5) THE GRAB BARS IN THE ACCESSIBLE SHOWER IN THE ADA | | SLEEPING ROOM SHALL COMPLY WITH 2014 FBC-ACCESSIBILITY | | SECS.608.3.2 OR 608.3.3. | | 6) SHT. A-01 - THE ACCESSIBLE FIGURE NUMBERS ARE FROM | | AN OUTDATED CODE. PROVIDE THE CORRECT FIGURE NUMBERS | | FROM THE 2014 FBC-ACCESSIBILITY.WPB AMEND. TO FBC | | SEC.107.2.1. | | 7) SHT. P-05 - THE BACK TO BACK SHOWERS IN THE SLEEPING | | ROOMS ARE NOT VENTED.COMPLY WITH 2014 FBC-PLUMBING | | SEC.901.2.1. | | 8) PROVIDE INFORMATION AS TO WHAT STANDARD THE GREASE | | INTERCEPTOR CALCULATIONS ARE BASED ON. THERE IS NO | | REFERENCE TO ANY RECOGNIZED STANDARD OR CODE SECTION. | | 2014 FBC- PLUMBING SEC. 1003.2. | | 9) SHTS. P-01 & P-02 SHOWS A 4 INCH TEST PORT AND SHT. | | P-05 SHOWS 3 INCH.CLARIFY. | | 10) SHOW THE HOT WATER RECIRCULATION LINE ON THE WATER | | HEATER DETAIL ON SHT. P-08. | | 11) SHT. A-00 - PROPERTY INFORMATION BOX - THERE IS A | | NOTE IN THE "OCCUPANT LOAD" AREA THAT REFERS TOSHT. | | LS-01. THERE IS NO SUCH SHEET IN THESE PLANS. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-07-19 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-07-19 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-07-19 |
Time |
09:42 |
Sent To |
|
|
Notes |
2017-07-19 14:54:51 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE BATHROOMS IN THE ACCESSIBLE UNITS DO NOT COMPLY | | WITH FBC ACC 223.2.1 FACILITIES NOT SPECIALIZING IN | | TREATING CONDITIONS THAT AFFECT MOBILITY. | | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS | | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER | | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE | | MOBILITY FEATURES COMPLYING WITH 805. | | | | 805.4 TOILET AND BATHING ROOMS. | | TOILET AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A | | PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH | | 603.WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE | | LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH | | THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610. | | | | PROVIDE DETAIL SHOWING COMPLIANCE WITH ALL ELEMENTS. | | PER WPB AMEND TO FBC 107.2.1 | | | | 2. SHT. A-01 FIG. #28 IS FOR THE EXCEPTIONN FOR | | RESIDENTIAL DWELLING UNITS AND DOES NOT COMPLY WITH THE | | I2 OCCUPANCY THE ACCESSIBLE TOILETS SHALL COMPLY WITH | | FBC ACC 604.3.2 WITHOUT EXCEPTIO3. | | | | 3. THE SHOWERS IN THE ACCESSIBLE BATHROOMS DO NOT | | COMPLY WITH FBC ACC 608.2.1 OR 608.2.2 OR 608.2.3 | | | | 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 | | DISPENSERS. | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | THE CENTERLINE OF THE DISPENSER. | | | | 5. ALL GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | GRIPPING SURFACE PER FBC ACC 609.4 | | | | 6. SHT. P-01 THE NOTE ON THE FD IN KITCHEN IS CALLING | | OUT FOR A BACKFLOW PREVENTER THE FD SHALL BE EQUIPPED | | WITH A TRAP PRIMER PLEASE CLARIFY WHAT YOU MEAN BY | | BACKFLOW. PER WPB AMEND TO FBC 107.2.1 | | | | 7. PLEASE PROVIDE CALCULATIONS FOR GREASE INTERCEPTOR. | | PER WPB AMEND TO FBC 107.2.1 | | | | 8. THE HORIZONTAL VENTS ON THE WC AND SH IN THE | | ACCESSIBLE BATHROOMS ARE NOT COMPLAINT THOSE FIXTURE | | ARE VENTED BY THE LAVATORY. PER FBC PL 905.3 AND 905.4 | | | | 9. A TEST PORT OF A MIN OF 4" IS REQUIRED ON THE OUTLET | | OF THE GREASE INTERCEPTOR A 4" TWOWAY CLEAN OUT CAN BE | | USED. PER WPB ORD. | | | | 10. TEMPERED WATER IS REQUIRED AT THE LAVATORY'S IN THE | | COMMON BATHROOMS. PER FBC PL 416.5 TEMPERED WATER FOR | | PUBLIC HAND-WASHING FACILITIES. | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125 | | | | 11. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW AT | | WATER METER PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO | | FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2018-02-13 |
|
|
Cont ID |
|
Sent By |
LL |
Date |
2018-02-13 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2018-02-13 |
Time |
|
Sent To |
I |
|
Notes |
2018-02-13 13:11:56 | ZONING APPROVED WITH THE FOLLOWING PROVISO: | | | | 1.) SEPARATE PERMIT APPLICATIONS AND REVIEW REQUIRED | | FOR THE FOLLOWING: FENCE/WALL, SIGNAGE, PARKING AREA, | | LANDSCAPE AND IRRIGATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2018-01-30 |
|
|
Cont ID |
|
Sent By |
LL |
Date |
2018-01-30 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2018-01-29 |
Time |
|
Sent To |
|
|
Notes |
2018-01-30 11:28:21 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) THE PROPOSED 6 FT. HIGH FENCE (FENCE AND CONCRETE | | COLUMNS) ALONG THE SIDE PROPERTY LINE (OLD OKEECHOBEE | | ROAD) SEEMS TO BE WITHIN THE VISIBILITY TRIANGLE PER | | ZLDR S.94-305(E). PLEASE DEMONSTRATE COMPLIANCE BY | | SHOWING THE VISIBILITY TRIANGLE AND THE PROPOSED FENCE | | LOCATED OUTSIDE OF THE TRIANGLE. THE VISIBILITY | | TRIANGLE SHALL COMPLY WITH THE DIMENSION REQUIREMENTS | | OF ZLDR S.94-305(E) [1/9/18 REPEAT COMMENT] | | | | 2.) SHOW SIGN AREA CALCULATIONS FOR EACH LOW | | FREESTANDING SIGN. PLEASE NOTE THAT THE SIGN AREA ON | | THE FRONT STREET (AUSTRALIAN AVE.) SHALL BE A MAXIMUM | | OF 1.25 SQ. FT. FOR EACH ONE LINEAR FOOT OF FRONT | | STREET FRONTAGE, AND A MAXIMUM OF 0.75 SQ. FT. FOR EACH | | ONE LINEAR FOOT OF SIDE STREET FRONTAGE (OKEECHOBEE | | RD.). IF THE SIGN AREA CALCULATIONS ARE THE SAME, THEN | | IT SHOULD BE NOTED IN THE PLANS. [1/9/18 REPEAT | | COMMENT] | | | | | | NOTES: | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * ZONE: GC | | | | * REFERENCE: ZBA FINAL ORDER 3323 | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2018-01-09 |
|
|
Cont ID |
|
Sent By |
LL |
Date |
2018-01-09 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2017-12-28 |
Time |
15:08 |
Sent To |
|
|
Notes |
2018-01-09 13:22:12 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) THE PROPOSED 6 FT. HIGH FENCE ALONG THE SIDE | | PROPERTY LINE SEEMS TO BE WITHIN THE VISIBILITY | | TRIANGLE PER ZLDR S.94-305(E). PLEASE DEMONSTRATE | | COMPLIANCE BY SHOWING THE VISIBILITY TRIANGLE AND THE | | PROPOSED FENCE LOCATED OUTSIDE OF THE TRIANGLE. | | | | 2.) PLEASE DEFINE THE SIGN AREA. PER THE ZLDRS, THE | | AREA OF THE FACE OF A SIGN SHALL BE THE SMALLEST | | CIRCLE, TRIANGLE, OR PARALLELOGRAM, WHICH CONTAINS ALL | | CONTENT, BACKGROUND, AND STRUCTURAL ELEMENTS OF THE | | SIGN. [ZLDR S.94-405] | | | | 3.) SHOW SIGN AREA CALCULATIONS FOR EACH LOW | | FREESTANDING SIGN. PLEASE NOTE THAT THE SIGN AREA ON | | THE FRONT STREET (AUSTRALIAN AVE.) SHALL BE A MAXIMUM | | OF 1.25 SQ. FT. FOR EACH ONE LINEAR FOOT OF FRONT | | STREET FRONTAGE, AND A MAXIMUM OF 0.75 SQ. FT. FOR EACH | | ONE LINEAR FOOT OF SIDE STREET FRONTAGE (OKEECHOBEE | | RD.). [ZLDR S.94-408(D)] | | | | | | NOTES: | | | | * SEPARATE PERMIT REVIEW AND APPLICATIONS REQUIRED FOR: | | LANDSCAPING, SIGNAGE, PARKING LOT STRIPING AND AWNINGS. | | PLEASE NOTE THAT PER ZBA FINAL ORDER 3323, A | | CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL ALL | | CONDITIONS HAVE BEEN SATISFIED (PERMITS ISSUED AND THE | | WORK IMPLEMENTED ACCORDING TO PLANS). | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * ZONE: GC | | | | * REFERENCE: ZBA FINAL ORDER 3323 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-10-23 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2017-10-20 |
Time |
10:25 |
Sent To |
|
|
Notes |
2017-10-23 14:39:08 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) PLEASE CLARIFY IF THE PROPOSED SIGNS ARE LOW OR | | HIGH FREESTANDING SIGNS. EVEN THOUGH THE SIGNS SHALL BE | | PERMITTED BY A SEPARATE PERMIT, IT WOULD BE HELPFUL TO | | PROVIDE A GENERAL DETAIL OF EACH SIGN TO DETERMINE IF | | THE SIGNS ARE IN COMPLIANCE WITH THE ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDRS). | | | | 2.) FREESTANDING SIGNS SHALL BE PLACED A MINIMUM OF 5 | | FT. FROM THE PROPERTY LINE. SITE PLAN SHOWS THAT THE | | SIGN SETBACKS CURRENTLY DO NOT COMPLY WITH THIS | | REQUIREMENT. CLEARLY SHOW THE SETBACK FROM EACH | | PROPOSED SIGN TO THE PROPERTY LINE. [ZLDR S.94-408(D)] | | | | 3.) SEPARATE PERMIT REVIEW AND APPLICATIONS REQUIRED | | FOR: LANDSCAPING, SIGNAGE, PARKING LOT STRIPING AND | | AWNINGS. PLEASE NOTE THAT PER ZBA FINAL ORDER 3323, A | | CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL ALL | | CONDITIONS HAVE BEEN SATISFIED (THE PERMITS ISSUED AND | | THE WORK IMPLEMENTED ACCORDING TO PLANS). | | | | | | NOTES: | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENT. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * ZONED: GC | | | | * REFERENCE: ZBA FINAL ORDER 3323 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2017-07-26 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2017-07-26 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2017-07-26 |
Time |
|
Sent To |
|
|
Notes |
2017-07-26 15:43:30 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) ZBA FINAL ORDER 3323 STATES THAT THERE WILL BE A | | TOTAL OF FORTY-FOUR (44) BEDS; HOWEVER, THE PLANS | | INDICATE A TOTAL OF SEVENTY-FIVE (75). PLEASE | | ADDRESS/CORRECT. | | | | 2.) PLEASE CLARIFY HOW GUESTS OF PATIENTS WILL GET | | ACCESS TO THE PARKING LOT AREA IF THERE ARE MOTORIZED | | GATES PROPOSED? | | | | 3.) PROVIDE DIMENSION TO THE TALLEST POINT OF THE | | BUILDING (INCLUDING DECORATIVE FEATURES). | | | | 4.) PROJECTIONS (I.E. AWNINGS/CANOPIES) ARE SHOWN IN | | THE ELEVATIONS. PLEASE NOTE THAT CANOPIES/AWNINGS | | CANNOT PROJECT MORE THAN 4 FT. INTO ANY SETBACK. | | ILLUSTRATE IN THE PLANS (INCLUDING SITE PLAN) TO | | DEMONSTRATE COMPLIANCE. [ZLDR S.94-305(A)(5)] | | | | 5.) SHOW SETBACK DIMENSIONS FOR THE PROPOSED NEW PORTE | | COCHERE TO THE PROPERTY LINE(S). | | | | 6.) SIGNAGE IS NOT A PART OF THIS REVIEW; HOWEVER, ALL | | PROPOSED SIGNAGE MUST COMPLY WITH THE REQUIREMENTS OF | | ARTICLE XIII OF THE ZONING AND LAND DEVELOPMENT | | REGULATIONS (ZLDRS). | | | | | | NOTE: | | | | * REFERENCE: ZBA FINAL ORDER 3323 | | | | * SEPARATE PERMIT APPLICATIONS AND REVIEW REQUIRED FOR | | THE FOLLOWING: LANDSCAPING, PAVING AND STRIPING, | | SIGNAGE, AND FENCE/MECHANICAL GATES. A HOLD WILL BE | | PLACED ON THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | UNTIL ALL CONDITIONS OF FINAL ORDER 3323 HAVE BEEN | | ADDRESSED AND ALL PERMITS HAVE BEEN ISSUED. | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |