Plan Review Details - Permit 17070187
Plan Review Stops For Permit 17070187
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-30 Cont ID  
Sent By shill Date 2017-11-30 Time 08:13 Rev Time 0.00
Received By shill Date 2017-11-30 Time 08:13 Sent To I
Notes
2017-11-30 08:13:40***PROVIDE DETAIL AT INSPECTION - REVISION REQUIRED IF
 REQUESTED BY INSPECTOR***
 **ISSUED AT APPLICANT'S RISK**
  
 1. REVISE THE "DUAL FUEL VENTILATION" DETAIL ON SHEET
 3.3M:
  
 A. NO SPEC FOR THE ANCHORS OTHER THAN "EYEBOLTS"
 (LACKING SIZE, MATERIAL, MINIMUM EMBEDMENT, TYPE OF
 EYEBOLT).
  
 B. SUBSTRATE NOT CLEAR; SPEC INDICATES "MASONRY
 ANCHORED EYEBOLTS" BUT DOES NOT INDICATE DECK TYPE,
 REVISE TO INCLUDE. SPEC IMPLIES THAT THE SUBSTRATE IS
 "MASONRY" - DO YOU MEAN CONCRETE?
  
 C. SPEC STATES "PITCH POCKETS" AFTER ANCHOR BOLTS;
 PROVIDE A DETAIL, INSTALLATION SPEC IS NOT CLEAR.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By jwitmer Date 2017-10-31 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2017-10-31 Time 13:24 Sent To  
Notes
2017-10-31 10:29:32BUILDING PLAN REVIEW
 W. P. B. REVISION: 17070187
 W. P. B. PERMIT: 16120091
 ADD: 332 EVERNIA ST.
 CONT: MONTEIRO DEVELOPMENT INC.
 TEL: 561-346-6916
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 31/ 2017
 ACTION: DENIED
  
 1) THE SHEET 3.1 SHOWS A NEW PIZZA OVEN, THERE WILL BE
 MANY COMMENTS ABOUT THE USE AND LISTING OF THE OVEN AND
 VENTING. UNDER THE BUILDING CODE, 2014 FBC-B PLEASE
 PROVIDE HOW HIGH THE VENT WILL PENETRATE THE ROOF, WE
 WILL ALSO NEED TO KNOW THE HEIGHT OF THE PARAPET IN
 THIS AREA AS WELL AS THE HEIGHT OF THE OVERALL VENT AND
 IF THE VENT WILL REQUIRE, GUIDE WIRES FOR THE WIND AND
 HOW TO ANCHOR THE WIRES/ SUPPORTS TO THE ROOF AND TO
 THE VENT ITSELF.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2) PLEASE PROVIDE WHAT TYPE OF ROOF PENETRATION WILL BE
 MADE FOR THE STRUCTURAL DECK, AND HOW WILL THE OPENING
 AND VENT BE PROTECTED FROM WATER INTRUSION.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-29 Cont ID  
Sent By jpearson Date 2017-11-29 Time 07:30 Rev Time 0.00
Received By jpearson Date 2017-11-29 Time 07:30 Sent To  
Notes
2017-11-29 07:30:33APPROVED WITH EXCEPTION. BREAKER SIZE FEEDING PANEL C
 AND PANEL P ARE LIMITED TO 60 AMP FOR WIRE SIZE SHOWN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By jleahy Date 2017-11-02 Time 10:18 Rev Time 0.00
Received By jpearson Date 2017-11-02 Time 08:44 Sent To  
Notes
2017-11-02 10:18:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WHAT IS RATING OF METER CAN BEING INSTALLED? PROVIDE
 SPEC SHEETS. NEC 110.3
 2. PANEL A DOES NOT SHOW LOAD OF PANEL P. INCLUDE ALL
 LOADS IN PANEL A SCHEDULE. NEC 215.2, 408.30; FBC
 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, SHOW CURRENT
 DRAW FOR EACH PHASE. IT APPEARS THAT THE STATED 500
 KCMIL SERVICE IS OVERLOADED. CLARIFY AND/OR CORRECT AS
 NEEDED. NEC 215.2, 220, 230.42; FBC 107.2.1
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE NOTE FOR MARKING OF HI-LEG PER CODE. NEC
 110.15, 408.3(E) AND (F)(1)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PIECE OF SERVICE EQUIPMENT AND THE DOWNSTREAM PANELS.
 INCLUDE INFORMATION FROM THE POWER COMPANY STATING WHAT
 THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE
 TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 7. WIRING FROM DISCONNECT A TO PANEL A REQUIRES AN EGC.
 PROVIDE CORRECTION. NEC 250.122
 8. PROVIDE PANEL SCHEDULE FOR BREWHOUSE PANEL TO
 CONFIRM SIZING AND AIC RATINGS. NEC 110.3, 110.10,
 408.4, 408.30; FBC 107.2.1
 9. CLARIFY LOCATION FOR PANEL A AND PANEL B. IT APPEARS
 THAT THEY OCCUPY THE SAME SPACE IN A WALL. PROVIDE
 CORRECTION IF NECESSARY. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By pleduc Date 2017-11-21 Time   Rev Time 0.00
Received By pleduc Date 2017-11-21 Time 10:55 Sent To  
Notes
2017-11-21 12:50:03PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION.
  
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 1) THE PIZZA OVEN AS PROPOSED AND INSTALLED SHALL ONLY
 BE USED TO PREPARE PIZZA. ANY ADDITIONAL FOOD ITEMS
 THAT PRODUCE GREASE LADON VAPORS, INCLUDING, BUT NOT
 LIMITED TO, CHICKEN, CHICKEN WINGS, HAMBURGERS, HOT
 DOGS, AND RIIBS IS NOT APPROVED WITHOUT A INSTALLED
 FIRE SUPPRESSION SYSTEM.
  
 2) FUTURE FINDINGS OF THESE ITEMS OR THE BUILD-UP OF
 GREASE LADON VAPORS TO DANGEROUS LEVELS MAY CAUSE A
 CEASE AND DESIST OF THE PIZZA OVEN USE UNTIL
 CORRECTIONS ARE MADE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By pleduc Date 2017-10-25 Time   Rev Time 0.00
Received By pleduc Date 2017-10-25 Time 11:09 Sent To  
Notes
2017-10-25 15:10:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE REFERENCES TO THE ADDITION OF A PIZZA
 OVEN.
  
 I DO NOT FIND ANY PLAN SUBMITTALS FOR ANY PIZZA OVEN
 AND/OR ANY HOOD VENTILATION/SUPPRESSION SYSTEMS FOR
 THIS ADDRESS.
  
 SEPARATE SHOP DRAWINGS SHALL BE SUBMITTED THAT MEET THE
 REQUIRERMENTS OF THE MANUFACTURER AND NFPA 96.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 15:08 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 15:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-11-04 Cont ID  
Sent By gjohnson Date 2017-11-04 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2017-11-04 Time 09:49 Sent To  
Notes
2017-11-04 09:53:243RD REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. SHALL COMPLY WITH COMMENTS FROM BUILDING, FIRE AND
 MECHANICAL FOR VENTING OF PIZZA OVEN. WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-09-01 Cont ID  
Sent By gjohnson Date 2017-09-01 Time 08:48 Rev Time 0.00
Received By gjohnson Date 2017-09-01 Time 08:48 Sent To  
Notes
2017-09-01 08:49:452ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: NOT COMPLIED 2ND REQUEST
  
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 NEW COMMENTS:
 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 3. PLEASE BE ADVISED THAT A SEPARATE PERMIT APPLICATION
 WITH A COMPLETE SET OF PLANS AND SPECIFICATIONS IS
 REQUIRED FOR THE PIZZA OVEN THAT WILL GET A COMPLETE
 REVIEW BY FIRE , MECHANICAL, AND BUILDING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 09:34 Rev Time 0.00
Received By gjohnson Date 2017-07-14 Time 09:34 Sent To  
Notes
2017-07-14 09:51:061ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. DRAWING SHALL BE SIGNED AND SEALED BY DESIGNER OF
 RECORD FOR THIS PROJECT. WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 3. PROVIDE FLOOR PLAN SHOWING LOCATION OF PIZZA OVEN.
 WPB AMEND TO FBC 107.2.1
  
 4. CHANGES MADE ON PLAN WRITTEN IN PEN SHALL BE
 INITIALED BY DESIGNER OF RECORD. WPB AMEND TO FBC
 107.2.1
  
 5. THE SIZING TABLE SUBMITTED IN REV PACKAGE IS FBC FG
 TABLE 402.4(27) IT IS FOR PROPANE PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-30 Cont ID  
Sent By shill Date 2017-11-30 Time 08:13 Rev Time 0.00
Received By shill Date 2017-11-20 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-04 Cont ID  
Sent By gjohnson Date 2017-11-04 Time 09:53 Rev Time 0.00
Received By gjohnson Date 2017-10-20 Time 13:10 Sent To  
Notes
2017-10-24 13:10:50C21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-01 Cont ID  
Sent By gjohnson Date 2017-09-01 Time 10:36 Rev Time 0.00
Received By gjohnson Date 2017-08-30 Time 14:17 Sent To  
Notes
2017-08-31 14:17:21RESUB OF REVISION ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 09:51 Rev Time 0.00
Received By gjohnson Date 2017-07-06 Time 10:26 Sent To  
Notes
2017-07-10 10:26:52GJOHNSON'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-11-30 Cont ID  
Sent By ccole Date 2017-11-29 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-11-29 Time 08:46 Sent To I
Notes
2017-11-29 09:21:18MECHANICAL PROVISOS:
  
 1) PROVIDE A REVISED DUAL FUEL VENTILATION DETAIL WITH
 THE CORRECT UL1978 LISTING, AND THE "ZERO CLEARANCE
 GREASE DUCT" NOTE REMOVED.
  
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE PIZZA OVEN AND THE GREASE DUCT
 MUST BE ONSITE AT TIME OF INSPECTION.
  
 3) LIGHT TEST FOR GREASE DUCT REQUIRED- SECTION
 506.3.2.5.
  
 CCOLE- 11/30/17
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By ccole Date 2017-11-03 Time 09:39 Rev Time 0.00
Received By ccole Date 2017-11-03 Time 08:19 Sent To  
Notes
2017-11-03 10:08:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070187
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SELECTED B-VENT CANNOT BE USED AS A GREASE
 EXHAUST DUCT FOR THE PIZZA OVEN. PLEASE REVIEW THE
 PIZZA OVEN VENTING OPTIONS ON THE FRONT SHEET WHICH
 INDICATES TWO METHODS- DIRECT VENTING WITH 8 INCH
 "CHIMNEY" PIPE LISTED TO UL 103HT AND INSTALLED PER UL
 737, OR ATYPE 1 HOOD SYSTEM AND GREASE EXHAUST DUCT.
 THE UL 103 HT LISTED DUCTS TYPICALLY ALSO CARRY THE UL
 1978 LISTING APPLIED TO FACTORY BUILT GREASE DUCTS- SEE
 SECTION 506.3 & 506.3.1.1., AND IN SOME CASES CARRY THE
 UL 2221 LISTING APPLIED TO GREASE DUCT ENCLOSURES- SEE
 SECTION 506.3.11.3.
  
 2) REFER TO SECTION 7.8.2 NFPA 96 ROOFTOP TERMINATIONS
 ITEMS 1-9 AND SHOW COMPLIANCE. PLEASE NOTE THAT AN
 EXHAUST FAN IS REQUIRED PER ITEMS #8 & 9. PLEASE REVIEW
 THE MUGNAINI WEBSITE WHICH PROVIDES OPTIONS FOR EXHAUST
 DUCTS AND FANS,
  
 3) SHEET 3.4M: VERIFY THE TERMINATION LOCATION OF THE
 GREASE DUCT IS NOT WITHIN 10' OF THE ROOF EDGE OR
 PROVIDE A GUARD IF THE EXISTING PARAPET IS LESS THAN
 42".
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-04 Cont ID  
Sent By gjohnson Date 2017-11-04 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2017-11-04 Time 08:31 Sent To  
Notes
***NONE***