Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-12 Cont ID  
Sent By jwitmer Date 2018-02-12 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2018-02-12 Time 16:03 Sent To  
Notes
2018-02-12 17:02:20BUILDING PLAN REVIEW
 W. P. B. REVISION: 17070136
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO.
 TEL: 561-832-1616
 E-MAIL: [email protected] / ED HANRATTY
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 3RD REVIEW
 DATE: MON. FEB. 12/ 2018
  
 ACTION: BUILDING PROVISO
  
 1) PROVISO: SHAFT WALLS AND CHASE WALLS TO COMPLY WITH
 2010 FBC-B 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/ CEILING SEPARATING DWELLING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 2) PROVISO: RESPONSE INDICATES THE ROOFING COMPOSITION
 IS STILL PENDING TO BE PROVIDED AT A LATER TIME AS A
 DEFERRED SUBMITTAL. 107.3.4.2. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 3)PROVISO: VOIDED FOR THIS REVIEW. FOLDER20171212 PDF
 SHEET GENERATOR FRAMING ENCLOSURE, NO ELECTRONIC
 SIGNATURE FROM ROBERT WARR. P. E. AND NEEDS / PROVIDE
 SHAFTWALL INSTALLATION DETAILS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST./ WEST PALM BEACH. FL 33402
 TEL: 561-805-6715 / FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-09 Cont ID  
Sent By jwitmer Date 2018-01-09 Time 16:22 Rev Time 0.00
Received By jwitmer Date 2018-01-09 Time 12:25 Sent To  
Notes
2018-01-09 15:30:41BUILDING PLAN REVIEW
 W. P. B. REVISION: 17070136
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO.
 TEL: 561-832-1616
 E-MAIL: [email protected] / ED HANRATTY
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. JAN. 09 / 2018
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. SUBMITTED FOR DIGITAL PLAN REVIEW IS
 THE 2ND ELEVATION CERTIFICATE, BUILDING UNDER
 CONSTRUCTION. PLEASE NOTE THE CERTIFICATE SUBMITTED
 DATED 4/18/17 DOES SHOW A SIGNATURE AND SEAL BUT IT IS
 NOT A DIGITAL SIGNATURE, IT APPEARS THIS WAS SCANNED IN
 BUT ORIGINALLY A PAPER SCANNED TO BE ELECTRONIC BUT NO
 ELECTRONIC SIGNATURE. EITHER SUBMIT AN ELECTRONIC
 VERSION WITH ELECTRONIC SIGNATURE OR SUBMIT A PAPER
 WITH ORIGINAL SEAL AND SIGNATURE.
 SURVEYORS: F. S. 472.025 SEALS. . EACH REGISTRANT MAY
 IN ADDITION REGISTER HIS OR HER SEAL ELECTRONICALLY IN
 ACCORDANCE WITH SS. 668.001-668.006. DRAWINGS, PLANS,
 SPECIFICATIONS, REPORTS, OR DOCUMENTS PREPARED OR
 ISSUED BY A REGISTRANT MAY BE TRANSMITTED
 ELECTRONICALLY AND MAY BE SIGNED BY THE REGISTRANT,
 DATED, AND STAMPED ELECTRONICALLY WITH SUCH SEAL IN
 ACCORDANCE WITH SS. 668.001-668.006.
  
 LINE A4 INDICATES THIS TO BE A RESIDENTIAL BUILDING.
 PLEASE NOTE USING THE FEMA DEFINITIONS, THIS IS NOT A
 RESIDENTIAL BUILDING, BUT A MIXED USE BUILDING.
  
 LINE C2A) THE TOP OF THE BOTTOM FLOOR INCLUDING
 BASEMENT IS INDICATED AS 11.00 FEET NGVD. NO THE BOTTOM
 PARKING FLOOR IS LOWER ELEVATION THAN INDICATED. THE
 BOTTOM OF THE BUILDING IS DRY FLOOD PROOFED, BFE + 1
 FOOT.
  
 LINE C2D) INDICATES THE LOWEST SLAB AT 0.30 FT. NGVD IS
 THIS THE ELEVATOR PIT?
  
 LINE C2E) LOWEST ELEVATION OF MACHINERY OR EQUIPMENT
 SERVING THE BUILDING. PLEASE NOTE THERE IS ELECTRICAL
 SWITCH GEAR BELOW THE BFE BUT THE BUILDING IS DRY FLOOD
 PROOFED. THIS BUILDING IS BUILT TO FEMA'S TECHNICAL
 BULLITIN 3-93. FLOODPROOFED MIXED USE BUILDINGS THAT
 ARE PROFESSIONALLY DESIGNED WITH ALL RESIDENTIAL USES
 LOCATED ABOVE THE FLOODPROOFING DESIGN ELEVATION.
 DESIGNED TO RESIST THE HYDROSTATIC FLOOD FORCES AND A
 FLOOD EMERGENCY OPERATION PLAN.
  
  
 3A) BUILDING PROVISO: COMMENT AS TO SHEET 102-A2.52B
 AND SHEET 156-A4.13A DETAIL # 5. THE PLANS SHOW DOUBLE
 WOOD SLEEPERS AND WOOD DECK. THE PLANS ARE SILENT AS TO
 THE TYPE OF WOOD THE SLEEPERS AND DECK WILL BE MADE.
 HOW THE DECK WILL BE ANCHORED IN HIGH WIND EVENTS.
 SPACING OF THE SLEEPERS, THICKNESS OF DECK MATERIALS,
 SPACING OF MATERIAL AND THE COMPLIANCE WITH 2010 FBC-B
 603.1.1 FIRE RETARDANT TREATED WOODS.
  
 3B-C) COMPLIED.
  
 4A) COMPLIED. THE BUILDING OFFICIAL ROBERT BROWN HAS
 APPROVED THE USE OF FLAME BAR UNDER 104.11.1 ALTERNATE
 MATERIALS AND METHODS OF CONSTRUCTION FOR THE REPLACING
 SHAFT CONSTRUCTION WITH THE EXCEPTION OF WHERE THE
 PLANS SHOW DROPPED CEILINGS IN THE STAIRWELL LANDINGS.
 THIS CONDITION WILL NOT BE PART OF THIS APPROVAL AS
 DISCUSSED IN THE LAST MEETING AND WILL BE FURTHER
 APPROVAL AND EVALUATION BY THE BRISTOL TEAM AND TO BE
 REVIEWED BY THE BUILDING OFFICIAL ROBERT BROWN.
  
 4B) PROVISO: SHAFT WALLS AND CHASE WALLS TO COMPLY WITH
 2010 FBC-B 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN
 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED
 IN ACCORDANCE WITH ASTM E 90.
  
 5) PROVISO: RESPONSE INDICATES THE ROOFING COMPOSITION
 IS STILL PENDING TO BE PROVIDED AT A LATER TIME AS A
 DEFERRED SUBMITTAL. 107.3.4.2. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 6) COMPLIED. STRUCTURAL WALL DETAILS OF POOL, HOT TUB
 AND SPAS ARE TO BE SUBMITTED UNDER THE POOL PERMITS
 17100628 MAIN POOL & HOT TUB
 17100632 MENS JACUZZI
 17100635 WOMENS JACUZZI
 17100637 SPLASH PAD
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-05 Cont ID  
Sent By jwitmer Date 2017-08-05 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2017-07-31 Time 10:55 Sent To  
Notes
2017-07-31 14:34:24BUILDING PLAN REVIEW
 W. P. B. REVISION: 17070136
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO.
 TEL: 561-832-1616
 E-MAIL: [email protected] / ED HANRATTY
  
 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SAT. AUGUST 05/ 2017
 ACTION: DENIED
  
 1) I MISSPOKE IN THE MEETING DATED JULY 26TH IN REGARDS
 TO MECHANICAL CLOSETS IN RATED EXIT PASSAGE WAYS.
 SHEETS 080-A2.01 & 098-A2.51A BOTH SHOW THE MECHANICAL
 CLOSET 103A AND (2) DOORS, 103F & 103G THAT BOTH OPEN
 INTO A 2 HOUR FIRE RATED EXIT PASSAGE WAY. PLEASE
 REVIEW THE 2010 FBC-B SECTIONS 1023.1 AND EXCEPTION
 402.4.6 ALLOWS FOR MECHANICAL ROOMS, ELECTRICAL ROOMS
 BUILDING SERVICE AREAS OPENING DIRECTLY INTO THE EXIT
 PASSAGEWAY ARE ALLOWED!!!
  
 2) PLEASE NOTE WHEN THE (2) REMAINING FLOOD ZONE
 CERTIFICATES ARE REQUIRED. FLOOD ZONE CERTIFICATES/
 SURVEYORS- DEPT. OF AGRICULTURE
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1)COMPLETED. A FLOOD ZONE CERTIFICATE IS REQUIRED AS
 PART OF THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE
 107.3.5.1.1 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. ( 8) FLOOD REQUIREMENTS
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3A) COMMENT AS TO SHEET 102-A2.52B AND SHEET 156-A4.13A
 DETAIL # 5. THE PLANS SHOW DOUBLE WOOD SLEEPERS AND
 WOOD DECK. THE PLANS ARE SILENT AS TO THE TYPE OF WOOD
 THE SLEEPERS AND DECK WILL BE MADE. HOW THE DECK WILL
 BE ANCHORED IN HIGH WIND EVENTS. SPACING OF THE
 SLEEPERS, THICKNESS OF DECK MATERIALS, SPACING OF
 MATERIAL AND THE COMPLIANCE WITH 2010 FBC-B 603.1.1
 FIRE RETARDANT TREATED WOODS.
  
 3B) THERE ARE 2 OTHER CONCERNS ABOUT THE WOOD DECK
 SHOWN ON SHEET 102-A2.52B, BETWEEN GRAPH LINES 9 & 10
 THERE IS A BALCONY DIVIDER AND TO THE RIGHT AT POINT P5
 THE WOOD DECK ENDS, HOW IS THE FINISH DECK ELEVATION
 CHANGE IN REGARDS TO THE CONCRETE DECK TO THE RIGHT?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) WITHOUT THE KNOWN ELEVATION CHANGE FROM THE WOOD
 DECK TO THE FINISH CONCRETE DECK THE PROBLEM MAY OCCUR
 IF THE CONCRETE DECK IS THE SAME HEIGHT THROUGHOUT ALL
 OF THE 2ND FLOOR LEVEL AND THE WOOD DECK BEING 3 ?
 INCHES HIGHER THAN THE CONCRETE DECK, THEN WE WOULD NOT
 MET THE HEIGHT REQUIREMENT FOR THE GUARDRAIL OF 42
 INCHES, PER 2010 1013.2.
  
 4A) THE MEETING HELD ON JULY 26TH/ 2017 IN THE PLANNING
 DEPARTMENT INDICATED PLANS WILL NEED TO BE UPDATED IN
 REGARDS TO THE USE OF 2 HR. RATED SHAFTS VERSES THE USE
 OF FLAMEBAR. THE CURRENT SET OF REVISIONS SUBMITTED
 SHOW ON SHEET 437-M5.01 IN NOTE 1 THE USE OF FLAMEBAR
 ON ALL TOILET & KITCHEN EXHAUST DUCT HORIZONTAL OFFSETS
 TO BE COMPLETED WITH FLAMEBAR DUCT.
 SHEET $38-M5.02 A SIMILAR NOTE. SHEET 440-M504 NOTE 1
 ALL SMOKE EXHAUST, PRESSURIZATION DUCTS AND OUTSIDE AIR
 HORIZONTAL OFFSETS SHALL BE DONE WITH FLAME BAR. PLEASE
 NOTE ONCE THE DISCUSSION WAS STARTED IT APPEARS THE
 PLANS ARE NOT CORRECT, AND FLAMEBAR IS TO BE USED
 TOTALLY AND THE ELIMINATION OF ALL SHAFTS.
 DISCUSSION BETWEEN THE ARCHITECT AND MECHANICAL
 ENGINEER SHOWED TO DATE( 7/18/17 MEETING) THERE HADN?T
 BEEN AN AGREEMENT REACHED.
 IN DISCUSSION OVER E-MAILS THERE HAD BEEN TALK OF A
 FLORIDA DECLARATORY STATEMENT, BUT TO DATE NONE HAS
 BEEN PROVIDED. IN THE 2010 FBC-B IN SECTION 708.2
 PROVIDES WHERE SHAFTS ARE REQUIRED AND THE EXCEPTIONS.
 IF THE DESIGNERS WOULD LIKE THE BUILDING DEPARTMENT TO
 CONSIDER THIS UNDER THE 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 104.11. ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT. THE DESIGNER MUST REQUEST
 IN WRITING THAT THE BUILDING OFFICIAL WOULD REVIEW, AND
 ALLOW THIS AS AN EQUAL TO THE CODE.
  
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT. THE
 PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT THE
 INSTALLATION OF ANY MATERIAL OR TO PROHIBIT
 ANY DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT
 ANY SUCH ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE
 MATERIAL, DESIGN OR METHOD OF
 CONSTRUCTION SHALL BE APPROVED WHERE THE BUILDING
 OFFICIAL FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE INTENT OF THE
 PROVISIONS OF THIS CODE, AND THAT THE MATERIAL, METHOD
 OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT LEAST
 THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE LIFE SAFETY
 SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION
 ANALYSIS AND DESIGN OF BUILDINGS, OR OTHER METHODS
 APPROVED BY THE BUILDING OFFICIAL MAY BE USED.
 THE BUILDING OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO SUBSTANTIATE ANY
 CLAIM MADE REGARDING THE ALTERNATIVE.
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF
 MATERIALS OR ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR
 IN THIS CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS OF
 THIS CODE, OR EVIDENCE THAT A MATERIAL OR METHOD DOES
 NOT CONFORM TO THE REQUIREMENTS OF THIS
 CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR
 ALTERNATIVE MATERIALS OR METHODS, THE BUILDING
 OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS
 EVIDENCE OF COMPLIANCE TO BE MADE AT NO
 EXPENSE TO THE JURISDICTION. TEST METHODS SHALL BE AS
 SPECIFIED IN THIS CODE OR BY OTHER
 RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED
 AND ACCEPTED TEST METHODS, THE
 BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES.
 TESTS SHALL BE PERFORMED BY AN APPROVED
 AGENCY. REPORTS OF SUCH TESTS SHALL BE RETAINED BY THE
 BUILDING OFFICIAL FOR THE PERIOD REQUIRED
 FOR RETENTION OF PUBLIC RECORDS.
  
 4B) THE OTHER ISSUE THAT WILL NEED TO BE CONSIDERED
 WITH THE REMOVAL OF SHAFT WALL CONSTRUCTION,
 (CONSIDERED COMMON AREAS) WILL BE THE REPLACEMENT WALL
 SYSTEM, USUALLY A CHASE WALL SYSTEM POSSIBLY
 WITH DRYWALL ON ONLY ONE SIDE, AND OR MAYBE INSULATION.
 THIS WALL SYSTEM WOULD STILL NEED TO SHOW COMPLIANCE
 WITH THE 2010 FBC-B 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5) DURING THE MEETING HELD ON 7/26/17 THERE WAS
 DISCUSSION BETWEEN THE USE OF THE TYPE OF ROOFING
 INSULATION TO BE USED. THE ARCHITECT SHOWS ON THE PLANS
 THE USE POLYISOCYANURATE BOARD SHEET A4.31 DETAIL # 1.
 THE ROOFING SPEC 07 5400 IS GIVEN. THE SPEC BOOKS ARE
 NOT INCLUDED IN THE PLAN REVIEWS NOR DO WE REVIEW THEM.
 IN THE MEETING IT WAS DISCUSSED POSSIBLY TO GOING AND
 USING LIGHTWEIGHT CONCRETE INSTEAD OF POLYISOCYANURATE
 BOARD.
  
 WHEN YOU REVIEW THE LIGHTWEIGHT SPEC SECTION 03 52 00
 FOR LIGHTWEIGHT CONCRETE ROOF INSULATION WRITER HAS
 MANY OPTIONS AS TO HOW TO WRITE THE SPEC FOR VENTING
 DEPENDING ON LOCATION TYPE OF DECK CONCRETE VERSES
 STEEL DECK WITH VENTING OF DECK OR NON-VENTED STEEL
 DECKING TO ALIEVE THE MOISTURE WITHIN THE LIGHTWEIGHT
 CONCRETE.
  
 I COULD NOT FIND A ROOFING SPEC LISTED FOR 07 5400 BUT
 DID FIND A ROOF SPEC 07 5300 FOR SINGLE PLY MEMBRANE
 ROOFING, THE COMPANIES LISTED ARE CARLISLE, FLEX, GAF,
 SIKA SARNAFIL, AND VERSICO EACH WRITING THEIR OWN
 REQUIREMENTS FOR ROOF INSULATION AND INSTALLATION OF
 SYSTEMS AND VENTING REQUIREMENTS.
  
 6A) WITHIN THE MEETING HELD ON 7/26/2017 THERE WAS
 DISCUSSION ON THE POOL AND REQUIREMENT FOR A SEPARATE
 BUILDING PERMIT. IT WAS INDICATED THERE WILL BE A
 PREFABRICATED WALL SYSTEM WITH POOL LINER.
 THIS REVISION SHOWS DETAILS FOR THE MEMBRANE LINER,
 SHEET 746-W5.1_04:
 DETAIL 01 MAIN POOL TYPICAL EDGE
 DETAIL 02 MAIN POOL STAIRS
 DETAIL 03 MAIN POOL STRUCTURAL SYSTEM / HOT SPA WALL &
 EDGE
 THESE AND OTHER DETAILS SHOW THE PREFABRICATED WALL AND
 STRUCTURAL BRACING/ STRUCTURAL WALL COMPONENT POOL WALL
 SYSTEM WILL BE UNDER A SEPARATE POOL (BUILDING PERMIT)
 OR WILL SUFFOLK CONSTRUCTION BE SUBMITTING THESE
 DETAILS UNDER A FUTURE REVISION? 107.2.1.3. ADDITIONAL
 INFORMATION REQUIRED?
  
 6B) SHEET 746-W5-104 DETAIL 03, IN THE SUBMITTED DETAIL
 IT WOULD APPEAR THERE WOULD BE GREATER WATER PRESSURE
 ON THE POOL SIDE WALL SINCE IT IS DEEPER THAN THE SPA,
 SHOULD THE LATERAL BRACING BE TURNED THE OPPOSITE WAY
 TO HELPS SUPPORT, AND BRACE THE POOL WALL. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2018-02-16 Cont ID  
Sent By jleahy Date 2018-02-16 Time 12:37 Rev Time 0.00
Received By jleahy Date 2018-02-16 Time 12:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-01-16 Cont ID  
Sent By jleahy Date 2018-01-16 Time 15:55 Rev Time 0.00
Received By jleahy Date 2018-01-16 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-04 Cont ID  
Sent By jleahy Date 2018-01-04 Time 16:04 Rev Time 0.00
Received By jleahy Date 2018-01-03 Time 14:15 Sent To  
Notes
2018-01-04 16:08:26FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NARRATIVE STATES THIS IS FOR REVISION #4. THERE IS ALSO
 REVISION #5 AND #11 ON SOME PAGES?
 SOME OF THE REVISION IS CLOUDED AND ALOT OF IS NOT.
 THERE ARE OTHER #4 REVISIONS ON THE PAGES THAT ARE NOT
 NOTED IN THE NARRATIVE.
  
 PAGE MISSING E2.02P
 NARRATIVES MISSING FOR E2.0P2, E6.03, E6.04, E6.05,
 E6.06
  
 ALL CHANGES NEED TO BE CLOUDED FOR REVIEW.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-03 Cont ID  
Sent By jleahy Date 2017-08-03 Time 18:37 Rev Time 0.00
Received By jleahy Date 2017-08-01 Time 15:03 Sent To  
Notes
2017-08-01 16:01:51FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FOR THE REVISION I WAS MISSING PAGES E6.12, E6.13,
 E7.02, E7.05, E7.07 FROM WHAT THE NARITIVE SHOWS IN THE
 PAGE SCHEDULE. REVISION WAS GENERALLY
 OK FOR THE REVISED PAGES, BUT DID NOTE ALOT OF
 DISCREPANCIES IN PANEL SCHEDULES AND CIRCUITRY, MISSING
 CIRCUIT NUMBERS THAT WAS NOT PART OF THE REVISION.
  
  
 FOUND GENERAL DISCREPANCIES BETWEEN PANEL SCHEDULES AND
 CIRCUITS IN UNITS. THE NOTES SHOW ARC FAULT WHEN
 CIRCUITS SHOULD BE GFCI PROTECTED.
 MOST BATHROOMS SHOW AN OUTLET IN THE MIDDLE OF THE
 BATHROOM COUNTER ON SAME CIRCUIT AS GFIS BUT DOES NOT
 STATE WHAT IT IS FOR AND IT IS NOT SHOWN
 TO BE GFCI PROTECTED, ANOTHER NOTE STATES TO PLACE
 SMOKE ALARMS ON KITCHEN CIRCUIT BUT ARE SHOWN ON
 BEDROOM CIRCUIT, KITCHEN COUNTERS IN SOME UNITS ARE
 LACKING THE REQUIRED OUTLET SPACING REQUIRED BY CODE.
  
 ONCE I CATCH UP ON MY REGULAR WORK I WILL LOOK THE
 REVISION OVER AGAIN.
  
 JAKE LEAHY
  
 .
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-02-06 Cont ID  
Sent By pleduc Date 2018-02-06 Time   Rev Time 0.00
Received By pleduc Date 2018-02-06 Time 15:43 Sent To  
Notes
2018-02-06 15:45:41PLEASE NOTE ALL PROVIO COMMENTS WITH PREVIOUS
 SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-12 Cont ID  
Sent By pleduc Date 2018-01-12 Time   Rev Time 0.00
Received By pleduc Date 2018-01-08 Time 09:32 Sent To  
Notes
2018-01-12 14:10:072ND REVIEW COMMENTS
  
  
 1) SHEET FP P 1 & P 2 - THERE APPEARS TO BE
 INSUFFICIENT FIRE SPRINKLER COVERAGE OVER THE NEW
 RESIDENT STORAGE AREAS.
  
 PROVISO:
  
 COMMENT PROVIDED - WILL REVIEW WITH SPRINKLER DRAWINGS
 AND INSPECTIONS.
  
  
  
 2) SHEET FP 2.01 - THERE APPEARS TO BE NO FIRE
 SPRINKLER COVERAGE OVER THE WOOD DECK FLOORING AREA ON
 THE LOBBY SHEETS.
  
 PROVISO:
  
 COMMENT PROVIDED THAT PRODUCT SHEETS WILL BE PROVIDED -
 WILL REVIEW DRAWINGS, AMTERIALS AND INSPECTIONS.
  
  
  
  
 3) SHEET 156 4A 13A - INDICATES THE WOOD DECKING WITH
 SUBFLOORING WITH A NOTE CALL-OUT "WOOD FINISH FLOOR,
 LANSCAPE DWG" BUT NO DRAWING REFERENCE SHEET.
  
 PROVISO:
  
 COMMENT PROVIDED THAT PRODUCT SHEETS WILL BE PROVIDED -
 WILL REVIEW DRAWINGS, AMTERIALS AND INSPECTIONS.
  
  
  
  
 4) SHEETS FP P1 & P2 - THERE ARE INTERANL PRIVATE
 GARAGES INDICATED WITH THE PARKING GARAGE AREAS. THERE
 ARE NO INDICATIONS THAT WHEN THE INTERANL GARAGE DOOR
 IS OPEN, THAT FIRE SPRINKLER PROTECTION WILL BE
 PROVIDED FOR THE POSSIBLE OBSTRUCTION.
  
  
 PROVISO:
  
 COMMENT PROVIDED THAT PRODUCT SHEETS WILL BE PROVIDED -
 WILL REVIEW DRAWINGS, AMTERIALS AND INSPECTIONS.
  
  
  
  
 5) FIRE SHARES IDENTICAL CONCERNS REGARDING THE FIRE
 DAMPERS, GENERATOR EXHAUST. SMOKE CONTROL SYSTEMS BUT
 WILL NOT BE DUPLICATED THOSE QUESTIONS.
  
 COMMENTS ARE BEING ADDRESSED THRU MECHANICAL
  
  
  
 6) N/A
  
  
 7) N/A
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By pleduc Date 2017-08-09 Time   Rev Time 0.00
Received By pleduc Date 2017-07-26 Time 09:09 Sent To  
Notes
2017-08-09 10:56:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP P 1 & P 2 - THERE APPEARS TO BE
 INSUFFICIENT FIRE SPRINKLER COVERAGE OVER THE NEW
 RESIDENT STORAGE AREAS.
  
 THIS WAS DISCUSSED AT THE MOST RECENT MEETING IN JULY.
 IT WAS DISCUSSED THAT A FENCE TYPE MATERIAL WILL BE
 PLACED OVER THE THE UNITS FOR SECURITY AND SPRINKLER
 COVERAGE WOULD NEED TO NE MODIFIED.
  
 PLEASE PROVIDE FOR PROPER FIRE SPRINKLER COVERAGE OVER
 THESE AREAS.
  
  
  
 2) SHEET FP 2.01 - THERE APPEARS TO BE NO FIRE
 SPRINKLER COVERAGE OVER THE WOOD DECK FLOORING AREA ON
 THE LOBBY SHEETS.
  
 PER NFPA 1, CHAPTER 13 FIRE PROTECTION SYSTEMS
  
 13.3.2.6* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES,
 BALCONIES, DECKS, OR SIMILAR PROJECTIONS. IN BUILDINGS
 PROTECTED THROUGHOUT BY AUTOMATIC SPRINKLERS IN
 ACCORDANCE WITH NFPA 13, AUTOMATIC SPRINKLER PROTECTION
 SHALL BE PROVIDED FOR
 THE EXTERIOR SPACES IN ACCORDANCE WITH 13.3.2.6.
  
 13.3.2.6.1 UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR
 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, BALCONIES,
 DECKS, OR SIMILAR PROJECTIONS EXCEEDING 4 FT (1.2 M) IN
 WIDTH. [13:8.15.7.1]
 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE CANOPIES, ROOFS, PORTE-COCHERES, BALCONIES,
 DECKS, OR SIMILAR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT?TREATED WOOD AS DEFINED IN NFPA 703,
 STANDARD FOR FIRE RETARDANT?TREATED WOOD AND FIRE-
 RETARDANT COATINGS FOR BUILDING MATERIALS.
 [13:8.15.7.2]
  
 PLEASE PROVIDE THE MATERIAL SPECIFICATIONS OF ALL WOOD
 ELEMENTS OF THE FLOORING DESING IN COMPLIANCE WITH THE
 ABOVE NOTED CODE.
  
  
  
  
 3) SHEET 156 4A 13A - INDICATES THE WOOD DECKING WITH
 SUBFLOORING WITH A NOTE CALL-OUT "WOOD FINISH FLOOR,
 LANSCAPE DWG" BUT NO DRAWING REFERENCE SHEET.
  
 PLEASE PROVIDE.
  
  
  
 4) SHEETS FP P1 & P2 - THERE ARE INTERANL PRIVATE
 GARAGES INDICATED WITH THE PARKING GARAGE AREAS. THERE
 ARE NO INDICATIONS THAT WHEN THE INTERANL GARAGE DOOR
 IS OPEN, THAT FIRE SPRINKLER PROTECTION WILL BE
 PROVIDED FOR THE POSSIBLE OBSTRUCTION.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE NOTE.
  
  
  
 5) FIRE SHARES IDENTICAL CONCERNS REGARDING THE FIRE
 DAMPERS, GENERATOR EXHAUST. SMOKE CONTROL SYSTEMS BUT
 WILL NOT BE DUPLICATED THOSE QUESTIONS.
  
 FIRE WILL REVIEW THE RE-SUBMITTAL INFORMATION TO
 MECHANICAL AND PROVIDE APPLICABLE COMMENTS IF
 NECASSARY.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 11:35 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 11:34 Sent To  
Notes
2018-01-18 11:36:21PROVISO:
  
 GAS COMMENTS:
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR GAS RANGE AND
 DRYER IN THE INDIVIDUAL UNITS. PER WPB AMEND TO FBC
 107.2.1 TO BE ON JOB SITE FOR INSPECTION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-03 Cont ID  
Sent By gjohnson Date 2017-08-03 Time 10:24 Rev Time 0.00
Received By gjohnson Date 2017-08-03 Time 10:18 Sent To  
Notes
2017-08-03 10:24:511ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. PLEASE PROVIDE A REVISED GAS ISO. PER WPB AMEND TO
 FBC 107.2.1
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR GAS RANGE AND
 DRYER IN THE INDIVIDUAL UNITS. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-16 Cont ID  
Sent By lmarchan Date 2018-02-16 Time 15:28 Rev Time 0.00
Received By lmarchan Date 2018-02-02 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 11:36 Rev Time 0.00
Received By gjohnson Date 2017-12-22 Time 10:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-11 Cont ID  
Sent By lmarchan Date 2017-08-11 Time 11:15 Rev Time 0.00
Received By lmarchan Date 2017-07-21 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-02-14 Cont ID  
Sent By ccole Date 2018-02-14 Time 09:18 Rev Time 0.00
Received By ccole Date 2018-02-13 Time 09:18 Sent To  
Notes
2018-02-14 09:26:18MECHANICAL PROVISOS
 THE BRISTOL
 REVISON #17070136
 2/14/2018
  
 THE MECHANICAL REVISION IS APPROVED WITH THE FOLLOWING
 LIST OF PROVISOS:
  
 1) PROVIDE THE BACK PRESSURE CALCULATIONS FOR THE
 GENERATOR EXHAUST PIPE, AND A REVISED DRAWING OF THE
 EXHAUST PIPE THAT SHOWS THE SEGMENTED LENGTHS OF THE
 PIPE AND THE TOTAL LENGTH OF THE RUN FROM THE GENERATOR
 TO THE OUTLET AT THE EXTERIOR WALL.
  
 2) PROVIDE ELECTRONICALLY SIGNED AND SEALED DRAWINGS
 AND DETAILS FOR THE FIRE-RATED EXHAUST PIPE ENCLOSURE.
  
 3) THE REVISED ENERGYGAUGE COMPLIANCE REPORT MUST BE
 ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO
 PREPARED THE CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-08 Cont ID  
Sent By ccole Date 2018-01-08 Time 16:46 Rev Time 0.00
Received By ccole Date 2018-01-08 Time 16:46 Sent To  
Notes
2018-01-08 17:21:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070136
 1/8/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT IS ACKNOWLEDGED THAT THE USE OF FLAMEBAR DUCTWORK
 TO REPLACE FIRE-RATED SHAFTS IN THE BUILDING HAS BEEN
 GRANTED APPROVAL UNDER SECTION 104.11 FBC ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND
 EQUIPMENT BY ROBERT BROWN WPB BUILDING OFFICIAL. THE
 APPROVAL, HOWEVER, DOES NOT INCLUDE THE FLAMEBAR DUCTS,
 OR ANY OTHER DUCTS, THAT ARE PENETRATING THE INTERIOR
 EXIT STAIRWELL SHAFTS IN THE NORTH AND SOUTH CORES.
 THIS CONDITION IS CURRENTLY BEING EVALUATED BY THE
 BRISTOL DESIGN TEAM AND IS EXCLUDED FROM THIS REVIEW
 UNTIL A LATER DATE.
  
 2) COMMENT #2 FROM THE 1ST HAS NOT BEEN COMPLETELY
 ADDRESSED. I AM UNABLE TO FIND THE SE-1 & SE-2
 IDENTIFICATION LABELS ON SHEETS M2.01, M2.02, & M2.03.
 PLEASE SHOW THE LOCATIONS ON THE PLANS.
  
 3) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. PER THE
 RESPONSE NARRATIVE THE REQUESTED INFORMATION AND
 SPECIFICATIONS FOR THE GENERATOR AND EXHAUST FLUE HAVE
 BEEN PROVIDED, HOWEVER NO DOCUMENTS HAVE BEEN UPLOADED
 FOR REVIEW.
  
 4) COMMENT #4 FROM THE 1ST REVIEW HAS NOT BEEN COMPLETE
 ADDRESSED. IT APPEARS THAT THE REVISED ENERGY
 COMPLIANCE REPORT DOES NOT INCLUDE THE DATA FOR THE NEW
 PARKING GARAGE HEAT PUMPS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By ccole Date 2017-08-02 Time 17:25 Rev Time 0.00
Received By ccole Date 2017-08-01 Time 17:45 Sent To  
Notes
2017-08-02 17:25:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070136
 8/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE USE OF FLAMEBAR DUCT TO CREATE CONTINUOUS
 VERTICAL AND HORIZONTAL FIRE-RATED SHAFTS FOR SMOKE
 CONTROL AND TOILET AND KITCHEN EXHAUST SYSTEMS WILL
 REQUIRE AN ALTERNATE MATERIALS AND METHOD APPROVAL BY
 THE BUILDING OFFICIAL. THERE ARE NO PROVISIONS IN
 EITHER THE FLORIDA BUILDING CODE- 2010, OR THE FIFTH
 EDITION FLORIDA BUILDING CODE- 2014 THAT ALLOW FOR THE
 USE OF FLAMEBAR DUCT IN THESE APPLICATIONS- SEE
 SECTIONS 708 (2010) OR 713 (2014) SHAFT ENCLOSURES.
 ADDITIONALLY THE USE OF FLAMEBAR DUCT FOR THE SMOKE
 CONTROL SYSTEMS IS NOT SPECIFIED IN THE SUBMITTED
 RATIONAL ANALYSIS REPORT FOR THE THE BRISTOL BY SLS
 FIRE PROTECTION ENGINEERS. PLEASE SEE PAGE 20 OF THE
 REPORT WHICH STATES SPECIFICALLY THAT THE DUCTS WILL BE
 ENCLOSED IN 2-HR. FIRE-RESISTANCE RATED CONSTRUCTION
 AND ARE ONLY REQUIRED TO BE RATED FOR EXPOSURE TO
 OUTSIDE AIR TEMPERATURES. THE FBC-10 AND 14 EDITIONS DO
 ALLOW FOR AN APPROVAL TO USE THE DUCTS UNDER SECTION
 104.11 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT. IT IS THE TASK OF THE
 DESIGN PROFESSIONAL OF RECORD HOWEVER TO PROVIDE
 SUPPORTING EVIDENCE, REPORTS, AND TESTING DATA AND
 SUBMIT A REQUEST TO THE BUILDING OFFICIAL FOR AN
 APPROVAL. ADDITIONALLY, PLEASE SEE SECTION 703 FIRE
 RESISTANCE RATINGS AND FIRE TESTS FOR ASTM AND UL
 LISTING AND ASSEMBLY INFORMATION.
  
 2) IT APPEARS THAT ALL THE UPLOADED REVISED SHEETS FROM
 M2.01 TO M2.24 ARE MISSING IDENTIFICATION TAGS TO
 INDICATE THE LOCATIONS OF THE SMOKE EXHAUST SHAFTS SE-1
 & SE-2. PLEASE PROVIDE THE TAGS ON ALL RELEVANT SHEETS
 TO SHOW THE LOCATIONS.
  
 3) SHEETS M2.01 & M2.01: CONCERNING THE RELOCATED
 EXHAUST FLUE FOR THE DIESEL GENERATOR PLEASE PROVIDE A)
 THE TOTAL RUN LENGTH OF THE FLUE ON THE PLANS. B)
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR, FLUE,
 AND THIMBLE. C) FLUE SIZING SCHEDULE FROM THE
 MANUFACTURER. D) UL LISTING NUMBER AND ASSEMBLY DETAILS
 FOR THE FIRE-RATED FLUE ENCLOSURE.
  
 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMPS AND AND REVISE THE ENERGY CALCULATIONS
 TO INCLUDE THE SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 5) M2.01: THERE APPEARS TO BE MISSING FIRE DAMPERS
 WHERE THE MAIN MANICURE EXHAUST DUCT IS PENETRATING THE
 FIRE-RATED CORRIDOR WALL, AND WHERE THE NEW O/A DUCT IS
 PENETRATING THE RATED DOMESTIC WATER ROOM, POOL
 EQUIPMENT ROOM, AND CORRIDOR WALLS- SECTION 607.5.2.
  
 6) M2.02, SOUTH CORE: THERE APPEARS TO BE FIRE DAMPERS
 MISSING WHERE THE 10X10" DUCT IS PENETRATING THE
 FIRE-RATED JANITOR, FIRE VESTIBULE, AND ELEVATOR LOBBY
 WALLS.
  
 7) M2.02, SOUTH CORE: THERE APPEARS TO BE FIRE DAMPERS
 MISSING IN THE MEN?S AND WOMEN?S SPA WHERE DUCTS FROM
 THE NEW HEAT PUMPS AND OTHER SYSTEMS ARE PENETRATING
 THE FIRE-RATED MECHANICAL CLOSET WALLS.
  
 8) M2.05: MISSING FIRE DAMPERS AT DUCTS PENETRATING THE
 FIRE-RATED SMOKE EXHAUST SHAFTS IN THE NORTH AND SOUTH
 CORES. IF USING FLAMEBAR DUCT PLEASE LABEL THE DUCTS
 ACCORDINGLY. THE DAMPERS MAY NOT BE REQUIRED PENDING AN
 ALTERNATE APPROVAL BY THE BUILDING OFFICIAL.
  
 9) M2.0P1: THERE APPEAR TO BE TWO O/A DUCTS CONNECTING
 TO THE 1-TON HP IN THE UNISEX BATHROOM- THE DUCT
 RUNNING SOUTH APPEARS TO BE AN ERROR.
  
 10) M2.0P1: P-129 IS IDENTIFIED AS PACKING STATION ON
 THE PLAN SHEET AND VALET STATION ON THE LIFE SAFETY
 PLAN A0.31. PLEASE NOTE THAT OCCUPIED SPACES REQUIRE
 O/A AND NONE IS SHOWN IN THE ROOM ON THE MECHANICAL
 PLAN- SECTION 402.
  
 11) M2.0P1: A FIRE DAMPER IS REQUIRED FOR THE EXHAUST
 OUTLET OPENING IN THE NEW STORAGE ROOM IN THE SOUTH
 CORE.
  
 12) M.17- M.25: MISSING FIRE DAMPERS AT DUCTS
 PENETRATING THE FIRE-RATED SMOKE EXHAUST SHAFTS IN THE
 NORTH AND SOUTH CORES. IF USING FLAMEBAR DUCT PLEASE
 LABEL THE DUCTS ACCORDINGLY. THE DAMPERS MAY NOT BE
 REQUIRED PENDING AN ALTERNATE APPROVAL BY THE BUILDING
 OFFICIAL.
  
 13) M2.53A- M2.61B: PLEASE NOTE THESE ADVISORIES
 COMMENTS FOR THE RESIDENTIAL SUITES: A) DRYER EXHAUST
 DUCTS SHALL NOT RUN THROUGH PLENUMS- SECTION 504.4. B)
 AC CLOSETS SHALL BE CONSIDERED PLENUM CHAMBERS AND
 SHALL BE CONSTRUCTED WITH NON-COMBUSTIBLE MATERIALS
 INCLUDING THE CLOSET DOOR- SECTION C403.2.7.2 FBC-14
 ENERGY CONSERVATION. C) MATERIALS WITHIN PLENUMS.
 EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH
 602.2.1.5, MATERIALS WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING
 A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 OR UL 723. D) COMMERCIAL
 COOKING APPLIANCES AND GREASE EXHAUST SYSTEMS ARE
 PROHIBITED- SECTION 623.2 FBC-14 FUEL GAS, AND SECTION
 506 INCLUDING ALL SUB-SECTIONS FBC-14 MECHANICAL.
  
 14) M5.07: THE NEW CONTROL DIAGRAM FOR THE PRIVATE
 GARAGE HP UNITS INDICATES O/A WILL BE PROVIDED TO THE
 SYSTEMS, HOWEVER THE MECHANICAL PLANS DO NOT INDICATE
 ANY O/A BEING PROVIDED- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By gjohnson Date 2018-01-18 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2018-01-18 Time 11:22 Sent To  
Notes
2018-01-18 11:30:46POOLS, SPAS, HOT TUBS AND SPLASH PAD UNDER SEPERATE
 PERMITS 17100637,17100635,17100632,17100628
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By gjohnson Date 2017-08-11 Time 08:51 Rev Time 0.00
Received By gjohnson Date 2017-07-27 Time 18:01 Sent To  
Notes
2017-08-03 10:17:391ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P2-0P1, P2-0P2, P2-01, P2-02, AND P2-03 PLEASE
 LABEL ALL STACKS TO MATCH UP WITH ISO DRAWINGS, TO
 INCLUDE WATER SANITARY AND GAS. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. P5-03C, D, E, AND P5-23 PLEASE SHOW THE LEVELS
 ON ISOMETRIC DRAWINGS, AND INDICATE LOCATION ON THE
 ISO. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE SHOW COMPLIANCE IN ALL BATHROOMS IN COMMON
 AREAS WITH FBC ACC
 A) 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 B) 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 C) 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES
 (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT
 BE LOCATED BEHIND GRAB BARS
 D) 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 E) 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 F) 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 G) 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4. PLEASE SHOW COMPLIANCE IN NEW COMMON BATHROOMS WITH
 FBC ACC
  
 A) 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 B) 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 C) LAVATORIES 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5. PLEASE REMOVE OLD REVISION CLOUDS FROM ALL SHEETS IT
 HAS BEEN VERY DIFFICULT TO LOCATE THE CHANGES ON THIS
 REVISION, HERE IS A LIST OF PLAN PAGES THAT I COULD NOT
 SEE ANY CHANGES FROM THE APPROVED PLAN PAGE: P2.19,
 P1.25, P2.26, P2.53A, P2.54A, P2.54C, P2.54G, P2.56B,
 P2.57B, P5.01, P5.02, P5.03, P5.03B. PER WPB AMEND TO
 FBC 107.2.1
  
 6. AAV ARE NOT PERMITTED BELOW 4TH BRANCH DOWN FROM
 ROOF NOT STILL ON FLOOR PLANS PLEASE REMOVE SHT.
 P2.55A, P2.55C PLEASE CHECK ALL FLOOR PLAN SHEETS. PER
 FBC PL 918.3.1/ WPB AMEND TO FBC 107.2.1
  
 7. SHT. P5.23 IS MISSING ISO #2 FROM APPROVED PLAN
 SHEET. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P5.03C PLEASE PROVIDE ISO THAT SHOWS SS S7, S8,
 AND S9 CONNECTING TO ONE SINGLE STACK AND SHOW THE
 LEVEL. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P2.01 THE SOIL STACK ON THE BACK SIDE OF
 ELEVATOR #1 SHOWS A 4? PIPE SHT. P2.0P1 SHOWS A 6? AT
 SAME LOCATION PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 10. ON THE RISER AND ISO DRAWINGS THERE ARE VENTS THAT
 END AND IT IS NOT CLEAR WHERE THEY CONTINUE OR
 TERMINATE PLEASE PROVIDE A TAG OR A WAY OF DETERMINING
 WHERE THEY CONTINUE OR TERMINATE. PER WPB AMEND TO FBC
 107.2.1
  
 11. SHT. P5.03B S12 LEVEL 25 THE ISO DOES NOT MATCH THE
 FLOOR PLAN ON SHT. P2.61B PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 12. PROVIDE ISO FOR NEW BATHROOMS ON LEVEL 1. PER WPB
 AMEND TO FBC 107.2.1
  
 13. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 LAUNDRY TRENCH DRAIN. PER WPB AMEND TO FBC 107.2.1
  
 14. PLEASE PROVIDE A REVISED CONDENSATE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
  
 POOL COMMENTS :
  
 1. SHT. W1-1.02 THE NOTE ON GUTTER DRAIN SHOULD BE 20
 WITH THE ADDITIONAL DRAIN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 2. SHT. W1-2.02 SHOW THE PIPE SIZE FOR THE NEW FLOOR
 HYDROTHERAPY JETS ALSO CHECK THE HIS AND HERS SPAS FOR
 PIPE SIZES. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE CHLORINE
 GENERATOR AND SACRIFICIAL ANODE AND STEAM UNIT. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE PIPING DIAGRAM AND DETAILS FOR STEAM
 SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. W1-2.01, W1-4.01, W1-5.01, W5-1.05 THE REVISED
 PAGES APPEAR TO BE THE SAME AS APPROVED PAGES PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-02-16 Cont ID  
Sent By lmarchan Date 2018-02-16 Time 15:28 Rev Time 0.00
Received By lmarchan Date 2018-02-16 Time 15:28 Sent To  
Notes
2018-01-18 11:40:191/18/18 DIG SIG ON PLUMB SHTS. IS OK/GPJ
2017-08-11 09:03:028/11/17 DIG SIG ON PLUMB AND POOL PLAN PAGES HAS BEEN
 VERIFIED AS GOOD/GPJ
2017-08-02 17:45:12MECH DIG/SIGS VERIFIED- CCOLE- 8/2/17

Review Stop Z ZONING
Rev No 3 Status P Date 2018-02-13 Cont ID  
Sent By jroach Date 2018-02-13 Time 09:42 Rev Time 0.00
Received By jroach Date 2018-02-13 Time 09:42 Sent To  
Notes
2018-02-13 10:11:57ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.13.2018
 PERMIT NO.: 15111020
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE PROPOSED PLANTING WITHIN THE CITY'S RIGHT-OF-WAY
 SHALL BE SUBJECT TO THE REVIEW AND APPROVAL BY THE
 CITY'S ENGINEERING SERVICES DEPARTMENT.
  
 2. PRIOR TO APPROVAL OF THE FINAL LANDSCAPE INSPECTION,
 LANDSCAPE MATERIAL SHALL BE PROVIDED AROUND THE
 UTILITIES (BACKFLOW PREVENTERS, DOUBLE CHECK DETECTORS,
 ETC.) AT THE SOUTH END OF THE PROPERTY, ALONG SOUTH
 FLAGLER DRIVE, TO MINIMIZE THEIR VISUAL IMPACT. SUCH
 MATERIAL MAY CONSIST OF SHRUBS AND/OR GROUNDCOVER USED
 TO DISGUISE THE UTILITIES. ADDITIONALLY, THE UTILITIES
 SHALL BE PAINTED IN A COLOR THAT MINIMIZES THEIR
 VISIBILITY.
  
 3. ALL PHOTOMETRICS FOR SITE LIGHTING SHALL BE
 SUBMITTED AS A SEPARATE REVISION, AND SHALL INDICATE
 THAT LEVELS DO NOT EXCEED 0.5 FOOTCANDLES WHEN MEASURED
 AT THE PROPERTY LINE.
  
 PLEASE NOTE THAT THE BRISTOL RESIDENTIAL PLANNED
 DEVELOPMENT (RPD) SHALL CONTINUE TO ADDRESS ALL
 DEVELOPMENT ORDER CONDITIONS IMPOSED BY RESOLUTION NO.
 140-14, APPROVED ON 07.07.2014, AND THE MINOR AMENDMENT
 (PB CASE NO. 1635G) APPROVED ON 09.09.2015. SUCH
 CONDITIONS SHALL BE SATISFIED IN ACCORDANCE WITH THE
 TIMEFRAMES SPECIFIED THEREIN.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-01-04 Cont ID  
Sent By JR Date 2018-01-04 Time 11:26 Rev Time 0.00
Received By jroach Date 2018-01-04 Time 11:26 Sent To  
Notes
2018-01-04 11:27:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.04.2018
 PERMIT NO.: 17070136 (REVISION TO PERMIT #15111020)
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. DATA TABLE SHALL BE PROVIDED INDICATING AT LEAST THE
 FOLLOWING:
  
  A. EXISTING/PROPOSED LAND USE AND ZONING.
  B. TOTAL ACRES OF THE PROJECT.
  C. TOTAL GROSS BUILDING SQUARE FOOTAGE.
  D. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
  E. DENSITY AND NUMBER OF DWELLING UNITS (RESIDENTIAL).
  F. PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC.)
  G. FLOOR AREA RATIO (FAR).
  
 2. PHOTOMETRIC LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES
 WHEN MEASURED AT THE PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-11 Cont ID  
Sent By jroach Date 2017-08-11 Time 11:12 Rev Time 0.00
Received By jroach Date 2017-08-11 Time 10:23 Sent To  
Notes
2017-08-11 11:14:14ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.10.2017
 PERMIT NO.: 17070136 (REVISION TO PERMIT #15111020)
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. DATA TABLE SHALL BE PROVIDED INDICATING AT LEAST THE
 FOLLOWING:
  
  A. EXISTING/PROPOSED LAND USE AND ZONING.
  B. TOTAL ACRES OF THE PROJECT.
  C. TOTAL GROSS BUILDING SQUARE FOOTAGE.
  D. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
  E. DENSITY AND NUMBER OF DWELLING UNITS (RESIDENTIAL).
  F. PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC.)
  G. FLOOR AREA RATIO (FAR).
  
 2. PHOTOMETRIC LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES
 WHEN MEASURED AT THE PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved