Plan Review Details - Permit 17070109
Plan Review Stops For Permit 17070109
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By jwitmer Date 2017-08-07 Time 06:32 Rev Time 0.00
Received By jwitmer Date 2017-08-07 Time 05:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jwitmer Date 2017-07-12 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2017-07-12 Time 06:01 Sent To  
Notes
2017-07-12 06:31:072014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070109
 ADD: 651 OKEECHOBEE BLVD. SUITE: 601
 CONT: ENTRUSTED
 TEL: 561-966-0765
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 12/ 2017
 ACTION: DENIED
  
 1) THE SUBMITTED FLOOR PLANS IS JUST THAT IT DOES NOT
 INDICATE THE WORK THAT IS BEING DONE UNDER THIS PERMIT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 2) CERTIFICATION BY CONTRACTOR. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DRAWN THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN. 107.3.4.3 CERTIFICATION BY CONTRACTOR.
  
 3) THE VALUE IS LOW FOR THE PROJECT, PERMIT VALUE
 STATED IS $20,151.79. THE CONTRACT VALUE THE SAME
 AMOUNT BUT THE OVERALL VALUE WITH O&P, TAX, OVERHEAD &
 PROFIT IS $28,955.00 IN VALUE.
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) THE PERMIT APPLICATION INDICATES FLOOR REPAIRS BUT
 IN THE CONTRACT THERE IS A LINE ITEMS FOR REMOVING THE
 EXISTING FLOORS AND INSTALLATION OF NEW UNDERLAYMENT
 AND FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-08-04 Cont ID  
Sent By jpearson Date 2017-08-04 Time 10:00 Rev Time 0.00
Received By jpearson Date 2017-08-04 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By jpearson Date 2017-07-17 Time 12:31 Rev Time 0.00
Received By jpearson Date 2017-07-17 Time 12:31 Sent To  
Notes
2017-07-17 12:32:16CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. IF THERE IS NOT ANY ELECTRICAL
 WORK INCLUDED WITH THIS PERMIT, STATE THAT ON PLAN. FS
 471.003(2)(H); 471.025; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-03 Cont ID  
Sent By pleduc Date 2017-08-03 Time   Rev Time 0.00
Received By pleduc Date 2017-08-02 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-07 Cont ID  
Sent By pleduc Date 2017-07-07 Time   Rev Time 0.00
Received By pleduc Date 2017-07-07 Time 13:56 Sent To  
Notes
2017-07-07 15:06:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE WAS NO MANUFACTURES SPECIFICATION SHEETS FOR
 THE FLOORING OR UNDERLAYMENT PROVIDED WITH THIS
 SUBMITAL THAT SHOWS COMPLIANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 PER NFPA 101, CHAPTER 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS CORRIDORS AND SPACES NOT SEPARATED FROM
 THEM BY WALLS COMPLYING WITH 30.3.6 SHALL BE NOT LESS
 THAN CLASS II.
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR 10.2.7.2, AS APPLICABLE.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE,
 SHALL HAVE A MINIMUM CRITICAL RADIANT FLUX OF 0.1
 W/CM2.
 10.2.7.3* INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH 10.2.7.4, BASED ON TEST RESULTS FROM
 NFPA 253, STANDARD METHOD OF TEST FOR CRITICAL RADIANT
 FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT HEAT
 ENERGY SOURCE, OR ASTM E 648, STANDARD TEST METHOD FOR
 CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A
 RADIANT HEAT ENERGY SOURCE.
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED AS
 FOLLOWS IN ACCORDANCE WITH THEIR CRITICAL RADIANT FLUX
 VALUES:
 (1) CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
 (2) CLASS II INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.22 W/CM2 BUT LESS THAN 0.45 W/CM2, AS DETERMINED BY
 THE TEST DESCRIBED IN 10.2.7.3.
  
  
 PLEASE PROVIDE THE SPECIFICATION SHEETS THAT INDICATE
 COMPLIANCE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-17 Cont ID  
Sent By gjohnson Date 2017-08-17 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2017-07-31 Time 13:30 Sent To  
Notes
2017-08-01 13:30:13B09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-17 Cont ID  
Sent By gjohnson Date 2017-07-17 Time 14:45 Rev Time 0.00
Received By gjohnson Date 2017-07-05 Time 14:35 Sent To  
Notes
2017-07-06 14:35:33B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-08-11 Cont ID  
Sent By ccole Date 2017-08-11 Time 11:02 Rev Time 0.00
Received By ccole Date 2017-08-11 Time 10:53 Sent To P
Notes
2017-08-11 11:07:43SEPARATE PERMIT AND PLANS REQUIRED FOR HVAC
 ALTERATIONS.
 CCOLE- 8/11/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 14:16 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 12:54 Sent To  
Notes
2017-07-14 14:15:251ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070109
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE
 REVIEW THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2) PLEASE PROVIDE A MECHANICAL PLAN IN THE FORMAT NOTED
 ABOVE IN COMMENT #1. THE PLAN SHALL INCLUDE A SCOPE OF
 WORK OUTLINE WITH CORRESPONDING DETAILS THAT WILL
 INDICATE WHAT MECHANICAL ALTERATIONS OR REPAIRS ARE
 PROPOSED IN EACH ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By gjohnson Date 2017-08-17 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2017-08-17 Time 15:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By gjohnson Date 2017-07-17 Time 14:42 Rev Time 0.00
Received By gjohnson Date 2017-07-17 Time 13:12 Sent To  
Notes
2017-07-17 14:45:501ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE FLOOR PLAN SHOW LOCATION OF FIXTURES AND
 APPLIANCES. PER WPB AMEND TO FBC 107.2.1
  
 2. SEE COMMENT FROM BUILDING, FIRE AND MECHANICAL
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  