Plan Review Details - Permit 17070088
Plan Review Stops For Permit 17070088
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-22 Cont ID  
Sent By jgomez Date 2017-09-22 Time 12:24 Rev Time 0.00
Received By jgomez Date 2017-09-22 Time 11:31 Sent To  
Notes
2017-09-22 11:38:35BUILDING REVIEW APPROVED WITH PROVISO:
 NOTE: PROVIDE INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS
  
 1- PROPOSED CABANA: SHOW COMPLIANCE WITH THE HEATING
 REQUIREMENTS OF SEC. R303.9 FBC-RESIDENTIAL. NOTE:
 SHEET E-1 SHOW AN EXISTING A/C UNIT TO BE RELOCATED
 ABOVE THE DOUBLE FRENCH DOORS. PROVIDE DETAIL SHOWING
 HOW THE RELOCATED A/C UNIT IS GOING TO BE INSTALLED
 ABOVE THE NEW FRENCH DOORS. IT DOESN'T SEEM TO BE
 ENOUGH ROOM.
  
 2- THE HANDRAILS WERE REMOVED. HANDRAILS CAN NOT BE
 REMOVED. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS AS
 REQUIRED BY SEC. R311.7.8-RESIDENTIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-07 Cont ID  
Sent By jgomez Date 2017-09-07 Time 13:53 Rev Time 0.00
Received By jgomez Date 2017-09-06 Time 09:42 Sent To  
Notes
2017-09-05 17:22:15RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. FEES MAY APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME.
 CONTRACTOR TO SUBMIT SEPARATE PERMIT APPLICATION FOR
 THE GARAGE STRUCTURE BEFORE ISSUING ANY PERMITS.
  
 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS PROPERTY.
 NEED A SEPARATE PERMIT APPLICATIONS FOR EACH STRUCTURE.
 ONE PERMIT APPLICATION FOR THE MAIN HOUSE AND THE OTHER
 ONE FOR THE GARAGE CONVERSION TO LIVABLE SPACE. SEC.
 105.1 CITY AMENDMENTS.
 NOTE: THERE ARE NOT ADDITIONAL FEES FOR THE REAR
 STRUCTURE PERMIT APPLICATIONS. FEES ARE ALREADY
 INCLUDED IN THE OVERALL SCOPE OF WORK IN THE ORIGINAL
 PERMIT APPLICATION. SEPARATE PERMIT APPLICATIONS ARE TO
 FACILITATE AND COORDINATE ALL THE INSPECTIONS AND FOR
 PROPER RECORD RETENTION FILES. CONTRACTOR MAY USE SAME
 PLANS FOR BOTH STRUCTURES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 2- PROPOSED CABANA ON THE EXISTING GARAGE: SHOW
 COMPLIANCE WITH THE HEATING REQUIREMENTS OF SEC. R303.9
 FBC-RESIDENTIAL. NOTE: PORTABLE UNITS ARE NOT ALLOWED.
 RESPONSE: INFORMATION ON THE TOP LEFT HAND SIDE AND
 CABANA FLOOR PLAN ON SHEET E-1 SHOW AN EXISTING A/C
 UNIT TO BE RELOCATED ABOVE THE DOUBLE FRENCH DOORS.
 PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 RELOCATED A/C UNIT IS GOING TO BE INSTALLED ABOVE THE
 NEW FRENCH DOORS. IT DOESN'T SEEM TO BE ENOUGH ROOM.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 HANDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5 AND SPECIFICATIONS OF SEC. R311.7.8 AND
 SEC. R312.1 FBC-RESIDENTIAL. SPECIFY MATERIAL,
 FASTENERS, HEIGHT, PICKETS SPACING, ETC.
 RESPONSE: THE HANDRAILS WERE REMOVED. HANDRAILS CAN NOT
 BE REMOVED. SEE SECTION R311.7.8 FBC-RESIDENTIAL.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS AS REQUIRED
 ON THE ORIGINAL COMMENT.
  
 PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By jgomez Date 2017-08-01 Time 12:55 Rev Time 0.00
Received By jgomez Date 2017-07-31 Time 18:11 Sent To  
Notes
2017-08-01 12:56:59RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THERE ARE TWO SEPARATE STRUCTURES IN THIS PROPERTY.
 NEED A SEPARATE PERMIT APPLICATIONS FOR EACH STRUCTURE.
 ONE PERMIT APPLICATION FOR THE MAIN HOUSE AND THE OTHER
 ONE FOR THE GARAGE CONVERSION TO LIVABLE SPACE. SEC.
 105.1 CITY AMENDMENTS.
 NOTE: THERE ARE NOT ADDITIONAL FEES FOR THE REAR
 STRUCTURE PERMIT APPLICATIONS. FEES ARE ALREADY
 INCLUDED IN THE OVERALL SCOPE OF WORK IN THE ORIGINAL
 PERMIT APPLICATION. SEPARATE PERMIT APPLICATIONS ARE TO
 FACILITATE AND COORDINATE ALL THE INSPECTIONS AND FOR
 PROPER RECORD RETENTION FILES. CONTRACTOR MAY USE SAME
 PLANS FOR BOTH STRUCTURES.
  
 3- SPECIFY THE DESIGN PRESSURES FOR ALL DOORS AND
 WINDOWS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE THE
 CALCULATED DESIGN PRESSURES ARE PROVIDED.
  
 4- PROPOSED CABANA ON THE EXISTING GARAGE: SHOW
 COMPLIANCE WITH THE HEATING REQUIREMENTS OF SEC. R303.9
 FBC-RESIDENTIAL. NOTE: PORTABLE UNITS ARE NOT ALLOWED.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 HANDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5 AND SPECIFICATIONS OF SEC. R311.7.8 AND
 SEC. R312.1 FBC-RESIDENTIAL. SPECIFY MATERIAL,
 FASTENERS, HEIGHT, PICKETS SPACING, ETC.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 RISERS AND TREADS SHOWN COMPLIANCE WITH SEC. 311.7.5
 FBC-RESIDENTIAL. SPECIFY RISER HEIGHT, NOSING, ETC.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) STORAGE SINGLE FIBERGLASS DOOR AS SHOWN ON PLANS.
 FLORIDA PRODUCT APPROVAL FL17184.12 SUBMITTED IS FOR
 DOOR WITH SIDE-LITE ASSEMBLY. IT DOESN'T MATCH PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER OF RECORD TO LIST THE CURRENT
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 8- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS BEFORE SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 9- CLEARLY SPECIFY SIZE OF MULLIONS TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
  
 10- SPRAY INSULATION ICC EVALUATION REPORT ESL-1060
 SUBMITTED:
 A) PROVIDE CURRENT REPORT. THE ONE SUBMITTED EXPIRED ON
 03/2017. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) PLANS DON'T SHOW ANY SPRAY INSULATION. ENGINEER OF
 RECORD TO CLEARLY SPECIFY ON PLANS AND WALL
 SECTIONS/DETAILS INSULATION TYPE AND LOCATION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) ENGINEER OF RECORD TO REVIEW AND APPROVE INSULATION
 REPORT PRIOR TO SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By jpearson Date 2017-09-22 Time 07:16 Rev Time 0.00
Received By jpearson Date 2017-09-22 Time 07:15 Sent To  
Notes
2017-09-22 07:15:53PERMIT APPROVED WITH EXCEPTION. THE FOLLOWING ITEMS
 NEED TO BE CORRECTED AND RE-SUBMITTED BEFORE FIRST
 INSPECTION:
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE INTERSYSTEM
 BONDING TERMINATION POINT REQUIRED. PROVIDE CORRECTION.
 NEC 250.94; FBC RE3609.3
 2. RESPONSE TO COMMENTS STATES THAT 4 CIRCUIT ARE USED
 FOR THE DETACHED BUILDING, WHICH IS A CODE VIOLATION.
 CODE STATES: "A BUILDING OR OTHER STRUCTURE THAT IS
 SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE
 OF A SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY
 ONLY ONE FEEDER OR BRANCH CIRCUIT". PROVIDE CORRECTION.
 NEC 225.30
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By jpearson Date 2017-07-24 Time 13:54 Rev Time 0.00
Received By jpearson Date 2017-07-24 Time 13:54 Sent To  
Notes
2017-07-25 07:41:41CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 THE SIGNATURE ON THE PLAN DOES NOT APPEAR TO BE FROM A
 LICENSED ENGINEER OR ARCHITECT. FS 471.003(2)(H);
 471.025; FBC 107.2.1
 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE3903.3
 3. PROVIDE PANEL SCHEDULE ON PLAN INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 FBC RE3706.2, RE3902
 4. NOTE 19 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE ACCURATE LOAD CALCULATION ON PLAN INCLUDING
 ALL LOADS. NEC 220; FBC RE3602.3; FBC 107.2.1
 8. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR POOL AND ALL LOW VOLTAGE SYSTEMS TO
 INCLUDE BUT NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND
 DATA, WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE. FBC 105.1
 9. THE CIRCUITRY TO THE GARAGE BUILDING IS NOT SHOWN.
 PER CODE: "A BUILDING OR OTHER STRUCTURE THAT IS SERVED
 BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE FEEDER OR BRANCH CIRCUIT. NEC 225.30" SHOW CIRCUIT
 AND/OR CIRCUITS TO GARAGE, CORRECT IF NECESSARY. NEC
 225.30
 10. BATHROOM GFCI OUTLETS ARE REQUIRED TO BE ON A
 DEDICATED 20 AMP CIRCUIT. SHOW CIRCUIT ON PLANS. FBC
 107.2.1; NEC 210.11(C)(3) , FBC RE3703.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-09-07 Cont ID  
Sent By fmittner Date 2017-09-07 Time 14:26 Rev Time 0.00
Received By fmittner Date 2017-09-07 Time 14:26 Sent To  
Notes
2017-09-06 09:47:46REVISED DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By fmittner Date 2017-08-25 Time 16:43 Rev Time 0.00
Received By fmittner Date 2017-08-25 Time 16:43 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By fmittner Date 2017-07-17 Time 13:07 Rev Time 0.00
Received By fmittner Date 2017-07-17 Time 13:07 Sent To  
Notes
2017-07-17 13:08:16AWAITING AUGUST HPB DECISION ON WINDOWS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-22 Cont ID  
Sent By jgomez Date 2017-09-22 Time 12:30 Rev Time 0.00
Received By jgomez Date 2017-08-29 Time 15:35 Sent To  
Notes
2017-08-30 15:35:16R33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-01 Cont ID  
Sent By jgomez Date 2017-08-01 Time 18:52 Rev Time 0.00
Received By jgomez Date 2017-07-05 Time 15:02 Sent To  
Notes
2017-07-06 15:02:51R01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-09-06 Cont ID  
Sent By jgomez Date 2017-09-06 Time 09:23 Rev Time 0.00
Received By jgomez Date 2017-09-06 Time 09:20 Sent To  
Notes
2017-09-06 09:25:06NO IMPACT FEES DUE. PERMIT TECH DIDN'T PROVIDE MU-
 NUMBER ON THE COUNTY STAMP ON SHEET A-1.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-01 Cont ID  
Sent By jgomez Date 2017-08-01 Time 12:52 Rev Time 0.00
Received By jgomez Date 2017-08-01 Time 12:46 Sent To  
Notes
2017-08-01 12:54:541- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-08-01 Cont ID  
Sent By jgomez Date 2017-08-01 Time 14:35 Rev Time 0.00
Received By jgomez Date 2017-08-01 Time 12:50 Sent To  
Notes
2017-08-01 14:38:22NO MECHANICAL WORK SHOWN. PROVIDE COMPLETE INFORMATION
 UNDER A SEPARATE PERMIT. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By gjohnson Date 2017-09-22 Time 09:11 Rev Time 0.00
Received By gjohnson Date 2017-09-22 Time 09:11 Sent To  
Notes
2017-09-06 09:51:11REVISED DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-25 Cont ID  
Sent By gjohnson Date 2017-07-25 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2017-07-25 Time 14:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-09-07 Cont ID  
Sent By fmittner Date 2017-09-07 Time 14:26 Rev Time 0.00
Received By fmittner Date 2017-09-07 Time 14:26 Sent To  
Notes
2017-09-06 09:48:00REVISED DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-17 Cont ID  
Sent By fmitner Date 2017-07-17 Time 13:07 Rev Time 0.00
Received By fmittner Date 2017-07-17 Time 13:07 Sent To  
Notes
***NONE***