2017-07-25 07:41:41 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN |
| PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. |
| THE SIGNATURE ON THE PLAN DOES NOT APPEAR TO BE FROM A |
| LICENSED ENGINEER OR ARCHITECT. FS 471.003(2)(H); |
| 471.025; FBC 107.2.1 |
| 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH |
| GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC |
| 210.70(A)(2)(B), FBC RE3903.3 |
| 3. PROVIDE PANEL SCHEDULE ON PLAN INDICATING ANY NEW OR |
| ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; |
| FBC RE3706.2, RE3902 |
| 4. NOTE 19 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE4002.14 |
| 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| 107.2.1 |
| 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 7. PROVIDE ACCURATE LOAD CALCULATION ON PLAN INCLUDING |
| ALL LOADS. NEC 220; FBC RE3602.3; FBC 107.2.1 |
| 8. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR POOL AND ALL LOW VOLTAGE SYSTEMS TO |
| INCLUDE BUT NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND |
| DATA, WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL |
| SUFFICE. FBC 105.1 |
| 9. THE CIRCUITRY TO THE GARAGE BUILDING IS NOT SHOWN. |
| PER CODE: "A BUILDING OR OTHER STRUCTURE THAT IS SERVED |
| BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A |
| SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY |
| ONE FEEDER OR BRANCH CIRCUIT. NEC 225.30" SHOW CIRCUIT |
| AND/OR CIRCUITS TO GARAGE, CORRECT IF NECESSARY. NEC |
| 225.30 |
| 10. BATHROOM GFCI OUTLETS ARE REQUIRED TO BE ON A |
| DEDICATED 20 AMP CIRCUIT. SHOW CIRCUIT ON PLANS. FBC |
| 107.2.1; NEC 210.11(C)(3) , FBC RE3703.4 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |