Plan Review Details - Permit 17070057
Plan Review Stops For Permit 17070057
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-11 Cont ID  
Sent By hmoser Date 2017-07-11 Time 14:16 Rev Time 0.00
Received By hmoser Date 2017-07-03 Time 16:06 Sent To  
Notes
2017-07-03 16:06:38MECH -$5000

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By hmoser Date 2017-07-11 Time 14:16 Rev Time 0.00
Received By hmoser Date 2017-07-11 Time 14:05 Sent To  
Notes
2017-07-11 14:16:21PLAN DENIED
 1( PROVIDE CFM ON ALL SUPPLY GRILLS.
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2014 RESIDENTIAL CODE. TRANSFER DUCT MUST BE 1 1/2
 TIMES
 LARGER THAN THE SUPPLY DUCT.
 PLEASE CONTACT ME IF THERE ARE ANY QUESTIONS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676