Plan Review Details - Permit 17070011
Plan Review Stops For Permit 17070011
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-18 Cont ID  
Sent By jgomez Date 2017-08-18 Time 14:46 Rev Time 0.00
Received By jgomez Date 2017-08-18 Time 14:46 Sent To  
Notes
2017-08-18 14:47:01MET WITH CONTRACTOR. FRANK LEO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-08-11 Cont ID  
Sent By ccole Date 2017-08-11 Time 15:34 Rev Time 0.00
Received By ccole Date 2017-08-11 Time 15:34 Sent To  
Notes
2017-08-11 15:38:273RD REVIEW FBC-2014 BUILDING
 PERMIT #17070011
 8/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE TAMKO NOA WAS RESUBMITTED A THIRD TIME WITHOUT
 THE REQUIRED ENGINEERING FOR THE FLAT ROOF- SEE 1ST
 REVIEW COMMENT PRINTED BELOW.
  
 2) REFER TO LIMITATION #7 ON PAGE 15 OF NOA #
 17-0222.09: INCREASED FASTENER DENSITIES AT PERIMETER
 AND CORNER AREAS REQUIRED. PROVIDE CALCULATIONS
 PREPARED AND SIGNED AND SEALED BY A FL. REGISTERED
 PROFESSIONAL ENGINEER, ARCHITECT, OR REGISTERED ROOF
 CONSULTANT.
  
 3) THE PERMIT VALUE OF $1560.00 FOR THE POPOSED ROOF
 REPLACEMENT APPEARS TO BE LOW. IN ACCORDANCE WITH
 SECTION 109.3 WPB AMENDMENTS TO THE FBC, PLEASE
 INDICATE THE SQUARE FOOTAGE AREAS OF THE FLAT ROOF AND
 SHINGLE ROOFS ON THE PERMIT APPLICATION AND SUBMIT A
 SIGNED CONTRACT.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-02 Cont ID  
Sent By ccole Date 2017-08-02 Time 18:03 Rev Time 0.00
Received By ccole Date 2017-08-02 Time 18:03 Sent To  
Notes
2017-08-02 18:05:091ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070011
 8/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION WAS RESUBMITTED WITHOUT THE REQUIRED
 ENGINEERING FOR THE FLAT ROOF- SEE 1ST REVIEW COMMENT
 PRINTED BELOW.
  
 1) REFER TO LIMITATION #7 ON PAGE 15 OF NOA #
 17-0222.09: INCREASED FASTENER DENSITIES AT PERIMETER
 AND CORNER AREAS REQUIRED. PROVIDE CALCULATIONS
 PREPARED AND SIGNED AND SEALED BY A FL. REGISTERED
 PROFESSIONAL ENGINEER, ARCHITECT, OR REGISTERED ROOF
 CONSULTANT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-03 Cont ID  
Sent By ccole Date 2017-07-03 Time 13:06 Rev Time 0.00
Received By ccole Date 2017-07-03 Time 13:06 Sent To  
Notes
2017-07-03 13:09:511ST REVIEW FBC-2014 BUILDING
 PERMIT #17070011
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO LIMITATION #7 ON PAGE 15 OF NOA #
 17-0222.09: INCREASED FASTENER DENSITIES AT PERIMETER
 AND CORNER AREAS REQUIRED. PROVIDE CALCULATIONS
 PREPARED AND SIGNED AND SEALED BY A FL. REGISTERED
 PROFESSIONAL ENGINEER, ARCHITECT, OR REGISTERED ROOF
 CONSULTANT.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-18 Cont ID  
Sent By jgomez Date 2017-08-18 Time 14:46 Rev Time 0.00
Received By jgomez Date 2017-08-18 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-08-11 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-09 Time 13:11 Sent To  
Notes
2017-08-10 13:11:24RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-02 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-31 Time 15:55 Sent To  
Notes
2017-08-01 15:55:22RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-03 Time   Rev Time 0.00
Received By cpuell Date 2017-07-03 Time 11:30 Sent To  
Notes
2017-07-03 11:30:57CCOLE'S DESK