Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By cthroop Date 2017-11-14 Time 09:36 Rev Time 0.00
Received By cthroop Date 2017-11-13 Time 07:26 Sent To  
Notes
2017-11-14 09:46:28BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEE PLAN PAGE A4.02. STAIR DETAIL REFERENCES DETAILS
 D,E&F 4.03. PLAN PAGE 4.03 IS MISSING. REVIEW OF STAIRS
 IS NOT COMPLETE.
 2. SEE STAIR DETAIL ON PAGE A4.02, OPENING BETWEEN
 GUARD AND STAIR SHALL NOT EXCEED 4 INCHES PER R312.1.3.
 3. NOTE #3 FROM FIRST REVIEW HAS NOT BEEN ADDRESSED.
 THERE IS A CONFLICT BETWEEN CEILING INSULATION ON
 DETAILS A&B, PAGE A4.00. PLEASE CLARIFY.
 4. NOTE #4 FROM FIRST REVIEW HAS NOT BEEN ADDRESSED.
 DESIGNER TO SELECT ICYNENE PRODUCT TO BE INSTALLED FROM
 ICC-ES REPORT. ALSO PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS AT TIME OF INSPECTION.
 5. ONLY ONE SET OF SUBMITTALS PROVIDED FOR THE BBQ
 GRILL, DRYER AND TANKLESS WATER HEATER. TWO SETS
 REQUIRED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By cthroop Date 2017-07-28 Time 10:12 Rev Time 0.00
Received By cthroop Date 2017-07-27 Time 08:19 Sent To  
Notes
2017-07-28 10:18:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW BARREL TILE
 ROOFING.
 3. REFERENCE PLAN PAGE A4.00 - WALL SECTION A SPECIFIES
 R-19 TO BE USED IN CEILING ASSEMBLY, WALL SECTION B
 SPECIFIES R-20 - PLEASE CLARIFY.
 4. DESIGNER TO SELECT ICYNENE PRODUCT TO BE USED BASED
 ON PROPOSED R-VALUE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-25 Cont ID  
Sent By jpearson Date 2017-10-25 Time 13:44 Rev Time 0.00
Received By jpearson Date 2017-10-25 Time 13:44 Sent To  
Notes
2017-10-25 13:44:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS: PREVIOUS COMMENTS CORRECTED
 ARE NOTED AS CORRECTED. COMMENTS THAT NEED FURTHER
 CORRECTION HAVE ADDITIONAL INFORMATION IN PARENTHESES.
  
 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER
 CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE
 NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION
 FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN
 SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED
 GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220,
 250.50; FBC RE3601.2, 3602.1, 3608.1 (LOAD CALCULATION
 PROVIDED IS FOR A MULTI-FAMILY DWELLING WITH 3 UNITS,
 WHICH DOES NOT APPLY WHEN THERE ARE ONLY 2 UNITS. THE
 DEMAND FACTOR APPLIED IS NOT PERMITTED FOR THIS. IT
 APPEARS THAT THE 3/0 WIRE STATED FOR THE SERVICE RISER
 IS OF ADEQUATE SIZE, BUT THE LOAD CALCULATION NEEDS TO
 BE ACCURATE.)
 2. CORRECTED
 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14 (NOTE 4 HAS BEEN
 EDITED, BUT IT STILL STATES THE WRONG CODE REFERENCE.
 IT SHOULD BE EITHER NEC 406.12 OR FBC RE 4002.14)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By jpearson Date 2017-07-18 Time 09:35 Rev Time 0.00
Received By jpearson Date 2017-07-18 Time 09:35 Sent To  
Notes
2017-07-18 10:36:51CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER
 CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE
 NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION
 FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN
 SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED
 GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220,
 250.50; FBC RE3601.2, 3602.1, 3608.1
 2. LOAD CALCULATION PROVIDED FOR EACH UNIT DOES NOT
 INCLUDE THE RANGE. PROVIDE CORRECTION TO INCLUDE THE
 RANGE. NEC 210.19(3), 220.55; FBC RE3602.2, 3702.9.1
 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14
 3. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE
 AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE
 ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT
 DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS
 REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE
 CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12
 4. UNIT B SHOW THE BATHROOM OUTLETS ON A 15 AMP
 CIRCUIT, AND IT DOES NOT SHOW A GFCI OUTLET LOCATED
 WITHIN 3 FEET OF THE BASIN. PROVIDE 20 AMP CIRCUIT AND
 OUTLET PER CODE. NEC 210.11(C)(3) , 210.52(D) FBC
 RE3703.4, 3901.6
 5. UNIT B, CIRCUIT 19,21 SHOWS THE AHU ON A 45 AMP
 BREAKER. SPECS FROM MECHANICAL DRAWING SHOW A MAX 30
 AMP BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 6. UNIT B, CIRCUIT 16,18 SHOW A 20 AMP CIRCUIT TO THE
 RANGE. A MINIMUM 40 AMP CIRCUIT IS REQUIRED. PROVIDE
 CORRECTION. NEC 210.19(3), 220.55; FBC RE3602.2,
 3702.9.1
 7. UNIT B SHOWS THE DINING ROOM LIGHT ON THE SAME
 CIRCUIT AS THE DINING ROOM OUTLETS, WHICH IS NOT
 PERMITTED PER CODE. PROVIDE CORRECTION. NEC
 210.11(C)(1), 210.52(B)(2); FBC RE3703.2
 8. UNIT B AND C SHOW ONLY ONE SMALL APPLIANCE CIRCUIT
 FEEDING THE KITCHEN COUNTER OUTLETS. CODE REQUIRES A
 MINIMUM OF 2 CIRCUITS. PROVIDE CORRECTION. NEC
 210.11(C)(1), 210.52(B)(3); FBC RE3703.2
 9. UNIT C, CIRCUIT 18, SHOWS THE BATHROOM OUTLETS ON A
 15 AMP CIRCUIT, WHICH IS NOT PERMITTED PER CODE.
 PROVIDE CORRECTION. NEC 210.11(C)(3); FBC RE3703.4,
 3901.6
 10. UNIT C, CIRCUIT 17,19 SHOWS THE AHU ON A 45 AMP
 BREAKER. SPECS FROM MECHANICAL DRAWING SHOW A MAX 30
 AMP BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 11. UNIT C SHOWS THE DINING ROOM ON A 15 AMP CIRCUIT,
 WHICH IS NOT PERMITTED PER CODE. PROVIDE CORRECTION.
 NEC 210.11(C)(1), 210.52(B)(2),(3); FBC RE3703.2
 12. UNIT C DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE3901.8
 13. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED FOR BOTH UNITS DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE3901.4
 14. UNIT C SHOWS THE KITCHEN LIGHT ON CIRCUIT B-1. IS
 THIS LIGHT FED FROM B UNIT FOR SOME REASON, OR SHOULD
 THIS BE CORRECTED TO BE FED FORM UNIT C? CLARIFY AND/OR
 CORRECT. FBC 107.2.1
 15. BOTH UNITS SHOW THE DISHWASHER AND DISPOSAL ON ONE
 CIRCUIT. TYPICALLY, THESE ARE ON SEPARATE CIRCUITS DUE
 TO THE DEMAND LOAD. IF THE INTENTION IS TO HAVE BOTH OF
 THESE ON ONE CIRCUIT, PROVIDE SPEC SHEETS OF UNITS
 SHOWING THE AMPERAGE DRAW TO CONFIRM THE CIRCUIT WILL
 NOT BE OVERLOADED. NEC 110.3, 215.2, 210.23; FBC
 RE3701.2
 16. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-10-19 Cont ID  
Sent By gjohnson Date 2017-10-19 Time 10:51 Rev Time 0.00
Received By gjohnson Date 2017-10-19 Time 10:50 Sent To  
Notes
2017-10-19 10:50:192ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: PLEASE REMOVE REFERENCE TO GAS APPLIANCES
 IF NOT GAS
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 PLEASE
 REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS
  
 2. SHOW LOCATION OF TANKLESS WATER HEATERS ON ELEVATION
 PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION
 GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC
 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF
 NOT GAS
  
 3.SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 SHOW AN
 ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF
 NOT GAS
  
 4. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 SHOW AN
 ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF
 NOT GAS
  
 5.SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF THE AC UNITS
 ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS WH NORTH OF
 AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE EAST WALL P1
 SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS ON THE EAST
 WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1 PLEASE
 REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 15:39 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 15:39 Sent To  
Notes
2017-07-18 15:41:261ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. SHOW LOCATION OF TANKLESS WATER HEATERS ON ELEVATION
 PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION
 GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC
 107.2.1
  
 3.SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 SHOW AN
 ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 SHOW AN
 ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 5.SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF THE AC UNITS
 ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS WH NORTH OF
 AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE EAST WALL P1
 SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS ON THE EAST
 WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-07-11 Cont ID  
Sent By fmittner Date 2017-07-11 Time 10:13 Rev Time 0.00
Received By fmittner Date 2017-07-11 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-16 Cont ID  
Sent By hmoser Date 2017-11-16 Time 11:36 Rev Time 0.00
Received By hmoser Date 2017-10-02 Time 13:58 Sent To  
Notes
2017-10-03 13:58:46R33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-06 Cont ID  
Sent By hmoser Date 2017-08-06 Time 10:08 Rev Time 0.00
Received By hmoser Date 2017-06-29 Time 13:21 Sent To  
Notes
2017-06-30 13:22:06R05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-16 Cont ID  
Sent By hmoser Date 2017-11-16 Time 11:35 Rev Time 0.00
Received By hmoser Date 2017-11-16 Time 10:56 Sent To I
Notes
2017-11-16 11:35:45PLAN DENIED
 REFER TO SECTION M 1401.3 SIZING ENERGY CALCULATIONS
 REQUIRED FBC RESIDENTIAL CODE 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-06 Cont ID  
Sent By hmoser Date 2017-08-06 Time 10:08 Rev Time 0.00
Received By hmoser Date 2017-08-06 Time 10:01 Sent To  
Notes
2017-08-06 10:08:01PLAN DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT SUPPLY AND RETURN
 PER SECTION 107 FBC.
 2) PROVIDE LOCATION AND SIZE OF RETURN AIR ON PLAN
 SECTION 107 FBC.
 3) REFER TO SECTION M1401.3 SIZING
 ENERGY CALCULATIONS REQUIRED
 2014 RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-19 Cont ID  
Sent By gjohnson Date 2017-10-19 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2017-10-18 Time 17:46 Sent To  
Notes
2017-10-19 10:47:572ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS8US COMMENTS HAVE NOT BEEN
 COMPLIED WITH.
  
 2ND REQUEST1. THE WASHING MACHINES ON FIRST AND SECOND
 FLOOR ARE MISSING FROM RISER DIAGRAMS WATER AND
 SANITARY PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 2ND REQUEST 2. SHT. A1.03 SHOWS A GAS RANGE M1 AND E1
 SHOW AN ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES
 IF NOT GAS
  
 2ND REQUEST 3. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1
 SHOW AN ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES
 IF NOT GAS
  
 2ND REQUEST 4. SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF
 THE AC UNITS ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS
 WH NORTH OF AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE
 EAST WALL P1 SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS
 ON THE EAST WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1
 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 15:28 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 14:54 Sent To  
Notes
2017-07-18 15:38:281ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINES ON FIRST AND SECOND FLOOR ARE
 MISSING FROM RISER DIAGRAMS WATER AND SANITARY PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.3.5.3(11)
  
 2. SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 SHOW AN
 ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 SHOW AN
 ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF THE AC UNITS
 ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS WH NORTH OF
 AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE EAST WALL P1
 SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS ON THE EAST
 WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-11-13 Cont ID  
Sent By cthroop Date 2017-11-13 Time 17:14 Rev Time 0.00
Received By cthroop Date 2017-11-13 Time 07:26 Sent To  
Notes
2017-11-13 17:16:09BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR BARREL TILE ROOF.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By cthroop Date 2017-07-28 Time 09:58 Rev Time 0.00
Received By cthroop Date 2017-07-28 Time 09:58 Sent To  
Notes
2017-07-28 10:12:44BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW BARREL TILE
 ROOFING.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-18 Cont ID  
Sent By fmittner Date 2017-10-18 Time 15:02 Rev Time 0.00
Received By fmittner Date 2017-10-18 Time 15:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By fmittner Date 2017-07-11 Time 10:14 Rev Time 0.00
Received By fmittner Date 2017-07-11 Time 10:14 Sent To  
Notes
2017-07-11 10:14:49VALUE EXCEEDS 50% REQUIRES SEPERATE LANDSCAPE PERMIT