Plan Review Details - Permit 17061318
Plan Review Stops For Permit 17061318
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-30 Cont ID  
Sent By cthroop Date 2017-10-30 Time 10:06 Rev Time 0.00
Received By cthroop Date 2017-10-27 Time 14:35 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By cthroop Date 2017-08-07 Time 13:45 Rev Time 0.00
Received By cthroop Date 2017-08-07 Time 13:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By cthroop Date 2017-07-28 Time 08:21 Rev Time 0.00
Received By cthroop Date 2017-07-27 Time 08:18 Sent To  
Notes
2017-07-28 08:43:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE WIND DESIGN LOADS FOR WINDOW AND DOOR
 OPENINGS. PROVIDE INFORMATION OF WINDOW AND DOOR
 SCHEDULES OR PLACE ON PLAN NEXT TO EACH OPENING.
 3. PROVIDE DETAIL FOR CRACK CONTROL FOR NEW CONCRETE
 SLABS PER ACI 332 & FBC 107.
 4. SPECIFY CONNECTORS FOR NEW 2X8 FLOOR JOISTS TO
 EXTERIOR WALL CONNECTION PER FBC R502 & FBC 107.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By jpearson Date 2017-10-26 Time 16:08 Rev Time 0.00
Received By jpearson Date 2017-10-26 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jpearson Date 2017-07-19 Time 13:22 Rev Time 0.00
Received By jpearson Date 2017-07-19 Time 13:22 Sent To  
Notes
2017-07-19 13:43:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. LOAD CALCULATION PROVIDED DOES NOT INCLUDE THE
 RANGE. PROVIDE CORRECTION TO INCLUDE THE RANGE. NEC
 210.19(3), 220.55; FBC RE3602.2, 3702.9.1
 2. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14
 3. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE
 AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE
 ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT
 DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS
 REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE
 CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12
 4. CIRCUIT 25,27 SHOWS THE AHU ON A 25 AMP BREAKER.
 SPECS FROM MECHANICAL DRAWING SHOW A MAX 40 AMP
 BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 5. CIRCUIT 26,28 SHOWS THE CU ON A 45 AMP BREAKER.
 SPECS FROM MECHANICAL DRAWING SHOW A MAX 30 AMP
 BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 6. CIRCUIT 4 SHOW A 15 AMP CIRCUIT TO THE
 RANGE/COOKTOP. A MINIMUM 40 AMP CIRCUIT IS REQUIRED.
 PROVIDE CORRECTION. NEC 210.19(3), 220.55; FBC
 RE3602.2, 3702.9.1
 7. CIRCUIT 15 SHOWS THE DINING ROOM ON A 15 AMP
 CIRCUIT, WHICH IS NOT PERMITTED PER CODE. THE LIGHT IN
 DINING ROOM SHOULD NOT BE ON THE SAME CIRCUIT AS THE
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2),(3); FBC RE3703.2
 8. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. THE ONLY OUTLET SHOWN IS FOR THE
 TANKLESS WATER HEATER (CIRCUIT A-11), AND ALSO IS
 CONNECTED TO BATH #2 GFCI OUTLET. BATH GFCI OUTLETS ARE
 REQUIRED TO BE A 20 AMP CIRCUIT, AND NO OTHER ITEMS CAN
 BE ON THE SAME CIRCUIT, UNLESS THE CIRCUIT REMAINS IN
 ONE BATHROOM ONLY. PROVIDE CORRECTION. NEC 210.63,
 210.11(C)(3), 210.52(D); FBC RE3901.12, 3703.4
 9. CIRCUIT A-22 TO BATH 1 GFCI OUTLET NEEDS TO BE A 20
 AMP CIRCUIT. PROVIDE CORRECTION. NEC 210.11(C)(3); FBC
 3703.4
 10. MASTER BEDROOM DOES NOT COMPLY WITH THE WALL
 SPACING REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
 11. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By lcrespo Date 2017-10-17 Time 14:50 Rev Time 0.00
Received By lcrespo Date 2017-10-17 Time 14:50 Sent To  
Notes
2017-10-17 14:50:4910/13/17 APPROVED BY PLUMBING PUT CAJ IN "R32" LAC

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 13:10 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 13:10 Sent To  
Notes
2017-07-18 14:29:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. SHOW LOCATION OF TANKLESS WATER HEATER ON ELEVATION
 PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION
 GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-07-11 Cont ID  
Sent By fmittner Date 2017-07-11 Time 10:12 Rev Time 0.00
Received By fmittner Date 2017-07-11 Time 10:12 Sent To  
Notes
2017-07-11 10:12:58WEST ARCHED WINDOW BEING ENCLOSED SHALL RETAIN ORGINAL
 ARCH SHAPE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By hmoser Date 2017-11-03 Time 14:24 Rev Time 0.00
Received By hmoser Date 2017-10-02 Time 13:42 Sent To  
Notes
2017-10-03 13:42:53R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-06 Cont ID  
Sent By hmoser Date 2017-08-06 Time 09:17 Rev Time 0.00
Received By hmoser Date 2017-06-29 Time 13:19 Sent To  
Notes
2017-06-30 13:19:19R02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By hmoser Date 2017-11-03 Time 14:23 Rev Time 0.00
Received By hmoser Date 2017-11-03 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-06 Cont ID  
Sent By hmoser Date 2017-08-06 Time 09:17 Rev Time 0.00
Received By hmoser Date 2017-08-06 Time 08:53 Sent To  
Notes
2017-08-06 09:17:12PLAN DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT WORK SUPPLY
 AND RETURN. PER SECTION 107 FBC
 2) PROVIDE LOCATION AND SIZE OF RETURN AIR
 GRILL ON PLAN. SECTION 107 FBC
 3) REFER TO SECTION M1401.3 SIZING
 ENERGY CALCULATION REQUIRED WITH PLAN
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By lcrespo Date 2017-10-17 Time 14:21 Rev Time 0.00
Received By lcrespo Date 2017-10-17 Time 14:21 Sent To  
Notes
2017-10-17 14:22:4810/13/17 APPROVED BY PLUMBING PUT CAJ IN "R32" LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 12:35 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 09:56 Sent To  
Notes
2017-07-18 13:09:401ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE IS MISSING FROM RISER DIAGRAMS
 WATER AND SANITARY PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-07-28 Cont ID  
Sent By cthroop Date 2017-07-28 Time 08:47 Rev Time 0.00
Received By cthroop Date 2017-07-28 Time 08:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-11 Cont ID  
Sent By fmittner Date 2017-07-11 Time 10:08 Rev Time 0.00
Received By fmittner Date 2017-07-11 Time 10:08 Sent To  
Notes
2017-07-11 10:12:17VALUE EXCEEDS 505 REQUIRES SEPERATE LANDSCAPE PERMIT.
  
 DRIVEWAY REQUIRES SEPERATE PERMIT