Plan Review Details - Permit 17061315
Plan Review Stops For Permit 17061315
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By jgomez Date 2017-07-05 Time 09:14 Rev Time 0.00
Received By jgomez Date 2017-07-05 Time 08:48 Sent To  
Notes
2017-07-05 09:28:43RE-ROOF REVISION , BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BASE SHEET MECHANICALLY ATTACHED FASTENERS NEED THE
 WITHDRAWAL RESISTANCE TEST (TAS 105) AS REQUIRED BY
 NOTE #10 OF FLORIDA PRODUCT APPROVAL FL2533-R17
 SUBMITTED. PROVIDE 2 SIGNED AND SEALED COPIES OF THE
 TEST. SEC. 1609.1 FBC.
  
 2- THE DESIGN PRESSURES FOR SELECTED SYSTEM LWC-33 IS
 -52.5 PSF. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY NOTE #8 OF FLORIDA PRODUCT APPROVAL SUBMITTED.
 PROVIDE 2 SIGNED AND SEALED CALCULATIONS. NOTE:
 ENGINEER DOING THE CALCULATIONS TO COORDINATE WITH THE
 TAS 105 RESULTS AS REQUIRED ON ITEM #1 ABOVE.
 SEC. 1609.1 FBC
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-05 Cont ID  
Sent By jgomez Date 2017-07-05 Time 09:28 Rev Time 0.00
Received By jgomez Date 2017-06-29 Time 09:32 Sent To  
Notes
2017-06-30 09:32:36REVISION ROUTED TO JGOMEZ