Plan Review Details - Permit 17061225
Plan Review Stops For Permit 17061225
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2017-10-26 Cont ID  
Sent By spalmer Date 2017-10-26 Time 16:34 Rev Time 0.00
Received By spalmer Date 2017-10-26 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-10-25 Cont ID  
Sent By jgomez Date 2017-10-25 Time 15:05 Rev Time 0.00
Received By jgomez Date 2017-10-25 Time 12:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-10-04 Cont ID  
Sent By jgomez Date 2017-10-03 Time 18:49 Rev Time 0.00
Received By jgomez Date 2017-10-03 Time 16:29 Sent To  
Notes
2017-10-03 16:33:44NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THE FOOTPRINT OF THE HOUSE SHOWN ON THE DRAINAGE
 PLAN SUBMITTED DOESN'T MATCH PLANS. REVISE AS REQUIRED
 TO MATCH. SUBMIT TWO NEW SIGNED AND SEALED COPIES SEC.
 R401.3 FBC -RESIDENTIAL.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By jgomez Date 2017-08-17 Time 09:47 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 08:10 Sent To  
Notes
2017-08-17 09:30:46NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THIS PROPERTY WAS SUBDIVIDED INTO TWO LOTS. LOT 11
 AND LOT 12. THIS PERMIT APPLICATION IS FOR THE HOUSE TO
 BE BUILT IN LOT 12. THE PROPOSED ADDRESS FOR LOT 12 IS
 749 TALLAPOOSA STREET. REVISE ADDRESS ON PLANS TO
 REFLECT THE CORRECT ADDRESS. 745 TALLAPOOSA STREET IS
 FOR THE HOUSE TO BE BUILT IN LOT 11. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
 2- PROVIDE DRAINAGE PLAN ( 2 COPIES) AS REQUIRED BY
 SEC. R401.3 FBC -RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE CORRECT INFORMATION ON TOP OF FORM. THE
 ADDRESS NEEDS TO BE COORDINATED WITH ITEM #1 ABOVE.
 REVISE AS REQUIRED. SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE CALCULATIONS ARE NOT USING THE
 SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By jgomez Date 2017-07-25 Time 08:53 Rev Time 0.00
Received By jgomez Date 2017-07-24 Time 19:21 Sent To  
Notes
2017-07-25 08:37:47NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THIS PROPERTY WAS SUBDIVIDED INTO TWO LOTS. LOT 11
 AND LOT 12. THIS PERMIT APPLICATION IS FOR THE HOUSE TO
 BE BUILT IN LOT 12. THE PROPOSED ADDRESS FOR LOT 12 IS
 749 TALLAPOOSA STREET. REVISE ADDRESS ON PLANS TO
 REFLECT THE CORRECT ADDRESS. 745 TALLAPOOSA STREET IS
 FOR THE HOUSE TO BE BUILT IN LOT 11. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) . SEC. R401.4
 FBC-RESIDENTIAL 5TH EDITION (2014).
  
 4- PROVIDE DRAINAGE PLAN ( 2 COPIES) AS REQUIRED BY
 SEC. R401.3 FBC -RESIDENTIAL.
  
 5- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUE TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. THE VALUATION
 WAS UPDATED TO $192,501. THE PERMIT FEE BALANCE IS
 $3,627.36.
  
 6- SHEET 1-4:
 A) THE LOADS SPECIFIED ON THE DESIGN CRITERIA DON'T
 MATCH THE LOADS SPECIFIED ON STRUCTURAL NOTE #2 ON SAME
 DRAWING. REVISE AS REQUIRED TO MATCH. ALSO, THE ATTIC
 LIVE LOAD NEEDS TO BE REVISED IF THE ATTIC ACCESS HAS
 AN STAIR AND FOOTNOTES "B" AND "G" OF TABLE R301.5
 FBC-RESIDENTIAL APPLY.
  
 B) SPECIFY ATTIC ACCESS SIZE. SEC. R807
 FBC-RESIDENTIAL.
  
 C) STRUCTURAL NOTE #2 REFERENCES FBC 2010. THE CURRENT
 CODE IS FBC 5TH EDITION (2014). REVISE AS REQUIRED.
 SEC. 553 F.S.
  
 7- SHEET 3-4: FOUNDATION PLAN IDENTIFIES DETAIL
 SECTIONS 1/S-3 AND 2/S-3. THERE IS NO S-3 SHEET. REVISE
 AS REQUIRED. PROVIDE CORRECT DETAIL REFERENCE. . SEC.
 107.2.1 CITY AMENDMENTS.
  
 8- PLANS NEED TO SPECIFY CARBON MONOXIDE ALARMS FOR ALL
 BEDROOMS. SEE SEC. R315.1 FBC-RESIDENTIAL FOR REQUIRED
 LOCATION.
  
 9- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE ADDRESS NEEDS TO BE COORDINATED WITH ITEM #2
 ABOVE. THE OWNER NAME DOESN'T MATCH OWNER INFORMATION
 SHOWN ON THE PERMIT APPLICATION AND PBC PROPERTY
 APPRAISER. REVISE AS REQUIRED TO MATCH. ALSO, PROVIDE
 THE BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER 604700.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) INSULATION R-VALUE SHOWN ON ITEM #9 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PAGE 3 OF 4 IS SHOWING AN ATTIC VENT RATIO OF 1/300.
 TYPICALLY THE VENTILATION RATIO IS 1/150. PERSON
 PREPARING THE ENERGY CALCULATIONS TO PROVIDE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R806.2
 FBC-RESIDENTIAL TO GET THE 1/300 VENT RATIO.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE CALCULATIONS ARE NOT USING THE
 SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 10- ENGINEER PLANS NEED TO BE REVISED SHOWING THE
 COMPLIANCE WITH THE 1/300 ATTIC VENT RATIO. COORDINATE
 WITH ENERGY CALCULATIONS SUBMITTED. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-22 Cont ID  
Sent By jpearson Date 2017-08-22 Time 09:02 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By jpearson Date 2017-07-17 Time 08:59 Rev Time 0.00
Received By jpearson Date 2017-07-17 Time 08:59 Sent To  
Notes
2017-07-17 09:10:18CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHOW COMPLIANCE WITH ENERGY CODE FOR LIGHTING: "A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
 2. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUITS 15, 24,
 SHOULD BE AFCI PROTECTED CIRCUITS. CIRCUIT 29 SHOWS A
 #14 WIRE ON A 20 AMP BREAKER. NEC 215.5, 408.4, ; FBC
 107.2.1, FBC RE3706.1
 3. WIRE FEEDING INTERIOR PANEL FROM OUTSIDE SERVICE IS
 TOO SMALL. 2/0 COPPER CAN ONLY BE USED WHERE IT FEEDS
 100% OF THE LOAD. PROVIDE CORRECTION. NEC 310.15(B)(7);
 FBC RE3602.2
 4. KITCHEN COUNTER OUTLETS SHOW ONLY ONE CIRCUIT (#20).
 CODE REQUIRES MINIMUM OF 2 SMALL APPLIANCE CIRCUITS.
 PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(3); FBC
 RE3703.2
 5. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE
 CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER
 CODE. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2),(3); FBC RE3703.2
 6. LOAD CALCULATION SHOULD INCLUDE 2 SMALL APPLIANCE
 CIRCUITS. NEC 210.11(C)(1), NEC 220,; FBC RE3602.2
 7. IN SEVERAL LOCATIONS THE OUTLET SPACING IS NOT
 WITHIN THE LIMITS PER CODE: "RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET". PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
 8. PROVIDE NOTE TO COMPLY WITH CODE FOR LIGHTING IN
 CLOSETS PER NEC 410.16, FBC RE4003.12.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-10-25 Cont ID  
Sent By jgomez Date 2017-10-25 Time 15:05 Rev Time 0.00
Received By jgomez Date 2017-10-20 Time 11:09 Sent To  
Notes
2017-10-24 11:09:49RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-04 Cont ID  
Sent By jgomez Date 2017-10-04 Time 11:17 Rev Time 0.00
Received By jgomez Date 2017-09-20 Time 14:56 Sent To  
Notes
2017-09-22 14:56:16RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-06 Cont ID  
Sent By lmarchan Date 2017-09-06 Time 08:15 Rev Time 0.00
Received By lmarchan Date 2017-08-08 Time 14:41 Sent To  
Notes
2017-08-09 14:42:00R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-25 Cont ID  
Sent By jgomez Date 2017-07-25 Time 18:55 Rev Time 0.00
Received By jgomez Date 2017-06-27 Time 11:57 Sent To  
Notes
2017-06-30 11:57:45R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2017-10-26 Cont ID  
Sent By jgomez Date 2017-10-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2017-10-26 Time 16:03 Sent To  
Notes
2017-10-26 16:04:30$9,766.49 PAID. MU-2017-028064

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2017-10-25 Cont ID  
Sent By jgomez Date 2017-10-25 Time 15:05 Rev Time 0.00
Received By jgomez Date 2017-10-25 Time 12:26 Sent To  
Notes
2017-10-25 12:28:021- NEED COPY OF IMPACT FEE PAID RECEIPT FOR CITY
 RECORDS. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-10-03 Cont ID  
Sent By jgomez Date 2017-10-03 Time 18:49 Rev Time 0.00
Received By jgomez Date 2017-10-03 Time 18:49 Sent To  
Notes
2017-10-03 18:49:231- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By jgomez Date 2017-08-17 Time 09:31 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 09:31 Sent To  
Notes
2017-08-17 09:31:491- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEE ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By jgomez Date 2017-07-25 Time 14:21 Rev Time 0.00
Received By jgomez Date 2017-07-25 Time 07:51 Sent To  
Notes
2017-07-25 14:22:051- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-10-04 Cont ID  
Sent By jgomez Date 2017-10-04 Time 11:17 Rev Time 0.00
Received By jgomez Date 2017-10-04 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By jgomez Date 2017-08-17 Time 10:16 Rev Time 0.00
Received By jgomez Date 2017-08-17 Time 10:16 Sent To  
Notes
2017-08-17 10:17:06NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE THE DUCT SIZE SPECIFIED FOR THE MASTER
 BEDROOM RETURN AIR TRANSFER DUCT TO COMPLY WITH SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). NEED TO
 CONSIDER ALL THE SUPPLY AIR ENTERING THE MASTER BEDROOM
 AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4. . THIS
 INCLUDES THE BATHROOM AND CLOSETS.
 RESPONSE: DUCT WAS REVISED TO 12" DIAMETER. NEED AT
 LEAST 13" DUCT. THERE IS NO 13" DUCT. THEREFORE, NEED
 14" DUCT. REVISE AS REQUIRED.
  
 2- CALCULATIONS TO HAVE THE ENGINEER'S SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 RESPONSE: CALCULATIONS WERE DONE BY LILLIAN GONZALEZ
 "GOARCH ENGINEERING, INC.". NEED THE ENGINEER'S SEAL
 AND SIGNATURE.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By jgomez Date 2017-07-25 Time 18:55 Rev Time 0.00
Received By jgomez Date 2017-07-25 Time 18:38 Sent To  
Notes
2017-07-25 18:55:01NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE THE DUCT SIZE SPECIFIED FOR THE MASTER
 BEDROOM RETURN AIR TRANSFER DUCT TO COMPLY WITH SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). NEED TO
 CONSIDER ALL THE SUPPLY AIR ENTERING THE MASTER BEDROOM
 AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4. . THIS
 INCLUDES THE BATHROOM AND CLOSETS.
  
 2- CLARIFY ATTACHMENT OF CONDENSING UNIT. THE MOUNTING
 DETAIL ON SHEET M-1 SPECIFIES (8) HOLD DOWN CLIPS ON
 TWO SIDES. CLARIFY HOW ARE THE (8) CLIPS INSTALLED ON
 TWO SIDES ONLY. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CALCULATIONS TO HAVE THE ENGINEER'S SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-17 Cont ID  
Sent By gjohnson Date 2017-07-17 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2017-07-17 Time 11:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-07-25 Cont ID  
Sent By jgomez Date 2017-07-25 Time 18:37 Rev Time 0.00
Received By jgomez Date 2017-07-25 Time 18:37 Sent To  
Notes
2017-07-25 18:38:21SHINGLES FL10124-R19.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-11 Cont ID  
Sent By njwira Date 2017-08-11 Time 13:52 Rev Time 0.00
Received By njwira Date 2017-08-11 Time 09:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-06 Cont ID  
Sent By njwira Date 2017-07-06 Time 16:38 Rev Time 0.00
Received By njwira Date 2017-07-06 Time 14:13 Sent To  
Notes
2017-07-06 16:39:357/6/17- PASSED
  
 REQUIRED
 LANDSCAPE PERMIT PRIOR TO CO
 DRIVEWAY PERMIT PRIOR TO CO
  
 DRIVEWAY EXCEEDS 992.44SQFT. OF REQUIRED PERVIOUS
 SURFACE IN THE FRONT SETBACK
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved