2017-08-22 18:21:30 | REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) (PREVIOUS COMMENT) SPECIFY THE DESIGN DATA ON THE |
| PLANS. PROVIDE THE APPLICABLE CODES, OCCUPANCY TYPE AND |
| TYPE OF CONSTRUCTION. FBC-R301 ( THIS IS AN R-3 |
| OCCUPANCY TYPE AND TYPE VB CONSTRUCTION. ) |
| |
| 2) (PREVIOUS COMMENT) FBC-R314.3.1 ALTERATIONS, REPAIRS |
| AND ADDITIONS. WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. SHOW THE |
| SMOKE ALARMS ON THE PLANS. |
| |
| 3) (PREVIOUS COMMENT) PROVIDE A DETAIL SHOWING HOW THE |
| MASTER BEDROOM WALL WILL BE FILLED IN WHEN THE SLIDING |
| GLASS DOOR IS REMOVED. FBC-R601 |
| |
| 4) (PREVIOUS COMMENT)THE PROPOSED FAMILY ROOM THAT IS |
| SHOWN ON THE PLANS IS CURRENTLY A SCREENED PORCH. THE |
| INSTALLATION OF THE SLIDING GLASS DOORS AT THE EXTERIOR |
| OF THE SCREEN PORCH ( UNDER PERMIT # 17060843 ) AND THE |
| PROPOSED REMOVAL OF THE DOORS BETWEEN THE PORCH AND THE |
| EXISTING LIVING SPACE WILL CONVERT THE PORCH TO |
| CONDITIONED SPACE. FBC ENERGY CONSERVATION SECTION |
| R101.4.5 REQUIRES ANY UNCONDITIONED SPACE THAT IS |
| ALTERED TO BECOME CONDITIONED SPACE TO BE BROUGHT INTO |
| FULL COMPLIANCE WITH THE ENERGY CODE. SUBMIT TWO SETS |
| OF FORMS AND DOCUMENTS TO SHOW COMPLIANCE. FBC ENERGY |
| CONSERVATION SECTION R103. |
| |
| 5) (PREVIOUS COMMENT) SHOW THE EXTERIOR WALL AND |
| CEILING INSULATION FOR THE ENCLOSED PORCH ( PROPOSED |
| FAMILY ROOM ) ON THE PLANS. FBC ENERGY CONSERVATION |
| SECTION 402. |
| |
| 6) (PREVIOUS COMMENT) THE PLANS INDICATE THAT |
| PREVIOUSLY UNCONDITIONED SPACE IS BEING CONVERTED TO |
| HABITABLE SPACE. PROVIDE AREA TABULATIONS ON THE PLANS |
| TO SHOW THE SQUARE FOOTAGE OF EXISTING AND PROPOSED |
| CONDITIONED AND UNCONDITIONED AREAS. FBC 107.2.1 THIS |
| INFORMATION IS PROVIDED ON THE PBC PROPERTY APPRAISERS |
| WEBSITE. |
| |
| 7) (PREVIOUS COMMENT) THE PLANS ARE REQUIRED TO BE |
| REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEES. BEFORE A |
| PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE |
| PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF |
| PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH |
| COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE |
| IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT MUST BE |
| RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE THE |
| BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| |
| 8) (PREVIOUS COMMENT)THE VALUATION FOR THIS WORK |
| APPEARS TO BE LOW. SUBMIT A COPY OF THE SIGNED |
| CONTRACT. FBC 109.3 BUILDING PERMIT VALUATION. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |