Plan Review Details - Permit 17061121
Plan Review Stops For Permit 17061121
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By jwitmer Date 2017-08-15 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2017-08-15 Time 07:15 Sent To  
Notes
2017-08-15 07:45:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061121
 ADD: 1617 N. FLAGLER DR. / SUITE NUMBER 902
 CONT: ED?S ISLAND TIME SERVICES INC.
 TEL: 561-541-0004
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUG. 15/ 2017
  
 ACTION: BUILDING PROVISO
  
 1) ALL NEW INTERIOR WALL STUDS ARE TO BE EITHER METAL
 STUDS OR FIRE RETARDANT TREATED STUDS PER 2014 FBC-B
 SECTION 603.1.1(1.1). NONBEARING PARTITIONS WHERE THE
 REQUIRED FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 15:50 Rev Time  
Received By jwitmer Date 2017-07-06 Time 15:33 Sent To  
Notes
2017-07-06 15:50:372014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061121
 ADD: 1617 N. FLAGLER DR. / SUITE NUMBER 902
 CONT: ED?S ISLAND TIME SERVICES INC.
 TEL: 561-541-0004
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 06/ 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE COMPLIANCE WITH THE 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 2) THE PLANS DO NOT REFLECT TO WHICH CODES THEY WERE
 CREATED. 2014 FBC-B AND 2014 FBC-EXISTING BUILDING
 CODE, LEVEL II ALTERATION.
  
 3) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN PROVIDING THE
 FOLLOWING INFORMATION
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY TYPE
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503)
 FIRE SPRINKLERED? FIRE SPRINKLERS REQUIRED?
 OCCUPANT LOAD
  
 4) THE PERMIT APPLICATION INDICATES THE (2) BATHROOMS
 ARE TO BE REMODELED. THE PLANS DO NOT INDICATE IF THE
 FLOOR TILE IS GOING TO BE REMOVED, IF SO THEN
 COMPLIANCE WITH FLOOR INSULATION WILL BE REQUIRED.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 16:26 Rev Time 0.00
Received By jpearson Date 2017-08-23 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 08:35 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 08:35 Sent To  
Notes
2017-08-15 08:34:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 PREVIOUS COMMENTS NOT ADDRESSED, SEE BELOW;
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5
 2. SHOW ON PLAN THE LOCATION OF ANY EXISTING SMOKE
 ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 907.2.11
 3. SHOW ON PLAN ANY NEW OR ALTERED CIRCUITS AND OUTLETS
 REQUIRED FOR WALL SPACE IN NEW WALLS. NEC 210.52
 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED
 CIRCUITS, SHOW WIRE AND BREAKER SIZE, INDICATE AFCI OR
 GFCI PROTECTION AS REQUIRED. NEC 210.8, 210.12, 215.5;
 FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By jpearson Date 2017-07-11 Time 09:39 Rev Time 0.00
Received By jpearson Date 2017-07-11 Time 09:39 Sent To P
Notes
2017-07-11 09:46:08CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5
 2. SHOW ON PLAN THE LOCATION OF ANY EXISTING SMOKE
 ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 907.2.11
 3. SHOW ON PLAN ANY NEW OR ALTERED CIRCUITS AND OUTLETS
 REQUIRED FOR WALL SPACE IN NEW WALLS. NEC 210.52
 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED
 CIRCUITS, SHOW WIRE AND BREAKER SIZE, INDICATE AFCI OR
 GFCI PROTECTION AS REQUIRED. NEC 210.8, 210.12, 215.5;
 FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By wjolin Date 2017-08-16 Time 13:05 Rev Time 0.00
Received By wjolin Date 2017-08-16 Time 13:04 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-28 Cont ID  
Sent By wjolin Date 2017-06-28 Time 11:04 Rev Time 0.00
Received By wjolin Date 2017-06-28 Time 10:59 Sent To  
Notes
2017-06-28 11:04:26FIRE SPRINKLER SYSTEM COVERAGE WILL NEED TO BE MODIFIED
 BY A LICENSED FIRE PROTECTION CONTRACTOR TO ACCOMMODATE
 NEW INTERIOR WALL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 16:28 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 11:29 Sent To  
Notes
2017-08-23 11:30:08RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 14:59 Rev Time 0.00
Received By gjohnson Date 2017-08-07 Time 13:22 Sent To  
Notes
2017-08-08 13:22:34B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-12 Cont ID  
Sent By tklarge Date 2017-07-12 Time 10:11 Rev Time 0.00
Received By tklarge Date 2017-06-26 Time 10:55 Sent To  
Notes
2017-06-27 10:55:22B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By jwitmer Date 2017-07-06 Time 15:31 Rev Time 0.00
Received By jwitmer Date 2017-07-06 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-08-16 Cont ID  
Sent By ccole Date 2017-08-16 Time 15:43 Rev Time 0.00
Received By ccole Date 2017-08-16 Time 15:43 Sent To  
Notes
2017-08-16 15:44:46SEPARATE PERMIT REQUIRED FOR MECHANICAL ALTERATIONS
 CCOLE- 8/16/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By ccole Date 2017-07-06 Time 11:56 Rev Time 0.00
Received By ccole Date 2017-07-06 Time 11:56 Sent To  
Notes
2017-07-06 12:07:421ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17061121
 7/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PLANS DO NOT PROVIDE ADEQUATE
 INFORMATION TO PERFORM A FULL REVIEW. PLEASE REVIEW THE
 FOLLOWING WEST PALM BEACH AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2) PROVIDE ON THE PLAN A LIST CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT-
 SECTION 107.2.1
  
 3) IDENTIFY ALL ROOMS AND SPACES SHOWN ON THE PLANS-
 107.2.1.
  
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 5) SHOW ALL ALTERATIONS TO THE EXISTING AC SYSTEM
 REQUIRED TO PROVIDE BALANCED AIR FLOW TO THE NEW ROOMS-
 SECTION 601.5.
  
 6) PROVIDE BATHROOM EXHAUST AT A RATE OF 50 CFMS FOR
 INTERMITTENT USE, OR 20 CFMS FOR CONTINOUS USE- TABLE
 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By gjohnson Date 2017-08-21 Time 14:58 Rev Time 0.00
Received By gjohnson Date 2017-08-21 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By tklarge Date 2017-07-12 Time 10:11 Rev Time 0.00
Received By tklarge Date 2017-07-12 Time 10:10 Sent To  
Notes
2017-07-12 10:11:16CLARIFY ON THE PLANS WHAT THE SCOPE OF THE PLUMBING
 WORK IS THAT WILL BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  