Plan Review Details - Permit 17061110
Plan Review Stops For Permit 17061110
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-26 Cont ID  
Sent By rmcdouga Date 2017-07-26 Time 13:19 Rev Time 0.00
Received By rmcdouga Date 2017-07-26 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-13 Cont ID  
Sent By rmcdouga Date 2017-07-13 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2017-07-13 Time 07:47 Sent To  
Notes
2017-07-13 11:37:33PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS FOR
 THE GENERATOR SLAB AND THE GENERATOR TO SLAB ANCHORING.
 FS 471.025 AND RULE FAC 61G15-23.003 REQUIRES THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THE
 DRAWINGS, SCANS, FACSIMILES, DIGITALLY CREATED OR
 COPIED SIGNATURES SHALL NOT BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-10 Cont ID  
Sent By rmcdouga Date 2017-07-10 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2017-07-10 Time 08:18 Sent To  
Notes
2017-07-10 08:29:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS FOR
 THE GENERATOR SLAB AND THE GENERATOR TO SLAB ANCHORING.
 THE ONES THAT WERE SUBMITTED ARE MISSING PARTS OF THE
 PAGES. FS 471.025 AND RULE FAC 61G15-23.003 REQUIRES
 THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THE
 DRAWINGS, SCANS, FACSIMILES, DIGITALLY CREATED OR
 COPIED SIGNATURES SHALL NOT BE USED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-12 Cont ID  
Sent By jleahy Date 2017-07-12 Time 14:37 Rev Time 0.00
Received By jleahy Date 2017-07-12 Time 14:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By jleahy Date 2017-07-06 Time 06:37 Rev Time 0.00
Received By jleahy Date 2017-07-06 Time 06:37 Sent To  
Notes
2017-07-06 06:39:55FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR WORK SHOWN TOO LOW.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION
 SHALL BE SET BY THE BUILDING
  
 PLEASE SUBMIT A SIGNED CONTRACT WITH CUSTOMER, OR CITY
 WILL VALUE THE WORK AT $25,000.00
  
 JUNCTION BOX UNDER TRANSFER SWITCH TOO SMALL NEEDS TO
 BE 16 X 16 MINIMUM.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-10 Cont ID  
Sent By rmcdouga Date 2017-07-10 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2017-07-10 Time 08:18 Sent To  
Notes
2017-07-10 08:28:54SEPARATE PERMIT, APPLICATION, PLANS AND REVIEW IS
 REQUIRED FOR GAS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-26 Cont ID  
Sent By rmcdouga Date 2017-07-26 Time 13:19 Rev Time 0.00
Received By rmcdouga Date 2017-07-24 Time 10:32 Sent To  
Notes
2017-07-25 10:32:48RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-13 Cont ID  
Sent By rmcdouga Date 2017-07-13 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2017-07-10 Time 10:26 Sent To  
Notes
2017-07-12 10:26:29RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-10 Cont ID  
Sent By rmcdouga Date 2017-07-10 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2017-06-26 Time 13:49 Sent To  
Notes
2017-06-27 13:50:08ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-06-30 Cont ID  
Sent By njwira Date 2017-06-30 Time 09:56 Rev Time 0.00
Received By njwira Date 2017-06-28 Time 08:38 Sent To  
Notes
***NONE***