Plan Review Details - Permit 17061090
Plan Review Stops For Permit 17061090
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-08 Cont ID  
Sent By cthroop Date 2017-08-08 Time 10:14 Rev Time 0.00
Received By cthroop Date 2017-08-08 Time 10:13 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-07-11 Cont ID  
Sent By cthroop Date 2017-07-10 Time 09:07 Rev Time 0.00
Received By cthroop Date 2017-07-10 Time 09:03 Sent To  
Notes
2017-07-10 09:09:58STRUCTURAL ATTACHMENT TO BE VERIFIED BY FIELD
 INSPECTOR. CT
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By jpearson Date 2017-08-07 Time 07:57 Rev Time 0.00
Received By jpearson Date 2017-08-07 Time 07:56 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By jpearson Date 2017-06-28 Time 07:43 Rev Time 0.00
Received By jpearson Date 2017-06-28 Time 07:43 Sent To  
Notes
2017-06-28 07:57:25 
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. IN SUBMITTED SPEC SHEETS, NOR ON PLAN, IS THE MODEL
 OF THE TRANSFER SWITCH OR GENERATOR IDENTIFIED. PROVIDE
 DETAILS OF GENERATOR ON PLAN, INDICATE WHICH MODEL OF
 TRANSFER SWITCH AND GENERATOR WILL BE USED ON SPEC
 SHEETS, AND SHOW LOCATION OF TRANSFER SWITCH (LOCATED
 INSIDE OR OUTSIDE). FBC 107.2.1; NEC 702.4, 110.9
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-11 Cont ID  
Sent By pleduc Date 2017-08-11 Time   Rev Time 0.00
Received By pleduc Date 2017-08-10 Time 17:03 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By pleduc Date 2017-06-29 Time   Rev Time 0.00
Received By pleduc Date 2017-06-28 Time 14:48 Sent To B
Notes
2017-06-29 12:30:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) WILL THIS PROPOSED GENERATOR PROVIDE BACKUP
 EMERGENCY POWER TO ANY LIFE SAFETY SYSTEM.I.E FIRE
 ALARM OR FIRE SPRINKLER?
  
 IF SO, IT SHALL COMPLY WITH NFPA 110. PLEASE PROVIDE AN
 APPLICABLE NOTE AND ENSURE COMPLIANCE.
  
  
  
 2) THE ATTACHED DATA SHEETS INDICATE THE PROPOSED WILL
 BE FUELED BY LP AND/OR NG. PLEASE CONFIRM.
  
 THE FUEL SUPPLY SHALL BE UNDER SEPARATE PERMIT IF NOT
 DONE BY THIS CONTRACTOR OR SPECIFICALLY INDENTIFIED
 UNDER THIS PERMIT WILL ALL APPLICABLE DRAWINGS SHOWING
 LOCATION AND SIZE OF ALL PIPE CONNECTIONS, LOCATION AND
 SIZE OF PROPOSED PIPE, DEPTH OF COVER, ETC., AND
 EQUIPMENT SPEC SHEETS.
  
  
  
 3) THE ARE NO DRAWINGS OF FOUNDATION PLANS OR HOW IT
 WILL BE SECURED TO THE FOUNDATION. THERE ARE NO
 DIMENSIONS FROM THE BUILDING.
  
 PLEASE PROVIDEAND ENSURE COMPLIANCE WITH THE APPLICABLE
 CODE.
  
  
  
 4) PLEASE PROVIDE DIMENSIONS OF THE NEAREST WINDOW AND
 OR DOOR TO ENSURE THE SEPARATION DISTANCES REQUIRED
 THAT AVOIDS FUMES ENTERING THE BUILDING. THERE IS NO
 INDICATION OF EXHAUST LOCTION.
  
 PLEASE PROVIDE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-16 Cont ID  
Sent By lmarchan Date 2017-08-16 Time 10:02 Rev Time 0.00
Received By lmarchan Date 2017-07-31 Time 15:51 Sent To  
Notes
2017-08-01 15:51:37RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-10 Cont ID  
Sent By cthroop Date 2017-07-10 Time 09:10 Rev Time 0.00
Received By cthroop Date 2017-06-23 Time 09:49 Sent To  
Notes
2017-06-26 09:49:35ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-03 Cont ID  
Sent By njwira Date 2017-08-03 Time 16:05 Rev Time 0.00
Received By njwira Date 2017-08-02 Time 08:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-06-26 Cont ID  
Sent By njwira Date 2017-06-26 Time 17:07 Rev Time 0.00
Received By njwira Date 2017-06-26 Time 16:51 Sent To E
Notes
***NONE***