Plan Review Details - Permit 17061090
Plan Review Stops For Permit 17061090 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2017-08-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-08-08 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-08-08 |
Time |
10:13 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2017-07-11 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-07-10 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-07-10 |
Time |
09:03 |
Sent To |
|
|
Notes |
2017-07-10 09:09:58 | STRUCTURAL ATTACHMENT TO BE VERIFIED BY FIELD | | INSPECTOR. CT | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2017-08-07 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-08-07 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-08-07 |
Time |
07:56 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-06-28 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-06-28 |
Time |
07:43 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-06-28 |
Time |
07:43 |
Sent To |
|
|
Notes |
2017-06-28 07:57:25 | | | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. IN SUBMITTED SPEC SHEETS, NOR ON PLAN, IS THE MODEL | | OF THE TRANSFER SWITCH OR GENERATOR IDENTIFIED. PROVIDE | | DETAILS OF GENERATOR ON PLAN, INDICATE WHICH MODEL OF | | TRANSFER SWITCH AND GENERATOR WILL BE USED ON SPEC | | SHEETS, AND SHOW LOCATION OF TRANSFER SWITCH (LOCATED | | INSIDE OR OUTSIDE). FBC 107.2.1; NEC 702.4, 110.9 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2017-08-11 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-08-11 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-08-10 |
Time |
17:03 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-06-29 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-06-29 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-06-28 |
Time |
14:48 |
Sent To |
B |
|
Notes |
2017-06-29 12:30:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) WILL THIS PROPOSED GENERATOR PROVIDE BACKUP | | EMERGENCY POWER TO ANY LIFE SAFETY SYSTEM.I.E FIRE | | ALARM OR FIRE SPRINKLER? | | | | IF SO, IT SHALL COMPLY WITH NFPA 110. PLEASE PROVIDE AN | | APPLICABLE NOTE AND ENSURE COMPLIANCE. | | | | | | | | 2) THE ATTACHED DATA SHEETS INDICATE THE PROPOSED WILL | | BE FUELED BY LP AND/OR NG. PLEASE CONFIRM. | | | | THE FUEL SUPPLY SHALL BE UNDER SEPARATE PERMIT IF NOT | | DONE BY THIS CONTRACTOR OR SPECIFICALLY INDENTIFIED | | UNDER THIS PERMIT WILL ALL APPLICABLE DRAWINGS SHOWING | | LOCATION AND SIZE OF ALL PIPE CONNECTIONS, LOCATION AND | | SIZE OF PROPOSED PIPE, DEPTH OF COVER, ETC., AND | | EQUIPMENT SPEC SHEETS. | | | | | | | | 3) THE ARE NO DRAWINGS OF FOUNDATION PLANS OR HOW IT | | WILL BE SECURED TO THE FOUNDATION. THERE ARE NO | | DIMENSIONS FROM THE BUILDING. | | | | PLEASE PROVIDEAND ENSURE COMPLIANCE WITH THE APPLICABLE | | CODE. | | | | | | | | 4) PLEASE PROVIDE DIMENSIONS OF THE NEAREST WINDOW AND | | OR DOOR TO ENSURE THE SEPARATION DISTANCES REQUIRED | | THAT AVOIDS FUMES ENTERING THE BUILDING. THERE IS NO | | INDICATION OF EXHAUST LOCTION. | | | | PLEASE PROVIDE. | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-08-16 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2017-08-16 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-07-31 |
Time |
15:51 |
Sent To |
|
|
Notes |
2017-08-01 15:51:37 | RESUB ROUTED TO NJWIRA VIA ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-07-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-07-10 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-06-23 |
Time |
09:49 |
Sent To |
|
|
Notes |
2017-06-26 09:49:35 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2017-08-03 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-08-03 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-08-02 |
Time |
08:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2017-06-26 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-06-26 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-06-26 |
Time |
16:51 |
Sent To |
E |
|
Notes |
|
|
|