Plan Review Details - Permit 17061037
Plan Review Stops For Permit 17061037
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-04 Cont ID  
Sent By shill Date 2017-08-04 Time 07:13 Rev Time 0.00
Received By shill Date 2017-08-04 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-27 Time 15:18 Rev Time 0.00
Received By shill Date 2017-06-27 Time 15:16 Sent To  
Notes
2017-06-27 15:16:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROVIDE A COPY OF THE CONTRACT, FBC 109. A COST
 BREAKDOWN MAY BE REQUIRED.
  
 2. PROVIDE THE FOLLOWING TEST REPORTS FOR THE FLOORING
 UNDERLAYMENT:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-30 Cont ID  
Sent By jpearson Date 2017-06-30 Time 10:26 Rev Time 0.00
Received By jpearson Date 2017-06-30 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-26 Cont ID  
Sent By scaldero Date 2017-06-26 Time 14:19 Rev Time 0.00
Received By scaldero Date 2017-06-26 Time 14:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-08-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-16 Time 14:48 Sent To  
Notes
2017-08-17 14:48:59RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-04 Cont ID  
Sent By shill Date 2017-08-04 Time 07:13 Rev Time 0.00
Received By shill Date 2017-07-27 Time 15:40 Sent To  
Notes
2017-07-28 15:40:47RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2017-06-22 Time 16:04 Sent To  
Notes
2017-06-23 16:04:35B14

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-18 Cont ID  
Sent By ccole Date 2017-08-18 Time 15:10 Rev Time 0.00
Received By ccole Date 2017-08-18 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-07-31 Cont ID  
Sent By ccole Date 2017-07-31 Time 09:36 Rev Time 0.00
Received By ccole Date 2017-07-31 Time 09:36 Sent To  
Notes
2017-07-31 09:42:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061037
 7/31/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW EXHAUST HOOD HAS A CAPACITY OF 600 CFMS
 WHICH REQUIRES MAKEUP AIR TO BE PROVIDED PER SECTION
 505.2. PLEASE REVISE THE PLAN TO SHOW HOW THE AIR WILL
 BE PROVIDED, AND SHOW THE EXHAUST DUCT RUN AND POINT OF
 CONNECTION TO THE EXISTING DUCT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-03 Cont ID  
Sent By ccole Date 2017-07-03 Time 15:47 Rev Time 0.00
Received By ccole Date 2017-07-03 Time 15:47 Sent To  
Notes
2017-07-03 15:57:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061037
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED AT A
 RATE OF 100 CFMS PER SQ. FT. FOR INTERMITTENT OPERATION
 OR 25 CFMS PER SQ. FT. FOR CONTINUOUS OPERATION- TABLE
 403.3
  
 2) PROVIDE AN EXHAUST HOOD AND DUCT SYSTEM FOR THE
 COOKTOP. PROVIDE DETAILS ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 505.2.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 DRYER AND SHOW EXHAUST DUCT ALTERATIONS- SECTION 504.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2017-07-06 Time 14:25 Sent To  
Notes
***NONE***