Plan Review Details - Permit 17061034
Plan Review Stops For Permit 17061034
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-09 Cont ID  
Sent By   Date 2017-08-09 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2017-08-09 Time 16:58 Sent To  
Notes
2017-08-09 17:01:582014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061034
 ADD: 310 S. DIXIE HWY. SUITE 300 & 302
 CONT: TBD/ TO BE DETERMINED
 TEL: 973-941-7444
 E-MAIL: ?????? WE PREFER E-MAIL FOR CORRESPONDENCE!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. AUGUST 09/2017
 ACTION: DENIED
  
 1) BUILDING PROVISO: PLEASE SHOW COMPLIANCE WITH CHECK
 OUT COUNTER: 2014 FBC-B 904.3.2 COUNTER. THE COUNTER
 SURFACE HEIGHT SHALL BE 38 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. THE TOP OF THE COUNTER EDGE
 PROTECTION SHALL BE 2 INCHES MAXIMUM ABOVE THE TOP OF
 THE COUNTER SURFACE ON THE AISLE SIDE OF THE CHECK-OUT
 COUNTER.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-31 Cont ID  
Sent By jwitmer Date 2017-07-31 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2017-07-31 Time 07:01 Sent To  
Notes
2017-07-31 07:39:152014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061034
 ADD: 310 S. DIXIE HWY. SUITE 300 & 302
 CONT: TBD/ TO BE DETERMINED
 TEL: 973-941-7444
 E-MAIL: ?????? WE PREFER E-MAIL FOR CORRESPONDENCE!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JULY 31/2017
 ACTION: DENIED
  
 1) ONLY ONE SET OF PRODUCT APPROVALS!!! NEED A SECOND
 SET FOR THE @ND SET OF PLANS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.1 SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, GEOTECHNICAL REPORT AND OTHER
 DATA SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION.
  
  
  
 BUILDING PROVISO: PLEASE SHOW COMPLIANCE WITH CHECK OUT
 COUNTER: 2014 FBC-B 904.3.2 COUNTER. THE COUNTER
 SURFACE HEIGHT SHALL BE 38 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. THE TOP OF THE COUNTER EDGE
 PROTECTION SHALL BE 2 INCHES MAXIMUM ABOVE THE TOP OF
 THE COUNTER SURFACE ON THE AISLE SIDE OF THE CHECK-OUT
 COUNTER.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By jwitmer Date 2017-06-29 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 15:39 Sent To  
Notes
2017-06-29 09:26:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061034
 ADD: 310 S. DIXIE HWY. SUITE 300 & 302
 CONT: TBD/ TO BE DETERMINED
 TEL: 973-941-7444
 E-MAIL: ?????? WE PREFER E-MAIL FOR CORRESPONDENCE!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 29
 ACTION: DENIED
  
 1) SHEET D-1:
 1A) SHEET D-1 SHOWS THE FRONT ENTRY WALL (BOWED WALL)
 BEING REMOVED AN APPROXIMATE 30 FOOT SECTION OF WALL.
 SHEET 1.0A SHOWS A STRAIGHT SECTION OF WALL WITH
 APPROX.. A 45 DEGREE TURN AND A 42 INCH SECTION OF
 WALL, 2 WINDOWS AND ONE DOOR AND SHEET 1.3A THE
 ELEVATION SHEET SHOWS A TRANSOM HORIZONTAL MULLION,
 WINDOWS AND DOOR. PLEASE PROVIDE A CUT SECTION THROUGH
 THIS PORTION OF NEW WALL. ON THE EXTERIOR CEILING THERE
 WILL BE CEILING MISSING SINCE THE BOWED FRONT WAS
 REMOVED, HOW WILL THIS NEW WALL SECTION TIE INTO THE
 FLOOR FRAMING SYSTEM? THE PLANS INDICATE USE THE
 EXISTING HEADER? TYPE OF MATERIAL? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED? THIS WALL SECTION WILL BE PART
 OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) PLEASE
 SHOW CONNECTIONS FBC-B 1609.6.4.
  
 1B) THIS SAME WALL SECTION SHOWS THE TRANSOM ABOVE AND
 A HORIZONTAL FRAMING MEMBER SEPARATING THE TRANSOM
 ABOVE FROM THE DOOR AND WINDOWS BELOW. WHAT SUPPORTS
 THE HORIZONTAL FRAMING MEMBER AT THE 45 DEGREE TURN? IS
 THERE A COLUMN NOT SHOWN, OR A 45 DEGREE ALUMINUM
 MULLION? PLEASE SHOW THE VERTICAL FRAMING MEMBER AS
 WELL, AND SHOW HOW BOTH THE HORIZONTAL AND VERTICAL
 FRAMING MEMBERS ARE GOING TO BE ANCHORED. MAYBE
 CONSIDERED AS MWFRS OR COMPONENTS AND CLADDING
 DEPENDING ON THE MATERIALS USED AND IF THERE IS PRODUCT
 APPROVALS.
  
 1C) SHEET 1.3A SECTION 3-1.3A SHOWS THE TRANSOM LITES
 AND HEADER NOT BEING MOVED, THEN WHAT MATERIAL WILL BE
 USED FOR INFILL BETWEEN THE BOWED SECTION ABOVE THAT
 STAYS AND THE NEW SECTION BELOW THAT SHOWS A STRAIGHT
 SECTION OF WALL WITH A 45 DEGREE TURN AN 42 INCH
 SECTION OF WALL?107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
 IF THIS DETAIL IS NOT CORRECTLY ILLUSTRATED AND THE
 TRANSOMS ARE TO BE REUSED AND REINSTALLED PLEASE
 PROVIDE THE INFORMATION ON THE WINDOW SASH, HOW WILL
 THEY BE RE-INSTALLED, DOES THE PRESENT GLAZING MEET THE
 WIND DESIGN PRESSURES OF TODAY, AND WITH BEING
 REINSTALLED HOW WILL THEY MEET THE REQUIREMENTS FOR
 LARGE MISSILE IMPACT TESTING OR BE SHUTTERED.
 1609.6.4.4 APPLICATIONS OF WIND PRESSURE.
 2404.1 VERTICAL GLASS.
 2) SHEET 1.3A THE WIND DESIGN CRITERIA IS GIVEN
 CORRECTLY BUT NOT THE PRESSURES ASSOCIATED WITH THE
 DESIGN.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (5.) DESIGN WIND
 PRESSURES.
 3) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) SHEET 1.0A DOOR # 1 IS MISSING ON THE PLANS & DOOR #
 6 IS THIS A INTERIOR DOOR NEEDING FIRE RATING OR IS
 THIS A EXTERIOR DOOR? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 7) SHEET1.2A THE REAR EXIT DOOR FROM THE DINING AREA
 DOES NOT HAVE THE REQUIRED 18 INCHES AT THE LATCH SIDE
 OF THE DOOR. PLEASE SHOW COMPLIANCE WITH: 2014 FBC
 ACCESSIBILITY CODE 404.2.4 OR
 404.3 AUTOMATIC AND POWER-ASSISTED DOORS AND GATES.
 404.3.2 MANEUVERING CLEARANCE.
 CLEARANCES AT POWER-ASSISTED DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. CLEARANCES AT AUTOMATIC DOORS AND
 GATES WITHOUT STANDBY POWER AND SERVING AN ACCESSIBLE
 MEANS OF EGRESS SHALL COMPLY WITH 404.2.4.
  
 EXCEPTION: WHERE AUTOMATIC DOORS AND GATES REMAIN OPEN
 IN THE POWER-OFF CONDITION, COMPLIANCE WITH 404.2.4
 SHALL NOT BE REQUIRED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-31 Cont ID  
Sent By jpearson Date 2017-07-31 Time 13:37 Rev Time 0.00
Received By jpearson Date 2017-07-31 Time 13:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By jleahy Date 2017-07-05 Time 08:50 Rev Time 0.00
Received By jleahy Date 2017-07-05 Time 08:50 Sent To  
Notes
2017-07-05 08:56:03FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND
 BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS
 AND JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE
 FEET (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING
 HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL DEVICES
 SHALL BE
 INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30
 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL
 EITHER
 BE MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY
 TURN THE LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By scaldero Date 2017-07-27 Time 08:18 Rev Time 0.00
Received By scaldero Date 2017-07-27 Time 08:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By scaldero Date 2017-06-26 Time 14:45 Rev Time 0.00
Received By scaldero Date 2017-06-26 Time 14:20 Sent To  
Notes
2017-06-26 14:45:53PERMIT # 17061034
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION.
  
 2) SHEET 1.2A: OCCUPANT LOAD CALCULATIONS DO NOT MATCH
 DETAILS PROVIDED ON PLANS. DINING AREA IS LISTED AS 157
 SQ. FT. WITH AN OCC LOAD OF 10.
 DRAWINGS SHOW / OUTLINE 209 SQ FT OCCUPIED BY TABLES
 AND CHAIRS, WITH SEATING FOR A MINIMUM OF 27.
 SHEET C-1 LISTS NUMBER OF SEATS AS "26". PLEASE REVIEW
 AND REVISE DETAILS TO SHOW ACCURATE CALCULATIONS AND
 OCCUPANY LOADS ON ALL RELEVANT SHEETS.
  
 3) SHEET 1.1A: PER EQUIPMENT PLAN DETAILS, ONLY
 EQUIPMENT THAT WILL BE USED FOR HEATING OF FOODS ARE
 TWO (2) RICE COOKERS.
 PLEASE VERIFY AND CONFIRM THAT NO ADDITIONAL COOKING
 EQUIPMENT WILL BE USED.
 PLEASE NOTE THAT ANY COOKING THAT MAY PRODUCE GREASE
 LADEN VAPORS WILL REQUIRE INSTALLATION OF AN APPROVED
 HOOD SUPPRESSION SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-08-08 Cont ID  
Sent By fmittner Date 2017-08-08 Time 08:37 Rev Time 0.00
Received By fmittner Date 2017-08-08 Time 08:37 Sent To Z
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-06-30 Cont ID  
Sent By fmittner Date 2017-06-30 Time 13:56 Rev Time 0.00
Received By fmittner Date 2017-06-30 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-09 Cont ID  
Sent By   Date 2017-08-09 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-24 Time 13:14 Sent To  
Notes
2017-08-09 15:07:01TO LAURA MERCHANT
2017-07-25 13:15:02B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 17:34 Rev Time 0.00
Received By gjohnson Date 2017-06-22 Time 13:55 Sent To  
Notes
2017-06-23 13:55:29B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-29 Cont ID  
Sent By jwitmer Date 2017-06-29 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 15:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 16:43 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 16:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-03 Cont ID  
Sent By ccole Date 2017-07-03 Time 15:19 Rev Time 0.00
Received By ccole Date 2017-07-03 Time 15:19 Sent To  
Notes
2017-07-03 15:37:241ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17061034
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ.
 FT. IS REQUIRED FOR THE KITCHEN- TABLE 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-03 Cont ID  
Sent By gjohnson Date 2017-08-03 Time 17:51 Rev Time 0.00
Received By gjohnson Date 2017-08-03 Time 17:51 Sent To  
Notes
2017-08-03 17:53:44PROVISO:
 PROVIDE APPROVED BY BUILDING DEPT. WATER ISOMETRIC
 DRAWING FOR 2ND ROUGH INSPECTION

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-06 Cont ID  
Sent By gjohnson Date 2017-07-06 Time 17:20 Rev Time 0.00
Received By gjohnson Date 2017-07-06 Time 14:24 Sent To  
Notes
2017-07-06 17:33:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. VENT REQUIRED ON PIPING SERVICING ICE MACHINE AN
 COLD PAN. PER FBC PL 901.2.1
  
 2. SHOW COMPLIANCE WITH FBC ACC
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 604 WATER CLOSETS
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.6 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE
 COMPARTMENTS COMPLYING WITH 604.8.2.
  
 604.5 GRAB BARS.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 606 LAVATORIES AND SINKS
  
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By aaponte Date 2017-08-09 Time 15:06 Rev Time 0.00
Received By aaponte Date 2017-08-09 Time 15:06 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-06-29 Cont ID  
Sent By aaponte Date 2017-06-29 Time 16:52 Rev Time 0.00
Received By aaponte Date 2017-06-29 Time 15:43 Sent To  
Notes
***NONE***