Plan Review Details - Permit 17061002
Plan Review Stops For Permit 17061002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By shill Date 2017-08-15 Time 16:45 Rev Time 0.00
Received By shill Date 2017-08-15 Time 16:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By shill Date 2017-07-24 Time 12:21 Rev Time 0.00
Received By shill Date 2017-07-24 Time 12:05 Sent To  
Notes
2017-07-24 12:21:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. WINDOW REMOVAL IS NOT TYPICALLY PERMITTED WITHOUT A
 PERMIT TO RESTORE THE BUILDING TO A WATERTIGHT
 CONDITION. PLEASE ADDRESS BY DOING ONE OF THE FOLLOWING
 (FBC 107):
  
 REMOVE FROM SCOPE, OR
 REVISE PLAN TO INCLUDE MASONRY INFILL AND WINDOWS, OR
 VIA EMAIL, PROVIDE INFORMATION REGARDING RATIONALE AND
 TIME FRAME (THIS IS NOT PREFERABLE).
  
 2. PLEASE HAVE THE ARCHITECT WHO IS WORKING ON THE PLAN
 CONTACT ME REGARDING EXITING STRATEGY. PER BUILDING
 OFFICIAL, DUE TO THE STAIRS WHICH ARE NOT REMOTELY
 LOCATED IN THIS EXISTING BUILDING (BUILT IN COMPLIANCE,
 LEVEL 3 ALTERATION, CHANGE OF OCCUPANCY TO A HIGHER
 HAZARD CATEGORY), TWO SMOKE DOORS (WITH HOLD OPEN) AND
 A SMOKE CONTROL SYSTEM WILL LIKELY BE REQUIRED.
  
 IT IS UNDERSTOOD THAT THIS WILL BE A PART OF THE
 BUILDING PERMIT, BUT RECOMMENDED TO HAVE THIS RESOLVED
 PRIOR TO PERMIT SUBMITTAL AS APPROVAL BY BUILDING
 OFFICIAL AND FIRE DEPT. WILL BE REQUIRED; FBC EB 805.2
 (2), 1012.4.1(2).
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By wjolin Date 2017-08-16 Time 13:35 Rev Time 0.00
Received By wjolin Date 2017-08-16 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-26 Cont ID  
Sent By scaldero Date 2017-07-26 Time 14:37 Rev Time 0.00
Received By wjolin Date 2017-07-26 Time 14:18 Sent To  
Notes
2017-07-26 14:37:15ALL FIRE PROTECTION, LIFE SAFETY AND DEMOLITION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-16 Cont ID  
Sent By cpuell Date 2017-08-16 Time 14:37 Rev Time 0.00
Received By cpuell Date 2017-08-15 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-26 Cont ID  
Sent By shill Date 2017-07-26 Time 14:48 Rev Time 0.00
Received By shill Date 2017-07-12 Time 09:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By shill Date 2017-08-15 Time 16:47 Rev Time 0.00
Received By shill Date 2017-08-15 Time 16:47 Sent To  
Notes
2017-08-15 16:47:45PROVISO - ANY NEW SHEETS SUBMITTED 3RD REVIEW, IF
 APPLICABLE, REQUIRE REVIEW
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By shill Date 2017-07-26 Time 14:48 Rev Time 0.00
Received By shill Date 2017-07-26 Time 14:48 Sent To  
Notes
2017-07-26 14:49:26PLANS ARE DIGITALLY SIGNED & SEALED IN ACCORDANCE WITH
 FS/FAC. NEW SHEETS SUBMITTED 2ND REVIEW CYCLE REQUIRE
 REVIEW.
 [email protected]
  