Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-07 Cont ID  
Sent By jwitmer Date 2017-10-07 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2017-10-07 Time 08:00 Sent To  
Notes
2017-10-07 08:14:432014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060979
 ADD: 525 S. FLAGLER DR. 3RD FLOOR
 CONT: L J SHEEHAN INC.
 TEL: 561-223-2750
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. OCT. 07/ 2017
  
 ACTION:BUILDING PROVISOS:
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By jwitmer Date 2017-08-25 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2017-08-25 Time 07:46 Sent To  
Notes
2017-08-25 11:04:572014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060979
 ADD: 525 S. FLAGLER DR. 3RD FLOOR
 CONT: L J SHEEHAN INC.
 TEL: 561-223-2750
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 25/ 2017
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) BUILDING PROVISO/ DEFERRED SUBMITTAL: NANA WALL
 SYSTEM. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 5) BUILDING PROVISO/ DEFERRED SUBMITTAL: PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014
 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL
 BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7A) 2ND REQUEST. THE PLANS DO NOT INDICATE IF THERE IS
 PROTECTION FROM DRIVING RAIN. SEE 1ST ROUND OF
 COMMENTS.
 1ST ROUND COMMENTS. 1710.5.1.1FBC-B EXTERIOR WINDOWS
 AND DOORS. (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED
 WHERE THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN
 1 NEED NOT BE TESTED FOR WATER INFILTRATION. THE
 OVERHANG RATIO SHALL BE CALCULATED BY THE FOLLOWING
 EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 7B) PLEASE BE ADVISED WITH THE USE OF NANA WALL SYSTEM,
 IN THE OUTSWING DOOR SYSTEM NOA 15-0226.05 HAS A ADA
 COMPLIANT SILL, AND WITH THE ADA COMPLIANT SILL THERE
 IS A NOTE THAT THE DOORS ARE NOT APPROVED WHERE WATER
 RESISTANCE IS REQUIRED, PAGE 7 OF 8 IN THE NOA. THE
 OTHER SILL HEIGHT OF THE PRODUCT APPROVAL PAGE 6 OF 8
 IS APPROXIMATELY 2 ? INCHES IN HEIGHT. SHEET A2.0.2.
 SHOWS A SILL WITH A HEIGHT OF 4 INCHES, PLEASE HAVE
 NANA WALL PROVIDE A LETTER ON THEIR LETTER HEAD STATING
 A 4 INCH HIGH SILL IS AVAILABLE WITH THIS SYSTEM.
 PLEASE PROVIDE HOW THE 4 INCH SILL IS GOING TO MEET THE
 REQUIREMENTS OF THE ACCESSIBILITY CODE UNDER SECTION
 404.2.4 OF THE 2014 ACCESSIBILITY CODE.
  
 7C) PLEASE NOTE WITH NANA DOOR PRODUCT APPROVAL NOA
 15-0226.05 WILL NOT MEET THE PRESSUES FOR THE DOORS
 LOCATED IN ZONE # 5. SHEET A2.01 INDICATES NEGAITIVE
 PREUUSRES OF - 131.1 FOR 20 SQ. FT. IN ZONE 5. THE
 TECHNICAL SHEET 1OF 8 IN THE NOA INDICATES THE HIGHEST
 NEGATIVE PRESSURES OF -90 TO THE LOWEST NEGATIVE
 PRESSURES OF -70 DEPENDING ON THE PANEL SIZE.
  
 1ST ROUND OF COMMENTS. THERE ARE 2 ISSUES, THE PLANS DO
 NOT PROVIDE A CUT SECTION THROUGH THE INTERIOR FINISH
 FLOOR, TRACK AND THE EXTERIOR FINISH FLOOR WITH NEW
 TILE. SHEET A2.02 DOOR & HARDWARE NOTE NUMBER 14
 INDICATES ALL THRESHOLDS SHALL HAVE NO STEP GREATER
 THAN ? INCH PER A.D.A. REQUIREMENTS. WITH NOT SEEING
 THE PRODUCT APPROVAL FOR THE EURO WALL SYSTEM THIS MAY
 OR MAY NOT BE AN ISSUE BUT A LOT OF THESE DOOR SYSTEMS
 HAVE DISCLAIMERS LIKE, WHEN AN ADA/ FLUSH SILL IS USED,
 THESE DOORS ARE NOT APPROVED FOR THE USE WHERE WATER
 INFILTRATION RESISTANCE IS REQUIRED. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) SHEET A2.01;
 8A-8B) COMPLIED.
  
 8C) 2ND REQUEST. SHEET A2.01. DOOR 328B IN ANY POSITION
 SHALL NOT REDUCE THE REQUIRED WIDTH BY ONE-HALF OF THE
 REQUIRED EGRESS WIDTH. FBC-B 1005.7.1. YOU CAN RECESS
 THE DOOR FURTHER INTO THE CLOSET TO GET THE ONE HALF OF
 THE REQUIRED WIDTH.
  
 1ST ROUND OF COMMENTS. DOOR 328B BLOCKS THE EGRESS
 PATH, MUST COMPLY WITH FBC-B 1005.7 ENCROACHMENT.
 ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION.
 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178
 MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 8D) 2ND REQUEST. PLEASE NOTE THE REVISED PLAN SHOWS THE
 STAIRWELLS AT THE ENDS OF THE BUILDING BUT THERE IS NO
 SEPARATION OF AN ELEVATOR LOBBY FROM THE CORRIDOR. THE
 ELEVATOR LOBBY IS CONTINUOUS SINCE SMOKE CAN GO FROM
 THE ELEVATOR SHAFT AND FILL UP THE CORRIDOR. THAT IS
 WHY YOU EITHER PRESSURIZE THE ELEVATOR SHAFT OR MEET
 ONE OF THE OTHER EXCEPTIONS PROVIDED IN FBC-B 713.14.1
 OR EXCEPTIONS.
  
 1ST ROUND OF COMMENTS. PLEASE PROVIDE AN OVERALL FLOOR
 PLAN FOR THIS FLOOR. IF THE WORK AREA IS OVER 50 % OF
 THE FLOOR PLATE THEN
 PLEASE SHOW COMPLIANCE WITH THE 2014 EXISTING BUILDING
 CODE 803.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING
 ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY
 FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE
 ENCLOSURE REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO
 VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE
 FLOOR. THE 2007 EXISTING COMMENTARY ON THE EXISTING
 BUILDING CODE SPEAKS ABOUT THE FIRST TIME THE CODE
 REQUIRES WORK OUTSIDE OF THE TENANT SPACE. SINCE THE
 DESIGNER OF RECORD IS ALREADY WORKING OUTSIDE OF THE
 TENANT SPACE THIS COMMENT IF OVER 50 % OF THE FLOOR
 PLATE IS BEING CONSIDERED THE WORK AREA THEN THIS
 COMMENT STANDS.
 THE PLANS DO NOT SHOW WHERE EITHER OF THE TENANT SPACES
 HAVE AT LEAST ONE MEANS OF EGRESS WITH NOT GOING
 THROUGH THE ELEVATOR LOBBY. 2014 FBC-B 713.14.1 AND
 EXCEPTIONS 1-7, PLEASE PROVIDE CODE COMPLIANCE.
  
 9-10) COMPLIED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jwitmer Date 2017-07-12 Time 16:54 Rev Time  
Received By jwitmer Date 2017-07-12 Time 11:44 Sent To  
Notes
2017-07-12 16:54:532014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060979
 ADD: 525 S. FLAGLER DR. 3RD FLOOR/ SUITE?
 CONT: L J SHEEHAN INC.
 TEL: 561-223-2750
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 12/ 2017
 ACTION: DENIED
  
 1) PLEASE CORRECT PLANS, SHEET A0.1.1. NOTE NUMBER 31
 MAKES REFERENCE TO THE CITY OF MIAMI FIRE DEPARTMENT
 REGULATIONS. PLEASE UPDATE PLANS TO THE WEST PALM BEACH
 FIRE DEPARTMENT REGULATIONS. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET ALS1.0 THE LIFE SAFETY SHEET INDICATES THE
 OCCUPANT LOAD BEING 123 TOTAL LOAD WHICH REQUIRES 2
 EXITS. THE LIFE SAFETY SHEET REFERENCES THE FBC-B TABLE
 1015.1. AND THE REQUIREMENT FOR 2 EXITS BUT THE PLAN
 ONLY SHOWS ONE STAIRWAY. OTHER NOTES IN THIS SET OF
 PLANS REFERENCES THIS TO BE A 38 STORY BUILDING. THE
 EXIT STAIRWELL WOULD ALSO BE REQUIRED TO BE 2 HOUR FIRE
 RATED EXITS. PLEASE SHOW THE 2ND MEANS OF EXIT.
  
 3) SHEET AD1.0 THE DEMO PLAN NOTE NUMBER 2 INDICATES
 THE EXTERIOR WINDOW AND DOORS ARE TO BE REMOVED. SHEET
 A1.0.1 SHOWS NEW EURO WALL DOOR SYSTEM AND A PAIR OF
 EXTERIOR SWING DOOR BEING REPLACED. SHEET A2.0.1.
 PROVIDES THE WIND DESIGN POSITIVE AND NEGATIVE (VASD)
 FOR WALL ZONES 4 & 5, NOTE # 3 INDICATES WALL ZONE 5 IS
 TO BE 20 FEET WIDE, BUT THERE IS NO REFERENCE TO THIS
 TENANT SPACE IN THE OVERALL RELATIONSHIP OF THE
 BUILDING? IT IS UNKNOWN IF THIS UNIT IS IN ANY PORTION
 OF WALL ZONE # 5, WITH THE HIGH ASSOCIATED PRESSURES.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE THE PRESSURES, ALSO THE MEAN ROOF HEIGHT IS
 NOT GIVEN, THIS NEEDS TO BE KNOWN TO VERIFY THE
 NEGATIVE PRESSURES WHICH ARE TAKEN FROM THE ROOF.
  
 4) SHEET A1.0.1 SHOW BOTH NEW EXTERIOR SWING DOORS AS
 WELL AS EURO WALL SYSTEM. TO DATE NO PRODUCT APPROVALS
 HAVE BEEN SUBMITTED. PLEASE SHOW COMPLIANCE WITH 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 5) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7A) 1710.5.1.1FBC-B EXTERIOR WINDOWS AND DOORS.
 (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE THE
 OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT
 BE TESTED FOR WATER INFILTRATION. THE OVERHANG RATIO
 SHALL BE CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 7B) THERE ARE 2 ISSUES, THE PLANS DO NOT PROVIDE A CUT
 SECTION THROUGH THE INTERIOR FINISH FLOOR, TRACK AND
 THE EXTERIOR FINISH FLOOR WITH NEW TILE. SHEET A2.01
 DOOR & HARDWARE NOTE NUMBER 14 INDICATES ALL THRESHOLDS
 SHALL HAVE NO STEP GREATER THAN ? INCH PER A.D.A.
 REQUIREMENTS. WITH NOT SEEING THE PRODUCT APPROVAL FOR
 THE EURO WALL SYSTEM THIS MAY OR MAY NOT BE AN ISSUE
 BUT A LOT OF THESE DOOR SYSTEMS HAVE DISCLAIMERS LIKE,
 WHEN AN ADA/ FLUSH SILL IS USED, THESE DOORS ARE NOT
 APPROVED FOR THE USE WHERE WATER INFILTRATION
 RESISTANCE IS REQUIRED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 8) SHEET A2.01;
 8A) THE 3 ENTRY DOORS 300, 321 & 328A ALL SHOW AS 45
 MINUTE RATED DOORS IN THE DOOR SCHEDULE FOUND ON A2.01.
 NONE OF THE WALLS THE DOORS ARE INSTALLED SHOW AS RATED
 WALLS. SECTION 708.1 FIRE PARTITIONS NO LONGER REQUIRES
 A FIRE RATING AND TABLE 1018.1 FOR BUSINESS OCCUPANCIES
 AND A FIRE SPRINKLERED BUILDING DOES NOT REQUIRE RATED
 CORRIDORS. 107.2.1.3 PLEASE PROVIDE ADDITIONAL
 INFORMATION WHY THE DOORS ARE RATED?
  
 8B) THE NEW DOOR IDENTIFIED AS 328A DOES NOT HAVE THE
 REQUIRED 18 INCHES ON THE LATCH SIDE OF THE DOOR.
 PLEASE REVIEW SECTION 404.2.4 OF THE 2014 ACCESS. CODE
 AND FIGURE 404.2.1(A).
  
 8C) DOOR 328B BLOCKS THE EGRESS PATH, MUST COMPLY WITH
 FBC-B 1005.7 ENCROACHMENT.
 ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION.
 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178
 MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 8D) PLEASE PROVIDE AN OVERALL FLOOR PLAN FOR THIS
 FLOOR. IF THE WORK AREA IS OVER 50 % OF THE FLOOR PLATE
 THEN
 PLEASE SHOW COMPLIANCE WITH THE 2014 EXISTING BUILDING
 CODE 803.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING
 ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY
 FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE
 ENCLOSURE REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO
 VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE
 FLOOR. THE 2007 EXISTING COMMENTARY ON THE EXISTING
 BUILDING CODE SPEAKS ABOUT THE FIRST TIME THE CODE
 REQUIRES WORK OUTSIDE OF THE TENANT SPACE. SINCE THE
 DESIGNER OF RECORD IS ALREADY WORKING OUTSIDE OF THE
 TENANT SPACE THIS COMMENT IF OVER 50 % OF THE FLOOR
 PLATE IS BEING CONSIDERED THE WORK AREA THEN THIS
 COMMENT STANDS.
 THE PLANS DO NOT SHOW WHERE EITHER OF THE TENANT SPACES
 HAVE AT LEAST ONE MEANS OF EGRESS WITH NOT GOING
 THROUGH THE ELEVATOR LOBBY. 2014 FBC-B 713.14.1 AND
 EXCEPTIONS 1-7, PLEASE PROVIDE CODE COMPLIANCE.
 9) SHEET A3.2 THE BOTTOM OF THE MIRROR, THE BOTTOM OF
 THE REFLECTIVE SURFACE IS NOT PROVIDED IN DETAIL 4,
 SHOW COMPLIANCE WITH 2014 ACCESS. CODE 603.3.
  
 SHEET A1.04 SHOWS THE USE OF PROFLEX MSC 90 AS A FLOOR
 UNDERLAYMENT, PLEASE PROVIDE COMPLIANCE WITH;
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARD FLAME SPREAD-
 FBC-B 2014 603.1. EXCEPTION 2. INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-10-10 Cont ID  
Sent By jpearson Date 2017-10-10 Time 06:28 Rev Time 0.00
Received By jpearson Date 2017-10-10 Time 06:28 Sent To  
Notes
2017-10-10 06:28:25NO CHANGES TO ELECTRICAL ALREADY APPROVED AND STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-19 Cont ID  
Sent By jpearson Date 2017-09-19 Time 06:26 Rev Time 0.00
Received By jpearson Date 2017-09-19 Time 06:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jpearson Date 2017-07-20 Time 07:46 Rev Time 0.00
Received By jpearson Date 2017-07-20 Time 07:46 Sent To  
Notes
2017-07-20 07:58:01CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE. WPB AMENDMENTS TO FBC 107.3.5
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 3. ALL RECEPTACLES IN KITCHEN AREAS (ROOM 311) REQUIRE
 GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2)
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL IN THE NEW LOCATION TO CONFIRM THE STATED AIC
 RATING OF THE PANELS IS ADEQUATE. NEC 110.9, 110.10
 5. DATA/PHONE ROOM 315 DOES NOT SHOW ANY POWER OUTLETS.
 HOW WILL THE EQUIPMENT IN THIS ROOM GET POWER? PLEASE
 CLARIFY AND/OR CORRECT. FBC 107.2.1
 6. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES
 PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED
 INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC
 C405.5, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-10-03 Cont ID  
Sent By pleduc Date 2017-10-03 Time   Rev Time 0.00
Received By pleduc Date 2017-10-03 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-22 Cont ID  
Sent By pleduc Date 2017-08-22 Time   Rev Time 0.00
Received By pleduc Date 2017-08-22 Time 07:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By pleduc Date 2017-06-26 Time   Rev Time 0.00
Received By pleduc Date 2017-06-26 Time 12:39 Sent To  
Notes
2017-06-26 14:43:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS 1 - DOOR 300 IS INDICATED AS 45-FIRE RATED
 IN THE DOOR SCHEDULE. THE WALL THAT IT IS INDICATED
 WITHIN DOES NOT HAVE A FIRE RATING.
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
 2) SHEET ALS 1 - DOOR 328 A IS INDICATED AS 45-FIRE
 RATED IN THE DOOR SCHEDULE. THE WALL THAT IT IS
 INDICATED WITHIN DOES NOT HAVE A FIRE RATING.
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
 3) SHEET ALS 1 - DOOR 321 IS NOT INDICATED AS A 45-FIRE
 RATED IN THE DOOR SCHEDULE. THE WALL THAT IT IS
 INDICATED WITHIN DOES NOT HAVE A FIRE RATING.
  
 PER NFPA 101, CHAPTER 39 EXISTING BUISNESS OCCUPANCIES.
  
 39.2.2.7 EXIT PASSAGEWAYS. EXIT PASSAGEWAYS COMPLYING
 WITH 7.2.6 SHALL BE PERMITTED.
  
 7.2.6.2 ENCLOSURE. AN EXIT PASSAGEWAY SHALL BE
 SEPARATED FROM OTHER PARTS OF THE BUILDING AS SPECIFIED
 IN 7.1.3.2, AND THE FOLLOWING ALTERNATIVES SHALL BE
 PERMITTED:
 (1) FIRE WINDOWS IN ACCORDANCE WITH 8.3.3 SHALL BE
 PERMITTED TO BE INSTALLED IN THE SEPARATION IN A
 BUILDING PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 9.7.
 (2) EXISTING FIXED WIRED GLASS PANELS IN STEEL SASH
 SHALL BE PERMITTED TO BE CONTINUED IN USE IN THE
 SEPARATION IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
  
 7.1.3.2 EXITS.
 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE
 SEPARATED FROM OTHER PARTS OF THE BUILDING, THE
 SEPARATING CONSTRUCTION SHALL MEET THE REQUIREMENTS OF
 SECTION 8.2 AND THE FOLLOWING:
  
 (3)* THE SEPARATION SHALL HAVE A MINIMUM 2-HOUR FIRE
 RESISTANCE RATING WHERE THE EXIT CONNECTS FOUR OR MORE
 STORIES, UNLESS ONE OF THE FOLLOWING CONDITIONS EXISTS:
 (A) IN EXISTING NON-HIGH-RISE BUILDINGS, EXISTING EXIT
 STAIR ENCLOSURES SHALL HAVE A MINIMUM 1-HOUR FIRE
 RESISTANCE RATING.
 (B) IN EXISTING BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, EXISTING EXIT STAIR
 ENCLOSURES SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING.
 (C) THE MINIMUM 1-HOUR ENCLOSURES IN ACCORDANCE WITH
 28.2.2.1.2, 29.2.2.1.2, 30.2.2.1.2, AND 31.2.2.1.2
 SHALL BE PERMITTED AS AN ALTERNATIVE TO THE REQUIREMENT
 OF 7.1.3.2.1(3).
 (4) RESERVED.
 (5) THE MINIMUM 2-HOUR FIRE RESISTANCE?RATED SEPARATION
 REQUIRED BY 7.1.3.2.1(3) SHALL BE CONSTRUCTED OF AN
 ASSEMBLY OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE
 MATERIALS AND SHALL BE SUPPORTED BY CONSTRUCTION HAVING
 A MINIMUM 2-HOUR FIRE RESISTANCE RATING, UNLESS
 OTHERWISE PERMITTED BY 7.1.3.2.1(7).
  
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
 4) SHEET ALS 1 - DOOR 301 IS NOT INDICATED AS A 45-FIRE
 RATED IN THE DOOR SCHEDULE. THE WALL THAT IT IS
 INDICATED WITHIN DOES NOT HAVE A FIRE RATING.
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
 5) THERE IS NO INDICATIONS OF THE ELEVATOR OR COMMON
 CORRIDOR AS BEING PRESSURIZED, SMOKE CONTROLED, OR
 BEING A SMOKE BARRIER. THUSLY, REQUIRING THE NEW WALLS
 AND DOORS OF THE COMMON CORRIDOR TO BE COMPLIANT.
  
 PLEASE REVIEW THE EXISITING LIFE SAFETY FEATURES AND
 EQUIPMENT OF THIS HIGH RISE AND ENSURE THAT ALL LIFE
 SAFETY FEATURES ARE MAINTAINED AND NOT BEING DIMINSIHED
 BY THIS PROPOSED PROJECT6)
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-12 Cont ID  
Sent By gjohnson Date 2017-10-12 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2017-09-29 Time 14:28 Sent To  
Notes
2017-10-02 14:28:42C40

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-25 Cont ID  
Sent By gjohnson Date 2017-09-25 Time 12:58 Rev Time 0.00
Received By gjohnson Date 2017-08-14 Time 10:05 Sent To  
Notes
2017-08-17 10:08:19C38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-20 Cont ID  
Sent By jpearson Date 2017-07-20 Time 08:00 Rev Time 0.00
Received By jpearson Date 2017-06-21 Time 15:27 Sent To  
Notes
2017-06-23 15:28:07C34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-12 Cont ID  
Sent By jwitmer Date 2017-07-12 Time 16:55 Rev Time  
Received By jwitmer Date 2017-07-12 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-10-13 Cont ID  
Sent By ccole Date 2017-10-10 Time 17:31 Rev Time 0.00
Received By ccole Date 2017-10-10 Time 17:10 Sent To  
Notes
2017-10-10 17:37:41MECHANICAL PROVISO- 10/13/17
  
 CHRISTOPHER L. COLE MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 CHRIS,
  
 PER OUR DISCUSSION PLEASE BE ADVISED THAT WE ARE
 WORKING WITH THE BUILDING ENGINEER OVER AT
 525 S. FLAGLER DR., 3RD FLOOR, PERMIT #17060979 TO
 CHOOSE A WINDOW AND DOOR SYSTEM DESIGN SUITABLE
 TO ALL PARTIES INVOLVED. ONCE A SYSTEM HAS BEEN
 SELECTED WE WILL BE COMING BACK IN WITH REVISED
 MECHANICAL DRAWINGS PER YOUR COMMENT:
  
 1) THE MECHANICAL PLANS AND CONTROL DIAGAM MUST BE
 REVISED IN ACCORDANCE WITH THE ARCHITECTURAL
 PLANS AND THE REMOVED EURO WALLS.
  
 AND REVISED DETAILS FOR THE CHOSEN SYSTEM. THIS LETTER
 IS TO REQUEST A PROVISO FOR YOUR
 LATEST COMMENT IN ORDER TO PROCEED WITH THE PERMITTED
 DEMOLITION OF THE SPACE. THEN, AS SOON AS
 AN AGREEMENT HAS BEEN MADE WITH THE BUILDING ENGINEER
 WE WILL COME BACK IN WITH THE
 REQUESTED REVISIONS.
  
 THANK YOU FOR YOUR TIME, VERY TRULY YOURS,
  
 KEITH M. SPINA PRESIDENT
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-18 Cont ID  
Sent By ccole Date 2017-09-18 Time 08:06 Rev Time 0.00
Received By ccole Date 2017-09-18 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By ccole Date 2017-07-18 Time 08:27 Rev Time 0.00
Received By ccole Date 2017-07-17 Time 17:20 Sent To  
Notes
2017-07-18 08:54:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060979
 7/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.01: INDICATE HOW O/A IS BEING PROVIDED TO
 THE CORRIDOR AND AHU-3-1A.
  
 2) M2.02: INDICATE HOW O/A IS BEING SUPPLIED TO THE
 RECEPTION, BREAKROOM, AND LOUNGE AREAS AND AHU'S 3-1E,
 3-1F-2, 3-1H-1, & 3-1H-2.
  
 3) M2.02: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 CU-3-1A/B TO VERIFY THE UNITS CAN BE INSTALLED INSIDE
 THE INTERIOR SPACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-12 Cont ID  
Sent By gjohnson Date 2017-10-12 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2017-10-12 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-25 Cont ID  
Sent By gjohnson Date 2017-09-25 Time 12:57 Rev Time 0.00
Received By gjohnson Date 2017-09-25 Time 12:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By gjohnson Date 2017-07-19 Time 08:33 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 14:53 Sent To  
Notes
2017-07-19 09:33:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER
 TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER
 TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 610.3 SHOWER
 COMPARTMENT SEATS. IN TRANSFER-TYPE SHOWERS, THE SEAT
 SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE TOP OF THE
 SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS
 SHALL COMPLY WITH 610.3.1 OR 610.3.2.
  
 4. TEMPERATURE LIMITING DEVISES FOR TEMPERED WATER
 DELIVERED FROM LAVATORY'S SHALL CONFORM TO ASSE 1070 OR
 CSA B125.3 PER FBC PL 416.5 , THE LEONARD TM-26-LL AND
 THE EEMAX EX48TFS SPECKED OUT ON THE PLAN DO NOT COMPLY
 WITH ASSE 1070 PER MANUFACTURE SPECIFICATIONS.
  
 5. THE BRANCH DRAIN FOR THE EWC SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP . PER FBC PL 912.1
  
 6. THE SANITARY AND VENT FOR THE FLOOR DRAIN IN ROOM
 301 APPEARS TO BE CONNECTING IN TO A EXISTING OA DUCT
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. A SERVICE SINK IS REQUIRED IS THERE AN EXITING ONE
 PLEASE SHOW ON THE PLAN. PER FBC PL TABLE 403.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  