Plan Review Details - Permit 17060927
Plan Review Stops For Permit 17060927
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-22 Cont ID  
Sent By cthroop Date 2017-09-22 Time 09:29 Rev Time 0.00
Received By cthroop Date 2017-09-22 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-19 Cont ID  
Sent By cthroop Date 2017-09-19 Time 11:24 Rev Time 0.00
Received By cthroop Date 2017-09-15 Time 11:25 Sent To M
Notes
2017-09-19 11:27:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS OR
 SELECT TO DEFER THESE SUBMITALS AT A LATER DATE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By cthroop Date 2017-07-12 Time 15:23 Rev Time 0.00
Received By cthroop Date 2017-07-12 Time 11:56 Sent To  
Notes
2017-07-12 15:33:56BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN ENERGY SUBMITTAL. R-VALUE FOR ATTIC BATT
 INSULATION AND RIGID FLOOR INSULATION NOT IDENTIFIED ON
 PLAN.
 2. PROVIDE PRODUCT APPROVALS REVIEWED AND APPROVED BY
 DESIGNER OF RECORD.
 3. ROOFING PERMIT WILL BE REQUIRED.
  
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 - OR -
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-11 Cont ID  
Sent By jpearson Date 2017-09-11 Time 09:28 Rev Time 0.00
Received By jpearson Date 2017-09-11 Time 09:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By jpearson Date 2017-07-11 Time 10:42 Rev Time 0.00
Received By jpearson Date 2017-07-11 Time 10:41 Sent To  
Notes
2017-07-11 11:05:06CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. RISER DIAGRAM SHOWS 3/0 AL CONDUCTORS IN SERVICE
 RISER. 3/0 AL IS NOT RATED FOR 200 AMPS. PROVIDE
 CORRECTION. NEC 310.15; FBC RE3603.1
 2. NOTE 1 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 3. NOTE 13 ALSO REFERENCES THE WRONG CODE SECTION FOR
 LIGHTING IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16; FBC RE4003.12
 4. REMOVE ANY NOTES NOT APPLICABLE TO THIS PROJECT. IF
 THERE WILL BE A POOL, PROVIDE NOTE THAT STATES THE POOL
 WILL BE UNDER SEPARATE PERMIT. FBC 107.2.1
 5. CIRCUITS 25, 27, 22, 24, AND 26 SHOULD BE AFCI
 PROTECTED CIRCUITS BASED ON THE DESCRIPTION. PROVIDE
 CORRECTION. NEC 210.12; FBC RE3902.12
 6. PROVIDE COMPLIANCE WITH LIGHTING ENERGY
 CONSERVATION: "A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC
 R404.1
 7. LIGHTING IN BATHTUB OR SHOWER AREAS AND PORCH AREA
 SHALL BE SUITABLE FOR DAMP LOCATIONS. THESE AREAS
 CURRENTLY SHOW A STANDARD RECESS LIGHT. PROVIDE
 CORRECTION. NEC 410.10(A), FBC RE4003.11
 8. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. THE MASTER CLOSET SHOWS A
 STANDARD RECESS LIGHT. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1
 10. PROVIDE OUTLET ON REAR OF HOUSE. FOR A ONE FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY
 ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (6.5 FT)
 ABOVE GRADE LEVEL SHALL BE INSTALLED AT THE FRONT AND
 BACK OF THE DWELLING. NEC 210.52(E)(1) FBC RE3901.7
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By destabro Date 2017-08-25 Time 14:02 Rev Time 0.00
Received By destabro Date 2017-08-25 Time 14:02 Sent To B
Notes
2017-08-25 14:04:178/25/2017 - REVISED PLANS HAVE NO IMPACT TO HISTORIC
 PROVISIONS. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-06-29 Cont ID  
Sent By destabro Date 2017-06-29 Time 15:15 Rev Time 0.00
Received By destabro Date 2017-06-29 Time 15:15 Sent To B
Notes
2017-06-30 07:54:116/29/2017 - NO PRODUCT APPROVALS INCLUDED WITH PERMIT.
 DLE
2017-06-29 15:18:086/29/2017 - MET WITH ARCHITECT TO DISCUSS PROPOSED
 RENOVATION TO LOCALLY DESIGNATED HISTORIC PROPERTY. ALL
 PROPOSED WORK MEETS DESIGN GUIDELINES, EXCEPT FOR
 MENTION OF VINYL LATTICE TO SHIELD CRAWLSPACE (A1.0,
 A2.1, A3.0 - PART R23). PLEASE REVISE TO WOOD LATTICE
 OR METAL SCREEN. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-19 Cont ID  
Sent By hmoser Date 2017-09-19 Time 13:58 Rev Time 0.00
Received By hmoser Date 2017-08-17 Time 12:54 Sent To  
Notes
2017-08-18 12:54:33R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-19 Cont ID  
Sent By hmoser Date 2017-07-19 Time 13:37 Rev Time 0.00
Received By hmoser Date 2017-06-20 Time 14:35 Sent To  
Notes
2017-06-21 14:35:46R18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-19 Cont ID  
Sent By hmoser Date 2017-09-19 Time 13:58 Rev Time 0.00
Received By hmoser Date 2017-09-19 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By hmoser Date 2017-07-19 Time 13:36 Rev Time 0.00
Received By hmoser Date 2017-07-19 Time 11:01 Sent To  
Notes
2017-07-19 13:36:13PLAN DENIED
 1) CAN'T HAVE RETURN AIR IN KITCHEN. REFER TO
 SECTION M1602.2 PROHIBITED SOURCES #4
 2014 RESIDENTIAL CODE
 2) MASTER BEDROOM REFER TO SECTION M1602.4
 BALANCED RETURN AIR 2014 RESIDENTIAL CODE
 3) HEAT LODE REQUIRED, REFER TO SECTION M1401.3
 SIZING 2014 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-14 Cont ID  
Sent By thunt Date 2017-09-14 Time 15:14 Rev Time 0.00
Received By thunt Date 2017-09-14 Time 14:52 Sent To  
Notes
2017-09-14 15:15:04BACKFLOW REQUIRES SEPERATE PERMIT

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By gjohnson Date 2017-07-11 Time 13:31 Rev Time 0.00
Received By gjohnson Date 2017-07-11 Time 13:31 Sent To  
Notes
2017-07-11 14:06:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PUT A NOTE ON THE PLAN THAT A SEPARATE PERMIT
 IS REQUIRED FOR THE BACKFLOW. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT P2.1 DETAIL #6 THE BACK FLOW IS REQUIRED TO BE
 LEAD FREE THE WATTS MODEL #909 THAT YOU REFERENCE ON
 DETAIL IS NOT LEAD FREE MANUFACTURE SPECS SHOWING
 DEVICE IS LEAD FREE WILL BE REQUIRED WITH SEPARATE
 PERMIT APPLICATION SO THIS DETAIL DOES NOT NEED TO BE
 ON THE MASTER SET OF PLANS. PER FBC RES P2905.2.1
  
 3. PLEASE SHOW WATER HEATER PAN DRAIN TERMINATION/ PER
 FBC RES P2801.5.2
  
 4. SHOW T AND P VALVE DISCHARGE PIPING. TO COMPLY WITH
 FBC RES P2803.6.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By cthroop Date 2017-09-22 Time 09:30 Rev Time 0.00
Received By cthroop Date 2017-09-22 Time 09:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-09-19 Cont ID  
Sent By cthroop Date 2017-09-19 Time 11:27 Rev Time 0.00
Received By cthroop Date 2017-09-15 Time 16:16 Sent To  
Notes
2017-09-19 11:30:15BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM COMPONENTS
 OR REMOVE ROOFING FROM SCOPE OF WORK AND SUBMIT STAND
 ALONE ROOFING PERMIT PRIOR TO ROOFING INSTALLATION.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By destabro Date 2017-08-25 Time 14:03 Rev Time 0.00
Received By destabro Date 2017-08-25 Time 14:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-06-29 Cont ID  
Sent By destabro Date 2017-06-29 Time 15:18 Rev Time 0.00
Received By destabro Date 2017-06-29 Time 15:18 Sent To B
Notes
***NONE***