Plan Review Details - Permit 17060795
Plan Review Stops For Permit 17060795
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-10 Cont ID  
Sent By jwitmer Date 2017-07-10 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2017-07-10 Time 06:15 Sent To  
Notes
2017-07-10 06:36:292014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060795
 ADD: 2101 CENTREPARK WEST DRIVE, SUITE 150
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 22/ 2017
 ACTION: APPROVED
 A SECOND SET OF SIGNED AND SEALED PLANS WAS BROUGHT IN
 TODAY. JW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2017-06-22 Time 08:28 Sent To  
Notes
2017-06-22 08:42:012014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060795
 ADD: 2101 CENTREPARK WEST DRIVE, SUITE 150
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 22/ 2017
 ACTION: DENIED
  
 1) SHEET A-1 SHOW THE UNIT NUMBER 150 BEING SPLIT INTO
 2 UNITS WITH THE NEW UNIT ADDRESSED AS UNIT 145. THE
 NEW UNIT DOES NOT SHOW RESTROOMS FOR THIS TENANT NOR
 COMMON AREA RESTROOMS.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
 UNDER THE 2014 FBC-B TABLE 2902.1 MINIMUM NUMBER OF
 FIXTURE (PLUMBING) PER OCCUPANCY TYPE. NO RESTROOMS ARE
 SHOWN FOR THE NEW TENANT SPACE 145.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-17 Cont ID  
Sent By jpearson Date 2017-07-17 Time 07:43 Rev Time 0.00
Received By jpearson Date 2017-07-17 Time 07:43 Sent To  
Notes
2017-07-17 07:44:44DEMO ONLY SHOWN ON PLANS. PLAN DOES NOT INCLUDE ANY NEW
 INSTALLATIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-23 Cont ID  
Sent By jleahy Date 2017-06-23 Time 14:46 Rev Time 0.00
Received By jleahy Date 2017-06-23 Time 14:46 Sent To  
Notes
2017-06-23 14:47:57CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN ON DRAWINGS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-05 Cont ID  
Sent By pleduc Date 2017-07-05 Time   Rev Time 0.00
Received By pleduc Date 2017-07-03 Time 16:05 Sent To  
Notes
2017-07-03 16:29:102ND REVIEW
  
 IT APPEARS THAT ONE OF THE PLAN SETS WAS MARKED VOID
 INCORRECTLY. IT MATCHES ONE OF THE RESUBMITTED PLAN
 SETS THAT HAS ARCHITECTUAL STAMP DATE OF 6/29/17. I
 HAVE STAMPED REVIEW ON THE VOIDED ONE FOR EXPEDITIOUS
 PURPOSES.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By pleduc Date 2017-06-21 Time   Rev Time 0.00
Received By pleduc Date 2017-06-20 Time 14:14 Sent To  
Notes
2017-06-20 16:07:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE IS A ROOM WITH WALLS INDICATED
 WITHIN SUITE # 150 WITH NO DOOR.
  
 PLEASE REVIEW AND CLARIFY AND/OR CORRECT. PROVIDE A
 DOOR SCHEDULE AS APPLICABLE.
  
  
  
 2) SHEET A 1 - THERE ARE INDICATIONS OF FIRE ALARM
 EQUIPMENT WORK. ANY FIRE ALARM EQUIPMENT WORK SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
 3) THE VALUE $ 600.00 ON THE APPLICATION APPEARS TO BE
 VERY LOW FOR THE AMOUNT OF WORK PROPOSED.
  
 PLEASE PROVIDE DETAILED AND ACCURATE VALUATION
 DOCUMENTS AND OR A COPY OF THE ACTUAL CONTRACT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-17 Cont ID  
Sent By jpearson Date 2017-07-17 Time 07:45 Rev Time 0.00
Received By jpearson Date 2017-06-30 Time 15:47 Sent To  
Notes
2017-06-30 15:47:58B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-23 Cont ID  
Sent By jleahy Date 2017-06-23 Time 14:48 Rev Time 0.00
Received By jleahy Date 2017-06-16 Time 09:58 Sent To  
Notes
2017-06-19 09:58:49B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2017-06-22 Time 08:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 09:16 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 07:48 Sent To  
Notes
2017-07-14 09:18:09MECHANICAL PROVISO
 CCOLE- 7/14/14
  
 SEPARATE PERMITS ARE REQUIRED FOR MECHANICAL WORK IN
 EACH OF THE TWO NEW TENANT SPACES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By ccole Date 2017-06-21 Time 15:10 Rev Time 0.00
Received By ccole Date 2017-06-21 Time 15:08 Sent To  
Notes
2017-06-21 15:22:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060795
 6/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: REFER TO NOTE #3 AND SHOW HOW THE
 EXISTING AC SYSTEMS WILL BE ALTERED TO PROVIDE
 SEPARATELY CONTROLLED, SEPARATELY ACCESSED, AND
 SEPARATELY BALANCED AIR FLOWS SYSTEMS TO EACH OF THE
 TWO TENANT SPACES.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]