Plan Review Details - Permit 17060769
Plan Review Stops For Permit 17060769
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-11-16 Cont ID  
Sent By jwitmer Date 2017-11-16 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2017-11-16 Time 11:30 Sent To  
Notes
2017-11-16 14:57:092014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060769 / SHELL BUILDING
 ADD: 1560 PALM BEACH LAKES BLVD.
 CONT: IBIS BUILDING
 TEL: 561-318-8408
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: THURS. NOV. 16/ 2017
 ACTION: BUILDING PROVISO
  
 1) PROVISO: 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 AND GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING RESIDENT INSPECTORS. COMMENT # 14. ( 3 )
 COPIES OF ALL SHOP DRAWINGS (PRODUCT APPROVALS,
 TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED TO THE
 BUILDING DEPARTMENT. TWO REVIEWED SETS OF DOCUMENTS
 WILL BE RETURNED TO THE JOB SITE BEFORE ANY OF THE
 ABOVE IS INSTALLED ON THE JOB.
  
 2) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 5) BUILDING PROVISO/ DEFERRED SUBMITTALS: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: EFIS SYSTEMS:
 PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE SYSTEM TO
 BE INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014
 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-10-30 Cont ID  
Sent By jwitmer Date 2017-10-30 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2017-10-30 Time 08:03 Sent To  
Notes
2017-10-30 09:16:472014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060769
 ADD: 1560 PALM BEACH LAKES BLVD.
 CONT: IBIS BUILDING
 TEL: 561-318-8408
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. OCT. 30/ 2017
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SEMI-COMPLIED, ONLY 2 SOILS REPORTS SUBMITTED 3
 REQUIRED FOR RESIDENT INSPECTOR.
  
 4) 3RD REQUEST. RESPONSE, NOT YET SELECTED. RESIDENT
 INSPECTOR 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE
 INCH
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION BOLTED AND WELDED CONNECTIONS.
 RESIDENT INSPECTOR WILL BE REQUIRED FROM FOUNDATION
 THROUGH ROOF FRAMING, ROOF DECKING, WINDOW FRAME AND
 GLAZING INSTALLATION.
  
 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS SENT TO: [email protected] OCT. 30/ 2017 AT
 09:15 AM.
  
 4B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED
  
 4C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED.
  
 4E) PROVISO: 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 AND GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING RESIDENT INSPECTORS. COMMENT # 14. ( 3 )
 COPIES OF ALL SHOP DRAWINGS (HANDRAILS, PRECAST JOINT
 AND SLABS, PRODUCT APPROVALS, TRUSSES, BAR JOIST, ETC.)
 MUST BE SUBMITTED TO THE BUILDING DEPARTMENT. TWO
 REVIEWED SETS OF DOCUMENTS WILL BE RETURNED TO THE JOB
 SITE BEFORE ANY OF THE ABOVE IS INSTALLED ON THE JOB.
  
 4F) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5) COMPLIED.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 8) BUILDING PROVISO/ DEFERRED SUBMITTALS: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 10) BUILDING PROVISO/ DEFERRED SUBMITTALS: EFIS
 SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE
 SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 11) COMPLIED. FOR SHELL BUILDING.
  
 12) COMPLIED. PALM BEACH COUNTY IMPACT FEES.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-26 Cont ID  
Sent By jwitmer Date 2017-08-26 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2017-08-26 Time 06:30 Sent To  
Notes
2017-08-26 07:12:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060769
 ADD: 1560 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 407-786-9724
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. AUGUST 26/ 2017
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST. RESPONSE, NOT YET SELECTED. THE SOILS
 REPORTS BY UNIVERSAL ENGINEERING SCIENCES DATED AUGUST
 04/2016 UES REPORT NO. 13869 INDICATES THAT THREE SOILS
 SAMPLES TEST RESULT INDICATE ORGANIC CONTENTS RANGED
 FROM 10.7 TO 26.8 PERCENT AND MOISTURE CONTENTS RANGING
 FROM 50.6 TO 121 PERCENT. ORGANIC SOILS (10 PERCENT OR
 HIGHER) ENCOUNTERED IN STRUCTURAL AREAS SHOULD BE
 REMOVED AND REPLACED WITH GOOD QUALITY FILL. PLEASE
 PROVIDE WHICH SOILS ENGINEERING COMPANY WILL BE
 OVERSEEING THE REMOVAL AND REPLACEMENT OF GOOD QUALITY
 FILL IN ACCORDANCE TO THE SPECIFICATIONS AND PROCEDURES
 OUTLINED IN THE SITE PREPARATION SECTION OF THIS
 REPORT? 107.2.1.3 ADDITIONAL INFORMATION WILL BE
 REQUIRED. 2014 FBC-B 1803.4 QUALIFIED REPRESENTATIVE.
  
 4) 2ND REQUEST. RESPONSE, NOT YET SELECTED. RESIDENT
 INSPECTOR 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE
 INCH
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION BOLTED AND WELDED CONNECTIONS.
 RESIDENT INSPECTOR WILL BE REQUIRED FROM FOUNDATION
 THROUGH ROOF FRAMING, ROOF DECKING, WINDOW FRAME AND
 GLAZING INSTALLATION.
  
 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS SENT TO: [email protected] 06/27/2017 97:15 AM
  
 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED
  
 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 4E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 RESIDENT INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP
 DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT
 APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED
 TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS OF
 DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY
 OF THE ABOVE IS INSTALLED ON THE JOB.
  
 4F) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5) COMPLIED.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 8) BUILDING PROVISO/ DEFERRED SUBMITTALS: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 10) BUILDING PROVISO/ DEFERRED SUBMITTALS: EFIS
 SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE
 SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 11) COMPLIED FOR SHELL BUILDING.
  
 12) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By jwitmer Date 2017-06-27 Time 09:06 Rev Time 0.00
Received By jwitmer Date 2017-06-26 Time 15:27 Sent To  
Notes
2017-06-27 09:06:402014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060769
 ADD: 1560 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 407-786-9724
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 26/ 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY WITH THE PROPOSED BUILDING
 LOCATION AND DISTANCES TO THE PROPERTY LINES SO
 COMPLIANCE WITH 2014 FBC-B TABLE 602 FOR FIRE
 RESISTANCE REQUIREMENTS FOR EXTERIOR WALLS BASED ON
 FIRE SEPARATION DISTANCE AND PERCENTAGE OF ALLOWABLE
 OPENINGS BASED ON FIRE SEPARATION PER TABLE 705.8.
  
 2) THE SOILS REPORTS BY UNIVERSAL ENGINEERING SCIENCES
 DATED AUGUST 04/2016 UES REPORT NO. 13869 HAS A COPY OF
 A STAMPED SEAL AND SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 3) THE SOILS REPORTS BY UNIVERSAL ENGINEERING SCIENCES
 DATED AUGUST 04/2016 UES REPORT NO. 13869 INDICATES
 THAT THREE SOILS SAMPLES TEST RESULT INDICATE ORGANIC
 CONTENTS RANGED FROM 10.7 TO 26.8 PERCENT AND MOISTURE
 CONTENTS RANGING FROM 50.6 TO 121 PERCENT. ORGANIC
 SOILS (10 PERCENT OR HIGHER) ENCOUNTERED IN STRUCTURAL
 AREAS SHOULD BE REMOVED AND REPLACED WITH GOOD QUALITY
 FILL. PLEASE PROVIDE WHICH SOILS ENGINEERING COMPANY
 WILL BE OVERSEEING THE REMOVAL AND REPLACEMENT OF GOOD
 QUALITY FILL IN ACCORDANCE TO THE SPECIFICATIONS AND
 PROCEDURES OUTLINED IN THE SITE PREPARATION SECTION OF
 THIS REPORT? 107.2.1.3 ADDITIONAL INFORMATION WILL BE
 REQUIRED. 2014 FBC-B 1803.4 QUALIFIED REPRESENTATIVE.
  
 4) 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE
 INCH
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION BOLTED AND WELDED CONNECTIONS.
 RESIDENT INSPECTOR WILL BE REQUIRED FROM FOUNDATION
 THROUGH ROOF FRAMING, ROOF DECKING, WINDOW FRAME AND
 GLAZING INSTALLATION.
  
 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS SENT TO: [email protected] 06/27/2017 97:15 AM
  
 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED
  
 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 4E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 RESIDENT INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP
 DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT
 APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED
 TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS OF
 DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY
 OF THE ABOVE ARE INSTALLED ON THE JOB.
  
 4F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5) SHEETS A5.1 DETAILS 1 & 4, A5.2 DETAILS 1 & 3, A5.3
 DETAILS 1, 2, &4, A6.2 DETAILS 1 & 2, S3.1, S3.2 & S3.3
 ALL WILL NEED TO SHOW COMPLIANCE WITH 2014 FBC-B 1403.8
 (5) & 2114.2.
 2014 FBC-B 1403.8 (5).
 MASONRY VENEERS CONSTRUCTED IN ACCORDANCE WITH SECTION
 2114.2.
 2114.2 CONCRETE BEARING LEDGE. BRICK, STONE OR OTHER
 VENEER SHALL BE SUPPORTED BY A CONCRETE BEARING LEDGE
 AT LEAST EQUAL TO THE TOTAL THICKNESS OF THE BRICK,
 STONE OR OTHER VENEER, WHICH IS POURED INTEGRALLY WITH
 THE CONCRETE FOUNDATION. NO SUPPLEMENTAL CONCRETE
 FOUNDATION POURS WHICH WILL CREATE A HIDDEN COLD JOINT
 SHALL BE USED WITHOUT SUPPLEMENTAL TREATMENT IN THE
 FOUNDATION, UNLESS THERE IS AN APPROVED PHYSICAL
 BARRIER. AN APPROVED PHYSICAL BARRIER SHALL ALSO BE
 INSTALLED FROM BELOW THE WALL SILL PLATE OR FIRST BLOCK
 COURSE HORIZONTALLY TO EMBED IN A MORTAR JOINT. IF
 MASONRY VENEER EXTENDS BELOW GRADE, A TERMITE
 PROTECTIVE TREATMENT MUST BE APPLIED TO THE CAVITY
 CREATED BETWEEN THE VENEER AND THE FOUNDATION, IN LIEU
 OF A PHYSICAL BARRIER.
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 TMS 402/ACI 530/ASCE 5, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXIST BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 6) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE,
 THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE
 AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 10) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 11) SHEET A2.1 ON THE DOOR HARDWARE SCHEDULE ALL THE
 EXTERIOR DOORS SHOW HARDWARE GROUP 1 WITH PUSH/ PULL
 HARDWARE. PLEASE NOTE WHEN THE OCCUPANT LOAD IS 50 OR
 MORE OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR
 LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-14 Cont ID  
Sent By jpearson Date 2017-11-14 Time 12:45 Rev Time 0.00
Received By jpearson Date 2017-11-14 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By jpearson Date 2017-09-22 Time 16:15 Rev Time 0.00
Received By jpearson Date 2017-09-22 Time 16:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-13 Cont ID  
Sent By jpearson Date 2017-07-13 Time 09:40 Rev Time 0.00
Received By jpearson Date 2017-07-13 Time 09:40 Sent To  
Notes
2017-07-13 10:07:46CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 2. NOTE 8 ON RISER DIAGRAM STATES THE EQUIPMENT
 GROUNDING CONDUCTOR (EGC) IS SIZED AT 1/0 COPPER, WHICH
 IS NOT PER CODE FOR A 1200 AMP SYSTEM. PROVIDE
 CORRECTION. NEC 250.122
 3. PROVIDE ACTUAL FAULT CURRENT FROM FPL. AN ESTIMATED
 VALUE IS NOT ACCEPTABLE. NEC 110.10
 4. SHEET EP1.2, PLEASE IDENTIFY WHICH LIGHT FIXTURE
 MODEL WILL BE USED. FBC 107.2.1
 5. INDICATE VOLTAGE DROP COMPLIANCE WITH FBC ENERGY
 CODE. A NOTE WILL SUFFICE. NOTE SHOULD INCLUDE
 INDICATION OF SUBMITTAL OF COMPLETION DOCUMENTS PER FBC
 C405.7.4 FBC C405.7.3
 6. LOAD CALCULATIONS PROVIDED IS INCOMPLETE. PROVIDE
 ACCURATE LOAD CALCULATIONS TO JUSTIFY SERVICE SIZE. NEC
 215.2, 215.5, 220; FBC 107.2.1
 7. WHY IS WIRING SHOWN TO THE RTU'S IN UNIT 9, BUT NOT
 IN ANY OTHER UNIT? WHY IS THERE NO WIRING SHOWN TO
 EMERGENCY AND EXIT LIGHTS REQUIRED? PROVIDE
 CLARIFICATION. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-11-14 Cont ID  
Sent By skennedy Date 2017-11-14 Time 12:24 Rev Time 0.00
Received By skennedy Date 2017-11-14 Time 12:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-10-02 Cont ID  
Sent By mgonzale Date 2017-10-02 Time 16:11 Rev Time 1.00
Received By mgonzale Date 2017-10-02 Time 16:11 Sent To ENG
Notes
2017-10-02 15:54:40PLAN REIVEW FOR SITE DEVELOPMENT THROUGH ENGINEERING
 AND ENGINEER OF RECORD - CIVIL.
  
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-15 Cont ID  
Sent By pleduc Date 2017-11-15 Time   Rev Time 0.00
Received By pleduc Date 2017-11-15 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By wjolin Date 2017-08-25 Time 11:46 Rev Time 0.00
Received By wjolin Date 2017-08-25 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By wjolin Date 2017-06-28 Time 12:17 Rev Time 0.00
Received By wjolin Date 2017-06-28 Time 11:55 Sent To  
Notes
2017-06-28 12:14:561560 PALM BEACH LAKES BOULEVARD
 PERMIT #17060769
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****SHELL ONLY***** SEPARATE PERMITS AND SUBPERMITS
 WILL BE NEEDED FOR TENANT FITOUT WORK. NO CERTIFICATE
 OF OCCUPANCY WILL BE GRANTED FOR THE SHELL-ONLY WORK.
  
 DESIGN SHALL CONFORM TO THE 5TH EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 NO SITE OR CIVIL PLANS SUBMITTED SHOWING FIRE HYDRANTS
 FOR FIRE DEPARTMENT ACCESS ROADS/LANES.
  
 PLANS DO NOT INDICATE ANY PORTABLE FIRE EXTINGUISHERS,
 EMERGENCY LIGHTING, ILLUMINATED EXIT SIGNS, TACTILE
 SIGNAGE.
  
 PER NFPA 101 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING "FIRE BARRIER-PROTECT ALL OPENINGS." CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 FIRE PROTECTION BACKFLOW PREVENTER IS LOCATED CLOSER
 THAN 40 FEET FROM THE BUILDING.
 PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE
 FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE
 ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO
 THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 PROVIDE A DRAWING NOTE INDICATING: AN APPROVED WRITTEN
 EMERGENCY PLAN FOR THE EMERGENCY EGRESS OF OCCUPANTS IS
 REQUIRED PRIOR TO OCCUPANCY. ALL EMPLOYEES SHALL BE
 INSTRUCTED AND PERIODICALLY DRILLED WITH RESPECT TO
 THEIR DUTIES UNDER THE PLAN. EMPLOYEES SHALL BE
 PERIODICALLY TRAINED OR INSTRUCTED IN THE USE OF
 PORTABLE FIRE EXTINGUISHERS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status F Date 2017-11-16 Cont ID  
Sent By   Date 2017-11-16 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-06 Time 15:39 Sent To  
Notes
2017-11-16 09:36:4611/16 TO JW DESK
  
  
2017-11-07 15:39:39C31

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-30 Cont ID  
Sent By jwitmer Date 2017-10-30 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2017-10-26 Time 13:35 Sent To  
Notes
2017-10-27 13:35:38RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-04 Cont ID  
Sent By cpuell Date 2017-10-04 Time 13:55 Rev Time 0.00
Received By cpuell Date 2017-08-22 Time 16:09 Sent To  
Notes
2017-08-23 16:20:34C23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-09 Cont ID  
Sent By lmarchan Date 2017-08-09 Time 16:12 Rev Time 0.00
Received By lmarchan Date 2017-06-15 Time 14:48 Sent To  
Notes
2017-06-16 14:48:14C19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2017-10-30 Cont ID  
Sent By jwitmer Date 2017-10-30 Time 08:22 Rev Time 0.00
Received By jwitmer Date 2017-10-30 Time 08:09 Sent To  
Notes
2017-10-30 08:22:39OCT. 30/2017
 PALM BEACH COUNTY IMPACT FEES PAID
 DATE RECEIVED: 10/26/2017
 TRACKING NUMBER: MU-2017-0289-0000
 RECEIPT NUMBER: 2017-1026-304
 TOTAL $207,112.42
 J. WITMER W. P. B. PLAN REVIEW
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-08-26 Cont ID  
Sent By jwitmer Date 2017-08-26 Time 07:13 Rev Time 0.00
Received By jwitmer Date 2017-08-26 Time 07:13 Sent To  
Notes
2017-08-26 07:13:24BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By jwitmer Date 2017-06-26 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2017-06-26 Time 16:56 Sent To  
Notes
2017-06-26 16:57:19IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-11-14 Cont ID  
Sent By skennedy Date 2017-11-14 Time 12:24 Rev Time 0.00
Received By skennedy Date 2017-11-14 Time 12:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-20 Cont ID  
Sent By ccole Date 2017-09-20 Time 13:15 Rev Time 0.00
Received By ccole Date 2017-09-20 Time 12:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-07 Cont ID  
Sent By ccole Date 2017-07-07 Time 12:22 Rev Time 0.00
Received By ccole Date 2017-07-07 Time 07:32 Sent To  
Notes
2017-07-07 12:46:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060769
 7/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE NUMBER OF PEOPLE FOR THE OCCUPANCIES
 LISTED IN THE O/A SCHEDULE ARE NOT IN COMPLIANCE WITH
 EITHER TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3
 FBC-14 MECHANICAL. OCCUPANT DENSITY FOR RETAIL IS 15
 PERSONS PER 1000 SQ. FT. WHICH RESULTS IN 32 PEOPLE FOR
 RTU-1, AND 19 PEOPLE FOR RTU-2-8. CONCERNING THE
 RESTAURANT OCCUPANCY (RTU- 9A, 9B, 9C) PLEASE PROVIDE A
 BREAKDOWN CALCULATION THAT DINING AND OTHER AREAS FROM
 THE KITCHEN AREA. PLEASE NOTE THAT THE OCCUPANT DENSITY
 FOR DINING IS 70 PER 1000 SQ. FT. PLEASE REVISE THE
 SCHEDULE ACCORDINGLING.
  
 2) PLEASE ADJUST THE AC COOLING AND HEATING
 CALCULATIONS TO INCLUDE THE ACCURATE NUMBER OF
 OCCUPANTS AND ALSO THE APPLIANCE LOADS FOR EACH
 OCCUPANCY.
  
 3) SHEETS M2.1 & S4.3: PLEASE CHOOSE ONE OF THE TWO RTU
 AND CURB INSTALLATION DETAILS WILL BE USED, AND MATCH
 THE OTHER DETAIL TO IT. THERE ARE DIFFERENCES BETWEEN
 THE TYPES AND NUMBER QUANTITIES OF FASTENERS AND ANCHOR
 BOLTS. CORRECT THE WIND SPEED SHOWN ON M2.1 TO 170 MPH.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-14 Cont ID  
Sent By skennedy Date 2017-11-14 Time 12:02 Rev Time 0.00
Received By skennedy Date 2017-11-14 Time 12:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 14:16 Rev Time 0.00
Received By gjohnson Date 2017-09-27 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 18:51 Rev Time 0.00
Received By gjohnson Date 2017-07-13 Time 18:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-11-14 Cont ID  
Sent By jroach Date 2017-11-14 Time 15:41 Rev Time 0.00
Received By jroach Date 2017-11-14 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By jroach Date 2017-09-22 Time 11:15 Rev Time 0.00
Received By jroach Date 2017-09-20 Time 17:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By jroach Date 2017-07-18 Time 15:48 Rev Time 0.00
Received By jroach Date 2017-07-18 Time 15:48 Sent To  
Notes
2017-07-18 15:49:34ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.18.2017
 PERMIT NO.: 17060769
 ADDRESS: 1560 PALM BEACH LAKES BOULEVARD
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 2. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED. THE
 SITE PLANS SHALL INCLUDE THE FOLLOWING:
  
  A. DATE, NORTH ARROW, AND A GRAPHIC SCALE.
  
  B. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO
 THE SURROUNDING AREA.
  
  C. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY,
 PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER
 ESSENTIAL FEATURES.
  
  D. STREETS, DRIVEWAYS, INTERSECTIONS, CURBS CUTS AND
 TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT
 PROPERTY.
  
  E. THE OUTLINES OF ALL BUILDINGS SHOWING THEIR
 PROPOSED USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER
 OF STORIES, HEIGHT AND POINTS OF ACCESS.
  
  F. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT
 (SIDEWALKS, FENCES, WALLS, OR BERMS).
  
  G. LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS
 AND OTHER ACCESSORY STRUCTURES.
  
  H. MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND
 FROM THE SITE.
  
  I. LAYOUT AND LOCATION OF ALL OFF-STREET PARKING,
 LOADING AND OTHER VEHICULAR USE AREAS.
  
  J. LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS.
  
  K. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES.
  
  L. STANDARD CITY DETAILS OF PARKING (SMALL CAR,
 HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS.
  
  M. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT:
  
  I. EXISTING/PROPOSED LAND USE AND ZONING.
  
  II. TOTAL ACRES OF THE PROJECT.
  
  III. TOTAL GROSS BUILDING SQUARE FOOTAGE.
  
  IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
  
  V. ACRES AND PERCENT OF WATER BODIES.
  
  VI. DENSITY AND NUMBER OF DWELLING UNITS
 (RESIDENTIAL).
  
  VII. PARKING COMPUTATIONS (PARKING REQUIRED,
 PROVIDED, ETC.)
  
  VIII. FLOOR AREA RATIO (FAR).
  
 3. PURSUANT TO THE HOME DEPOT COMMERCIAL PLANNED
 DEVELOPMENT (CPD) DEVELOPMENT ORDER (RESOLUTION NO.
 101-17), THE FOLLOWING SHALL BE ADDRESSED PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT:
  
  A. AN EASEMENT ABANDONMENT MUST BE FILED AND APPROVED
 BY THE CITY OF WEST PALM BEACH FOR THE SIX (6) FOOT
 UTILITY EASEMENT (PLAT BOOK 86, PAGE 13) THAT IS
 LOCATED BENEATH THE PROPOSED BUILDING.
  
  B. THE FINAL PLACEMENT, ANGLE, AND SIZE OF THE
 DUMPSTER ENCLOSURE SHALL BE REVIEWED AND APPROVED BY
 THE CITY?S PUBLIC WORKS DEPARTMENT. PLEASE PROVIDE
 WRITTEN APPROVAL FROM PETER BIENIEK, DIRECTOR OF PUBLIC
 WORKS, OR OTHER AUTHORIZED INDIVIDUAL. MR. BIENIEK MAY
 BE REACHED AT 561.494.1099 OR [email protected].
  
 4. A SEPARATE LANDSCAPE PERMIT SHALL BE OBTAINED. TWO
 (2) COPIES OF SIGNED/SEALED LANDSCAPE PLANS SHALL BE
 SUBMITTED TO THE BUILDING DIVISION WITH A PERMIT
 APPLICATION. PLEASE NOTE THE FOLLOWING SHALL BE
 ADDRESSED PRIOR TO ISSUANCE OF THE LANDSCAPE PERMIT
 (PER RESOLUTION NO. 101-17):
  
  A. LOCATIONS OF ROOT BARRIERS SHALL BE INDICATED TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
  B. TREES/PALMS SHOWN DIRECTLY ON TOP OF THE WATER
 SERVICE AND SEWER LINE SHALL BE ADJUSTED TO AVOID
 CONFLICTS AND ADD ROOT BARRIERS WHERE NEEDED.
  
 5. THE BUILDING APPROVED VIA RESOLUTION NO. 101-17
 CONSISTED OF 15,030 GROSS SQUARE FEET; THE PERMIT
 APPLICATION INDICATES THAT THE BUILDING IS PROPOSED TO
 BE 15,064 SQUARE FEET. ANY INCREASE IN SQUARE FOOTAGE
 SHALL BE REQUIRED TO SUBMIT AN AMENDMENT TO THE HOME
 DEPOT CPD. THE TYPE OF AMENDMENT IS DETERMINED BY THE
 CRITERIA IN SEC. 94-207(E) OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS. PLEASE NOTE THAT
 ADDITIONAL SQUARE FOOTAGE MAY IMPACT THE PARKING
 REQUIREMENTS, AS WELL AS REQUIRE ADDITIONAL TRAFFIC
 CONCURRENCY APPROVALS FROM PALM BEACH COUNTY.
  
 6. PLEASE CLARIFY WHY THE AWNINGS PROPOSED ON THE
 ?TENANT 2? SPACE ARE OF A DIFFERENT MATERIAL THAN THE
 REST OF THE BUILDING. IT IS STAFF?S DIRECTION THAT
 THESE AWNINGS SHOULD BE OF THE SAME MATERIAL AND STYLE.
 IF THE AWNING OVER THE OUTDOOR SEATING NEEDS TO CONSIST
 OF A FABRIC MATERIAL, THEN IT SHOULD HAVE A PLAIN
 VALENCE (NOT SCALLOPED) TO MATCH THE OVERALL STYLE OF
 THE BUILDING.
  
 7. ACCORDING TO THE ELEVATIONS AND ELECTRICAL PLAN, ALL
 OF THE METERS ARE SHOWN ON THE EAST ELEVATION OF THE
 BUILDING. STAFF WOULD LIKE TO DISCUSS HOW THESE CAN BE
 SCREENED FROM VIEW THROUGH LANDSCAPING, PAINTING OF THE
 EQUIPMENT, ETC. PLEASE CONTACT ME TO DISCUSS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  