2017-06-28 07:31:47 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON |
| RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. |
| |
| 1. PROVIDE DESIGN WIND LOADS PER FBC CHPT 16. |
| FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 2. PROVIDE DETAILS FOR ALL WELDED CONNECTIONS. |
| 3. PROVIDE COPIES OF WELDER CERTIFCATIONS. |
| 2204.1 WELDING. |
| THE DETAILS OF DESIGN, WORKMANSHIP AND TECHNIQUE FOR |
| WELDING, INSPECTION OF WELDING AND QUALIFICATION OF |
| WELDING OPERATORS SHALL CONFORM TO THE REQUIREMENTS OF |
| THE SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207, |
| 2208, 2210 AND 2211 (SEE SECTION 2222 FOR HVHZ). |
| |
| 4. PROVIDE DETAILS FOR ALL BOLTED CONNECTIONS. |
| 2204.2 BOLTING. |
| THE DESIGN, INSTALLATION AND INSPECTION OF BOLTS SHALL |
| BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE |
| SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207, |
| 2210 AND 2211. |
| |
| 5. PROVIDE DETAIL OF BRACKET TO POST CONNECTION. |
| 6. SPECIFY DESIGN OFSPRAYED FIRE-RESISTANT MATERIALS |
| (SFRM) TO BE USED ON RATED BEAMS. |
| 7. PROVIDE PRODUCT DATA ON COMPRESSIBLE FILLER USED AT |
| FRAMED WALL. |
| 8. PROVIDE FLASHING DETAIL. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |