Plan Review Details - Permit 17060498
Plan Review Stops For Permit 17060498
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-30 Cont ID  
Sent By cthroop Date 2017-10-30 Time 15:21 Rev Time 0.00
Received By cthroop Date 2017-10-30 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By cthroop Date 2017-06-28 Time 07:06 Rev Time 0.00
Received By cthroop Date 2017-06-27 Time 16:35 Sent To E
Notes
2017-06-28 07:31:47BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE DESIGN WIND LOADS PER FBC CHPT 16.
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 2. PROVIDE DETAILS FOR ALL WELDED CONNECTIONS.
 3. PROVIDE COPIES OF WELDER CERTIFCATIONS.
 2204.1 WELDING.
 THE DETAILS OF DESIGN, WORKMANSHIP AND TECHNIQUE FOR
 WELDING, INSPECTION OF WELDING AND QUALIFICATION OF
 WELDING OPERATORS SHALL CONFORM TO THE REQUIREMENTS OF
 THE SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207,
 2208, 2210 AND 2211 (SEE SECTION 2222 FOR HVHZ).
  
 4. PROVIDE DETAILS FOR ALL BOLTED CONNECTIONS.
 2204.2 BOLTING.
 THE DESIGN, INSTALLATION AND INSPECTION OF BOLTS SHALL
 BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
 SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207,
 2210 AND 2211.
  
 5. PROVIDE DETAIL OF BRACKET TO POST CONNECTION.
 6. SPECIFY DESIGN OFSPRAYED FIRE-RESISTANT MATERIALS
 (SFRM) TO BE USED ON RATED BEAMS.
 7. PROVIDE PRODUCT DATA ON COMPRESSIBLE FILLER USED AT
 FRAMED WALL.
 8. PROVIDE FLASHING DETAIL.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-06-28 Cont ID  
Sent By jleahy Date 2017-06-28 Time 16:38 Rev Time 0.00
Received By jleahy Date 2017-06-28 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-30 Cont ID  
Sent By cthroop Date 2017-10-30 Time 15:22 Rev Time 0.00
Received By cthroop Date 2017-10-20 Time 13:50 Sent To I
Notes
2017-10-24 15:44:28TO MISC 2 BOX
2017-10-23 13:51:10RESUB ROUTED TO AAPONTE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-28 Cont ID  
Sent By jleahy Date 2017-06-28 Time 16:38 Rev Time 0.00
Received By jleahy Date 2017-06-13 Time 12:32 Sent To  
Notes
2017-06-16 13:43:54TO MISC 2 BOX
2017-06-14 12:32:43ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-24 Cont ID  
Sent By AA Date 2017-10-24 Time 15:43 Rev Time 0.00
Received By aaponte Date 2017-10-24 Time 10:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-06-16 Cont ID  
Sent By aaponte Date 2017-06-16 Time 13:43 Rev Time 0.00
Received By aaponte Date 2017-06-16 Time 13:43 Sent To  
Notes
2017-06-14 14:41:45ROUTED TO LINDA LOUIE