Plan Review Details - Permit 17060343
Plan Review Stops For Permit 17060343
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-24 Cont ID  
Sent By shill Date 2017-10-24 Time 10:10 Rev Time 0.00
Received By shill Date 2017-10-24 Time 10:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-15 Cont ID  
Sent By shill Date 2017-08-15 Time 10:14 Rev Time 0.00
Received By shill Date 2017-08-15 Time 09:49 Sent To  
Notes
2017-08-15 09:50:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, G101 CALLS OUT THE TWO 1 HOUR RATED WALLS
 (10' LENGTH ONLY) AT INTERSECTIONS, BUT THE WALLS LACK
 THE 1 HR DESIGNATION SHOWN FOR THE OTHER RATED WALLS.
 EITHER EXPLAIN LOGIC OF LEAVING THIS OFF OR ADD.
  
 2. SEE COMMENTS FOR REVISION 17060328 WHICH AFFECT THIS
 REVISION. FOR YOUR CONVENIENCE, THE ISSUE IS AS
 FOLLOWS:
  
 SHEET G101 SUBMITTED WITH REVISION NUMBER 17060343 IS
 SIGNED & SEALED DATED 7/2/17. IT INCLUDES REVISIONS
 1,2,4,5,10,30 AND 32 DATED 6/6/17.
  
 SHEET G101 SUBMITTED WITH REVISION NUMBER 17060328 IS
 SIGNED & SEALED DATED 7/2/17. IT INCLUDES REVISIONS 1,
 10, AND 11.
  
 IT IS NOT CLEAR WHY ONE IS UP TO REVISION 32 AND HAS AN
 EARLIER DATE THAN THE ONE WHICH INCLUDES REVISION 11.
 WHY IS REVISION 11 NOT INCLUDED IN THE VERSION
 SUBMITTED WITH 17060343? WHY DID THE ARCHITECT SIGN AND
 SEAL TWO DIFFERENT SHEETS G101? (THESE ARE HYPOTHETICAL
 QUESTIONS, NO NEED TO RESPOND IN WRITING.)
  
 PLEASE CORRELATE. IT IS OK, BUT NOT PREFERABLE, FOR THE
 SAME SHEET TO BE SUBMITTED WITH TWO DIFFERENT
 REVISIONS, BUT THEY DO NEED TO BE THE SAME. BOTH SHEETS
 SHOULD BE THE SAME AND INCLUDE ALL INFORMATION WHICH
 WAS INCORPORATED INTO ALL REVISIONS.
  
 PLEASE VERIFY THAT OTHER SHEETS ARE ALSO CONSISTENT.
  
 3. REMOVED - FIELD ISSUE
  
 4. RESPONSE LETTER STATES THAT THE 3 HR HORIZONTAL
 SLIDING FIRE DOOR SPECS ARE ATTACHED. I WAS UNABLE TO
 LOCATE, PLEASE PROVIDE. IF THIS HORIZONTAL SLIDING
 ASSEMBLY DOES NOT INCLUDE A DOOR IN COMPLIANCE WITH FBC
 B 1008 AND FBC A, PROVIDE INFORMATION VIA EMAIL PRIOR
 TO RESUBMITTAL.
  
 NOTE THAT ALL DOORS IN THE MEANS OF EGRESS NEED TO
 COMPLY WITH BOTH FBC BUILDING AND FBC ACCESSIBILITY.
  
 5. IT IS NOT CLEAR WHY THE OCCUPANTS IN THE OTHER
 TOWER, NOW LEGALLY ANOTHER PROPERTY, ARE DIRECTED
 THROUGH THE NEW TOWER AREA RATHER THAN EXITING OUT OF
 THE DOUBLE DOOR WHICH IS NEAR THE COMMUNICATING DOOR,
 FBC 107. IT DOES NOT NECESSARILY NEED TO BE CHANGED,
 BUT I CANNOT RECALL IF WE ALREADY DISCUSSED THIS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By shill Date 2017-06-26 Time 09:25 Rev Time 0.00
Received By shill Date 2017-06-26 Time 07:38 Sent To  
Notes
2017-06-26 09:26:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, THE TRANSMITTAL LETTER STATES THAT A
 NARRATIVE IS INCLUDED BUT I WAS UNABLE TO LOCATE A
 NARRATIVE FOR BUILDING, ONLY PLUMBING. DUE TO THE
 SIGNIFICANT NATURE OF THIS REVISION, AND DUE TO THE
 FACT THAT THE CHANGE AND THE REASON FOR THE CHANGE ARE
 NOT EASILY DETERMINED BY SOMEONE UNFAMILIAR WITH THE
 PROJECT, PLEASE PROVIDE A DETAILED NARRATIVE.
  
 2. A101C, (AS AN EXAMPLE; APPLIES TO OTHER SHEETS) THE
 LAST REVIEWED SHEET WAS REVISION NO 20 DATED 9/30/16.
 THREE REVISIONS ARE SHOWN (28,29,30) AND NOT ALL
 CHANGES ARE CLOUDED. NARRATIVE SHOULD BE CLEAR AS TO
 CHANGES, CHANGES SHOULD BE INDICATED ON EACH PAGES.
  
 2. FBC 2010 706.5.1, REVISE PLAN TO SHOW COMPLIANCE
 WITH ONE OF THE OPTIONS. THE PROPOSED NEW L-SHAPED 3
 HOUR FIRE WALL INTERSECTS TWO EXTERIOR WALLS.
  
 3. FBC 2010 706.5.2, REVISE PLAN TO INDICATE WHETHER OR
 NOT HORIZONTAL PROJECTION ELEMENTS ARE AFFECTED BY THIS
 CHANGE.
  
 4. REVISE OTHER SHEETS AFFECTED BY THIS CHANGE; SUCH AS
 G001.
  
 5. WALL ID TAGS DO NOT APPEAR TO HAVE BEEN REVISED TO
 REFLECT THE CHANGE FROM A 1 HOUR PARTITION OR BARRIER
 AND AN UNRATED WALL TO A 3 HOUR FIRE WALL. THE EXTERIOR
 PORTION OF THE PROPOSED NEW 3 HOUR FIRE WALL LACKS A
 WALL TAG, FBC 107, FBC 706. THE DETAIL FOR WALL TYPE N
 DOES NOT INCLUDE A 3 HOUR RATING, WALL TYPE P IS NOT A
 RATED WALL. REVISE DETAILS AND WALL TAGS TO SHOW A 3
 HOUR WALL WHERE ONE IS PROPOSED. IT APPEARS THAT OTHER
 (PORTION OF) WALLS ALSO REQUIRE A RATING WHERE THEY
 INTERSECT THE 3 HOUR WALL, SEE OTHER COMMENTS.
  
 A102A, STAIR 1 SHOWS AN UNRATED WALL, ISN'T THIS AN
 EXIT STAIR WITH A 2 HOUR REQUIREMENT? STAIRS 1 AND 2
 APPEAR TO SHOW A 0 RATING, BUT ELEVATOR 2-2 APPEARS TO
 SHOW A 2 HOUR REQUIREMNT. FBC 107, CLARIFY AND REVISE
 WALL ID TAGS AS NECESSARY.
  
 6. PROVIDE A SUMMARY OF UNIT DESIGNATION NAME CHANGES
 (A COLUMN WITH THE OLD UNIT NUMBER, A COLUMN WITH THE
 CORRESPONDING NEW UNIT NUMBER), FBC 107. PAGES WHICH
 WERE AFFECTED BY THE CHANGE WHICH WERE NOT REVISED WILL
 BE COVERED UNDER THIS SUMMARY PAGE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 13:55 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 13:55 Sent To  
Notes
2017-08-15 13:55:11NO CHANGES TO PLAN SINCE APPROVED BY JAKE LEAHY, STILL
 STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-17 Cont ID  
Sent By dharvey Date 2017-07-14 Time 07:37 Rev Time 0.00
Received By jleahy Date 2017-07-14 Time 07:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By wjolin Date 2017-08-16 Time 13:28 Rev Time 0.00
Received By wjolin Date 2017-08-16 Time 13:27 Sent To  
Notes
2017-08-16 13:28:51INSTALLATION LISTING REQUIREMENTS OF THE EQUIPMENT
 SHALL BE FOLLOWED AND FIELD VERIFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-28 Cont ID  
Sent By wjolin Date 2017-06-28 Time 07:37 Rev Time 0.00
Received By wjolin Date 2017-06-28 Time 07:23 Sent To  
Notes
2017-06-28 07:36:584850 LORING DRIVE
 TRACKING #17060343
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET G101:
  
 1) NEW 3-HOUR FIRE WALL WITH SLIDING FIRE DOOR IS ALSO
 IDENTIFIED ON THE PLAN AS "1-HOUR FIRE BARRIER
 OCCUPANCY SEPARATION."
 2) SUBMIT PRODUCT DATA FOR NEW 3-HOUR SLIDING FIRE
 DOOR. DOORS IN ASSEMBLY OCCUPANCIES ARE REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS (NORTH) AND BE
 EQUIPPED WITH PANIC/FIRE EXIT HARDWARE. HOW WILL THIS
 BE ACCOMPLISHED WITH THE SLIDING FIRE DOOR?
 3) AN ADDITIONAL EXIT SIGN IS NEEDED ON THE SOUTH SIDE
 OF THE 3-HOUR FIRE DOOR NOW THAT THE CLOSEST EXIT SIGN
 WILL BE OBSTRUCTED BY THE NEW DOOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-24 Cont ID  
Sent By shill Date 2017-10-24 Time 10:11 Rev Time 0.00
Received By shill Date 2017-10-11 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-24 Cont ID  
Sent By tklarge Date 2017-08-24 Time 11:00 Rev Time 0.00
Received By tklarge Date 2017-08-07 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-06 Cont ID  
Sent By hmoser Date 2017-08-06 Time 12:34 Rev Time 0.00
Received By hmoser Date 2017-06-20 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-08-06 Cont ID  
Sent By hmoser Date 2017-08-06 Time 12:34 Rev Time 0.00
Received By hmoser Date 2017-08-06 Time 07:49 Sent To  
Notes
2017-08-06 12:34:19CHECK FIRE DAMPERS ON NEW 3 HR WALL
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-19 Cont ID  
Sent By gjohnson Date 2017-10-19 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2017-10-19 Time 16:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-24 Cont ID  
Sent By tklarge Date 2017-08-24 Time 11:00 Rev Time 0.00
Received By tklarge Date 2017-08-23 Time 06:08 Sent To  
Notes
2017-08-24 10:09:461) SHT. A-412 - FLOOR PLAN DETAIL #1 - SHOW THE
 DISTANCE BETWEEN THE KITCHEN COUNTER AND THE WALL.
 CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE
 CABINETS, COUNTERTOPS, APPLIANCES OR WALLS SHALL BE AT
 LEAST 40 INCHES. REFER TO ELEVATION #20 ON A413.
 FHAG REQ.#7 (1) ( B).
 2) SHT. A-412 - FLOOR PLAN DETAIL #1 - SHOW THE
 REQUIRED 30 INCHES BY 48 INCHES CLEAR FLOOR SPACE FOR
 THE KITCHEN SINK AND SHOW THAT THE CLEAR FLOOR SPACE IS
 CENTERED ON THE FIXTURE.FHAG REQ. #7.
 3) A-412 - FLOOR PLAN DETAIL #1 - SHOW THE DIMENSION
 FROM THE CENTERLINE OF THE WATER CLOSETS TO THE
 ADJOINING WALL IN THE BATHROOMS (18 INCHES REQD.) AND
 ALSO SHOW THE DIMENSION FROM THE ADJOINING WALL NEXT TO
 THE WATER CLOSET TO THE EDGE OF THE LAVATORY. A MINIMUM
 OF 33 INCHES IS REQD. SEE FHAG FIGURE #7A.
 4) SHT. A-412 - SHOW ON THE PLAN THAT THE CLEAR FLOOR
 SPACE FOR THE LAVATORIES IS CENTERED ON THE FIXTURE.
 FHAG FIGURE #7C.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By tklarge Date 2017-06-29 Time 07:54 Rev Time 0.00
Received By tklarge Date 2017-06-29 Time 05:46 Sent To  
Notes
2017-06-29 06:00:081) SUBMIT A FLOOR PLAN FOR THE "G" UNIT SHOWING
 COMPLIANCE WITH THE REQUIREMENTS OF THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES 24 CFR 100.205. SHOW ALL
 REQUIRED CLEAR FLOOR SPACES AT PLUMBING FIXTURES AND
 SHOW THE DIMENSIONS (LXW) OF THE CLEAR FLOOR SPACES.
 2) INDICATE ON THE FLOOR PLAN FOR THE "G" UNIT WHAT
 DESIGN SPECIFICATION ("A" OR "B") FROM THE FHAG IS
 BEING USED FOR THE BATHROOMS IN THE "G" UNIT.
 3) CLEARLY SHOW ON THE FLOOR PLAN FOR THE UNIT WHICH
 BATHROOM(S) IS THE FHAG COMPLIANT BATHROOM(S).WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) PROVIDE A SANITARY AND WATER RISER DIAGRAM FOR THE
 "G" UNIT. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 5) SHT. P104B - THE TEXT IN THE LOWER RIGHT HAND CORNER
 CALLS OUT A "B" FLOOR PLAN BUT THE UNITS ARE ALL SHOWN
 AS "C" UNITS ON THE PLAN. CLARIFY.
 6) SHT.P210A - THE NARRATIVE REFERS TO A HOT WATER
 RETURN LINE ON THE TENTH FLOOR. CLEARLY IDENTIFY THE
 LOCATION OF THE HWR LINE ON THE PLAN BY CLOUDING. WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) SHT. 210B - THE NARRATIVE REFERS TO A HOT WATER
 RETURN LINE ON THE TENTH FLOOR. CLEARLY IDENTIFY THE
 LOCATION OF THE HWR LINE ON THE PLAN BY CLOUDING. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-10-24 Cont ID  
Sent By shill Date 2017-10-24 Time 10:10 Rev Time 0.00
Received By shill Date 2017-10-24 Time 10:10 Sent To  
Notes
***NONE***