Plan Review Details - Permit 17060276
Plan Review Stops For Permit 17060276
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By shill Date 2017-08-28 Time 14:19 Rev Time 0.00
Received By shill Date 2017-08-28 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-27 Time 11:07 Rev Time 0.00
Received By shill Date 2017-06-27 Time 11:07 Sent To  
Notes
2017-06-27 11:07:40SEE 17060272

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By jpearson Date 2017-08-28 Time 10:43 Rev Time 0.00
Received By jpearson Date 2017-08-28 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-22 Cont ID  
Sent By jpearson Date 2017-06-22 Time 10:48 Rev Time 0.00
Received By jpearson Date 2017-06-22 Time 10:48 Sent To  
Notes
2017-06-22 10:48:48CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ACCURATE LOAD CALCULATION. THE CURRENT LOAD
 CALCULATION USES THE SMALLER OF THE NON-CONCURRENT
 LOAD, CODE REQUIRES THE USE OF THE LARGEST OF THE TWO
 LOADS. NEC 220.60
 2. PROVIDE DETAILS OF ALL CIRCUITS WIRED THROUGH THE
 LIGHTING CONTROL PANEL TO COMPLY WITH LIGHTING AND
 RECEPTACLE CONTROL PER THE NOTES ON PLAN. FBC 107.2.1
 3. PLAN SHOWS THAT BOTH ELECTRICAL ROOMS ARE FED FROM
 THE SAME MAIN, MAIN #5. PROVIDE LOAD CALCULATION FOR
 THE MAIN SERVICE TO SHOW SUFFICIENT SIZE FOR THE
 ADDITIONAL LOAD. NEC 220
 4. PROVIDE SHORT CIRCUIT CALCULATION AT
 METER/DISCONNECT TO CONFIRM AIC SIZING REQUIREMENT OF
 SERVICE EQUIPMENT. NEC 110.9, 110.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By pleduc Date 2017-08-23 Time   Rev Time 0.00
Received By pleduc Date 2017-08-23 Time 11:30 Sent To  
Notes
2017-08-23 12:34:152ND REVIEW
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND OPERATIONAL ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-23 Cont ID  
Sent By pleduc Date 2017-06-23 Time   Rev Time 0.00
Received By pleduc Date 2017-06-23 Time 11:28 Sent To  
Notes
2017-06-23 11:28:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND OPERATIONAL ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-29 Cont ID  
Sent By gjohnson Date 2017-08-29 Time 17:57 Rev Time 0.00
Received By gjohnson Date 2017-08-16 Time 09:50 Sent To  
Notes
2017-08-18 09:51:04B31
 *TRAVELLING TOGETHER - 17060272, 17060274, 17060275,
 17060276, 17060277, 17060278**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-29 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-07 Time 08:54 Sent To  
Notes
2017-06-21 14:49:55B30
 *TRAVELLING TOGETHER - 17060272, 17060274, 17060275,
 17060276, 17060277, 17060278**

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-29 Cont ID  
Sent By ccole Date 2017-08-29 Time 14:59 Rev Time 0.00
Received By ccole Date 2017-08-29 Time 14:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By ccole Date 2017-06-29 Time 16:26 Rev Time 0.00
Received By ccole Date 2017-06-29 Time 16:24 Sent To  
Notes
2017-06-29 16:26:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060276
 6/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A NON-COMBUSTIBLE DOOR IS REQUIRED FOR THE AC
 CLOSET. SHEET A901 INDICATES A WOOD-LOUVERED DOOR- SEE
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION & SECTION
 602.2.1 FBC-14 MECHANICAL.
  
 2) VERIFY THE O/A INTAKE OPENING IS IN COMPLIANCE WITH
 SECTIONS 401.4 AND 401.5.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 NEW CONDENSER TO THE EXISTING AC ROOF STANDS. IF
 SUBMITTING AN NOA PLEASE CIRCLE, HIGHLIGHT, OR
 OTHERWISE MARK ALL APPLICABLE DESIGN PRESSURES, STAND
 DETAILS, AND FASTENERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-08-29 Cont ID  
Sent By gjohnson Date 2017-08-29 Time 17:57 Rev Time 0.00
Received By gjohnson Date 2017-08-29 Time 17:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-28 Cont ID  
Sent By gjohnson Date 2017-08-28 Time 17:49 Rev Time 0.00
Received By gjohnson Date 2017-08-28 Time 17:49 Sent To  
Notes
2017-08-28 17:49:592ND REVIEW: FBC 2014 5TH EDITION
  
 PREVIOUS COMMENT NOT COMPLIED1. PLUMBING COMMENTS: THE
 BREAKROOM/ KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2
 AND 606.3
  
 PREVIOUS COMMENT NOT COMPLIED 2. THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC
 ACC 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 NEW COMMENT
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW. FBC ACC 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By gjohnson Date 2017-06-26 Time 11:51 Rev Time 0.00
Received By gjohnson Date 2017-06-26 Time 11:51 Sent To  
Notes
2017-06-26 11:53:261ST REVIEW: FBC 2014 5TH EDITION
  
 1. PLUMBING COMMENTS: THE BREAKROOM/ KITCHEN SINK SHALL
 COMPLY WITH FBC ACC 606.2 AND 606.3
  
 2. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE. PER FBC ACC 609.4 POSITION OF GRAB
 BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  